... ... @@ -320,15 +320,31 @@
320 320  
321 321  In “Always on” mode main contactor closes if all the following is true:
322 322  
323 -* Other contactors are open;
324 -* There are no errors from the "Errors 1, 2 ..." bitfileds.
323 +* Charging contactor is open;
324 +* Discharging contactor is open;
325 +* There are no errors from the list below:
326 +** Overcurrent;
327 +** Undervoltage;
328 +** Overvoltage;
329 +** High temperature (CH);
330 +** High temperature (DCH);
331 +** Unallowable charging;
332 +** Critical error.
325 325  
326 326  In “Always on” mode main contactor opens if all the following is true:
327 327  
328 -* Other contactors are open;
329 -* There is an error from the the "Errors 1, 2 ..." bitfileds.
336 +* Charging contactor is open;
337 +* Discharging contactor is open;
338 +* There is an error from the list below:
339 +** Overcurrent;
340 +** Undervoltage;
341 +** Overvoltage;
342 +** High temperature (CH);
343 +** High temperature (DCH);
344 +** Unallowable charging;
345 +** Critical error.
330 330  
331 -In “Automatic” mode, the main contactor closes by internal algorithms at the same time with other contactors.
347 +In “Automatic” mode, the main contactor closes by internal charging and discharging algorithms at the same time with Precharging, Charging and Discharging contactors.
332 332  
333 333  In “On demand” mode, the main contactor closes by external the “Close Main contactor” request.
334 334