... ... @@ -320,31 +320,15 @@
320 320  
321 321  In “Always on” mode main contactor closes if all the following is true:
322 322  
323 -* Charging contactor is open;
324 -* Discharging contactor is open;
325 -* There are no errors from the list below:
326 -** Overcurrent;
327 -** Undervoltage;
328 -** Overvoltage;
329 -** High temperature (CH);
330 -** High temperature (DCH);
331 -** Unallowable charging;
332 -** Critical error.
323 +* Other contactors are open;
324 +* There are no errors from the "Errors 1, 2 ..." bitfileds.
333 333  
334 334  In “Always on” mode main contactor opens if all the following is true:
335 335  
336 -* Charging contactor is open;
337 -* Discharging contactor is open;
338 -* There is an error from the list below:
339 -** Overcurrent;
340 -** Undervoltage;
341 -** Overvoltage;
342 -** High temperature (CH);
343 -** High temperature (DCH);
344 -** Unallowable charging;
345 -** Critical error.
328 +* Other contactors are open;
329 +* There is an error from the the "Errors 1, 2 ..." bitfileds.
346 346  
347 -In “Automatic” mode, the main contactor closes by internal charging and discharging algorithms at the same time with Precharging, Charging and Discharging contactors.
331 +In “Automatic” mode, the main contactor closes by internal algorithms at the same time with other contactors.
348 348  
349 349  In “On demand” mode, the main contactor closes by external the “Close Main contactor” request.
350 350  
... ... @@ -447,24 +447,8 @@
447 447  * On charger connected – charging is allowed when there is a signal “Charger connected”;
448 448  * On charge request – charging is allowed when there is a signal “Charge request”.
449 449  
450 -If the "**Always on**" algorithm is selected, the charging contactor and the allow charging contactor are always closed. If at least one of the errors appears:
434 +If the "**Always on**" algorithm is selected, the charging contactor and the allow charging contactor are always closed. If at least one of the errors from the "Errors 1, 2 ..." bitfields appears or one of the signals:
451 451  
452 -* Overvoltage;
453 -* Overcurrent;
454 -* High temperature (CH);
455 -* Low temperature (CH);
456 -* HYG offline (optional);
457 -* Combilift offline (optional);
458 -* Spirit offline (optional);
459 -* Spirit charger error (optional);
460 -* Short circuit (optional);
461 -* High contactor temperature (optional);
462 -* CH contactor cycles error;
463 -* Precharge error (optional);
464 -* Critical error
465 -
466 -or one of the signals:
467 -
468 468  * Service reset;
469 469  * Power down request;
470 470  * Inhibit charging,
... ... @@ -473,17 +473,17 @@
473 473  
474 474  When the algorithm "**On charger connected**" is selected, the control is performed as follows:
475 475  
476 -* If there is a signal “Charger connected” and there are no errors (see the list above), then through the delay time T,,on,, the charging contactor and the allow charging contactor close;
444 +* If there is a signal “Charger connected” and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the charging contactor and the allow charging contactor close;
477 477  * If the signal “Charger connected” disappears, the allow charging contactor opens and after the delay time T,,off,, the charging contactor opens;
478 478  * If in the process of charging the voltage on the cell exceeds the “Ready to charge” level, the allow charging contactor opens (while the charging contactor remains closed);
479 -* If errors in the list above occur the charging contactor and allow charging contactor open.
447 +* If errors from the "Errors 1, 2 ..." bitfields occur the charging contactor and allow charging contactor open.
480 480  
481 481  When the "**On charge request**" algorithm selected, the control is performed as follows:
482 482  
483 -* If there is a signal “Charge request” and there are no errors (see the list above), then through the delay time T,,on,, the charging contactor and the allow charging contactor close;
451 +* If there is a signal “Charge request” and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the charging contactor and the allow charging contactor close;
484 484  * If the signal “Charge request” disappears, the allow charging contactor opens and after the delay time T,,off,, the charging contactor opens;
485 485  * If in the process of charging the voltage on the cell exceeds the “Ready to charge” level, the allow charging contactor opens (while the charging contactor remains closed);
486 -* If errors in the list above occur the charging contactor and allow charging contactor open.
454 +* If errors from the "Errors 1, 2 ..." bitfields occur the charging contactor and allow charging contactor open.
487 487  
488 488  (% class="box infomessage" %)
489 489  (((
... ... @@ -520,26 +520,8 @@
520 520  * On charger disconnected – load is connected when there is no signal “Charger connected”;
521 521  * On discharge request – load is connected when there is signal “Discharge request”.
522 522  
523 -When the algorithm "**Always on**" is selected, the discharging contactor is always closed. If at least one of the errors appears:
491 +When the algorithm "**Always on**" is selected, the discharging contactor is always closed. If at least one of the errors from the "Errors 1, 2 ..." bitfields appears or one of the signals:
524 524  
525 -* Undervoltage;
526 -* Overvoltage (optional);
527 -* Overcurrent;
528 -* High temperature (DCH);
529 -* Low temperature (DCH) (optional);
530 -* HYG offline (optional);
531 -* Combilift offline (optional);
532 -* Spirit offline (optional);
533 -* Spirit charger error (optional);
534 -* Short circuit (optional);
535 -* High contactor temperature (optional);
536 -* Unallowable charging;
537 -* DCH contactor cycles error;
538 -* Precharge error (optional);
539 -* Critical error
540 -
541 -or one of the signals:
542 -
543 543  * Service reset
544 544  * Power down request
545 545  * Inhibit discharging
... ... @@ -548,13 +548,13 @@
548 548  
549 549  If the algorithm "**On charger disconnected**" is selected, the control is performed as follows:
550 550  
551 -* if there is no signal “Charger connected”, the charging contactor is open and there are no errors (see the list above), then through the delay time T,,on,, the discharging contactor closes;
552 -* If the signal “Charger connected” appears or errors occur (see the list above), then after the delay time T,,off,, the discharging contactor opens.
501 +* if there is no signal “Charger connected”, the charging contactor is open and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the discharging contactor closes;
502 +* If the signal “Charger connected” appears or errors occur (see the "Errors 1, 2 ..." bitfields), then after the delay time T,,off,, the discharging contactor opens.
553 553  
554 554  When the "**On discharge request**" algorithm selected, the control is performed as follows:
555 555  
556 556  * if there is signal “Discharge request”, the charging contactor is open and there are no errors (see the list above), then through the delay time T,,on,, the discharging contactor closes;
557 -* If the signal “Discharge request” disappears or errors occur (see the list above), then after the delay time T,,off,, the discharging contactor opens.
507 +* If the signal “Discharge request” disappears or errors occur (see the "Errors 1, 2 ..." bitfields), then after the delay time T,,off,, the discharging contactor opens.
558 558  
559 559  (% class="box infomessage" %)
560 560  (((