... ... @@ -431,13 +431,13 @@
431 431  * On charger connected – charging is allowed when there is a signal “Charger connected”;
432 432  * On charge request – charging is allowed when there is a signal “Charge request”.
433 433  
434 -If the "**Always on**" algorithm is selected, the charging contactor is always closed. If at least one of the errors from the "Errors 1, 2 ..." bitfield appears or one of the signals:
434 +If the "**Always on**" algorithm is selected, the charging contactor is always closed. If at least one of the errors from the "Errors 1, 2 ..." bitfields appears or one of the signals:
435 435  
436 436  * Service reset;
437 437  * Power down request;
438 438  * Inhibit charging,
439 439  
440 -contactor are open (no current flows).
440 +contactor opens (no current flows).
441 441  
442 442  When the algorithm "**On charger connected**" is selected, the control is performed as follows:
443 443