451 451  * If there is a signal “Charge request” and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the charging contactor and the allow charging contactor close;
452 452  * If the signal “Charge request” disappears, the allow charging contactor opens and after the delay time T,,off,, the charging contactor opens;
453 453  * If in the process of charging the voltage on the cell exceeds the “Ready to charge” level, the allow charging contactor opens (while the charging contactor remains closed);
454 -* If errors in the list above occur the charging contactor and allow charging contactor open.
454 +* If errors from the "Errors 1, 2 ..." bitfields occur the charging contactor and allow charging contactor open.
455 455  
456 456  (% class="box infomessage" %)
457 457  (((
... ... @@ -488,26 +488,8 @@
488 488  * On charger disconnected – load is connected when there is no signal “Charger connected”;
489 489  * On discharge request – load is connected when there is signal “Discharge request”.
490 490  
491 -When the algorithm "**Always on**" is selected, the discharging contactor is always closed. If at least one of the errors appears:
491 +When the algorithm "**Always on**" is selected, the discharging contactor is always closed. If at least one of the errors from the "Errors 1, 2 ..." bitfields appears or one of the signals:
492 492  
493 -* Undervoltage;
494 -* Overvoltage (optional);
495 -* Overcurrent;
496 -* High temperature (DCH);
497 -* Low temperature (DCH) (optional);
498 -* HYG offline (optional);
499 -* Combilift offline (optional);
500 -* Spirit offline (optional);
501 -* Spirit charger error (optional);
502 -* Short circuit (optional);
503 -* High contactor temperature (optional);
504 -* Unallowable charging;
505 -* DCH contactor cycles error;
506 -* Precharge error (optional);
507 -* Critical error
508 -
509 -or one of the signals:
510 -
511 511  * Service reset
512 512  * Power down request
513 513  * Inhibit discharging
... ... @@ -516,13 +516,13 @@
516 516  
517 517  If the algorithm "**On charger disconnected**" is selected, the control is performed as follows:
518 518  
519 -* if there is no signal “Charger connected”, the charging contactor is open and there are no errors (see the list above), then through the delay time T,,on,, the discharging contactor closes;
520 -* If the signal “Charger connected” appears or errors occur (see the list above), then after the delay time T,,off,, the discharging contactor opens.
501 +* if there is no signal “Charger connected”, the charging contactor is open and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the discharging contactor closes;
502 +* If the signal “Charger connected” appears or errors occur (see the "Errors 1, 2 ..." bitfields), then after the delay time T,,off,, the discharging contactor opens.
521 521  
522 522  When the "**On discharge request**" algorithm selected, the control is performed as follows:
523 523  
524 524  * if there is signal “Discharge request”, the charging contactor is open and there are no errors (see the list above), then through the delay time T,,on,, the discharging contactor closes;
525 -* If the signal “Discharge request” disappears or errors occur (see the list above), then after the delay time T,,off,, the discharging contactor opens.