... ... @@ -431,8 +431,24 @@
431 431  * On charger connected – charging is allowed when there is a signal “Charger connected”;
432 432  * On charge request – charging is allowed when there is a signal “Charge request”.
433 433  
434 -If the "**Always on**" algorithm is selected, the charging contactor and the allow charging contactor are always closed. If at least one of the errors from the "Errors 1, 2 ..." bitfields appears or one of the signals:
434 +If the "**Always on**" algorithm is selected, the charging contactor and the allow charging contactor are always closed. If at least one of the errors appears:
435 435  
436 +* Overvoltage;
437 +* Overcurrent;
438 +* High temperature (CH);
439 +* Low temperature (CH);
440 +* HYG offline (optional);
441 +* Combilift offline (optional);
442 +* Spirit offline (optional);
443 +* Spirit charger error (optional);
444 +* Short circuit (optional);
445 +* High contactor temperature (optional);
446 +* CH contactor cycles error;
447 +* Precharge error (optional);
448 +* Critical error
449 +
450 +or one of the signals:
451 +
436 436  * Service reset;
437 437  * Power down request;
438 438  * Inhibit charging,
... ... @@ -441,14 +441,14 @@
441 441  
442 442  When the algorithm "**On charger connected**" is selected, the control is performed as follows:
443 443  
444 -* If there is a signal “Charger connected” and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the charging contactor and the allow charging contactor close;
460 +* If there is a signal “Charger connected” and there are no errors (see the list above), then through the delay time T,,on,, the charging contactor and the allow charging contactor close;
445 445  * If the signal “Charger connected” disappears, the allow charging contactor opens and after the delay time T,,off,, the charging contactor opens;
446 446  * If in the process of charging the voltage on the cell exceeds the “Ready to charge” level, the allow charging contactor opens (while the charging contactor remains closed);
447 -* If errors from the "Errors 1, 2 ..." bitfields occur the charging contactor and allow charging contactor open.
463 +* If errors in the list above occur the charging contactor and allow charging contactor open.
448 448  
449 449  When the "**On charge request**" algorithm selected, the control is performed as follows:
450 450  
451 -* If there is a signal “Charge request” and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the charging contactor and the allow charging contactor close;
467 +* If there is a signal “Charge request” and there are no errors (see the list above), then through the delay time T,,on,, the charging contactor and the allow charging contactor close;
452 452  * If the signal “Charge request” disappears, the allow charging contactor opens and after the delay time T,,off,, the charging contactor opens;
453 453  * If in the process of charging the voltage on the cell exceeds the “Ready to charge” level, the allow charging contactor opens (while the charging contactor remains closed);
454 454  * If errors in the list above occur the charging contactor and allow charging contactor open.