... ... @@ -431,29 +431,13 @@
431 431  * On charger connected – charging is allowed when there is a signal “Charger connected”;
432 432  * On charge request – charging is allowed when there is a signal “Charge request”.
433 433  
434 -If the "**Always on**" algorithm is selected, the charging contactor and the allow charging contactor are always closed. If at least one of the errors appears:
434 +If the "**Always on**" algorithm is selected, the charging contactor is always closed. If at least one of the errors from the "Errors 1, 2 ..." bitfield appears or one of the signals:
435 435  
436 -* Overvoltage;
437 -* Overcurrent;
438 -* High temperature (CH);
439 -* Low temperature (CH);
440 -* HYG offline (optional);
441 -* Combilift offline (optional);
442 -* Spirit offline (optional);
443 -* Spirit charger error (optional);
444 -* Short circuit (optional);
445 -* High contactor temperature (optional);
446 -* CH contactor cycles error;
447 -* Precharge error (optional);
448 -* Critical error
449 -
450 -or one of the signals:
451 -
452 452  * Service reset;
453 453  * Power down request;
454 454  * Inhibit charging,
455 455  
456 -both contactors are open (no current flows).
440 +contactor are open (no current flows).
457 457  
458 458  When the algorithm "**On charger connected**" is selected, the control is performed as follows: