... ... @@ -320,31 +320,15 @@
320 320  
321 321  In “Always on” mode main contactor closes if all the following is true:
322 322  
323 -* Charging contactor is open;
324 -* Discharging contactor is open;
325 -* There are no errors from the list below:
326 -** Overcurrent;
327 -** Undervoltage;
328 -** Overvoltage;
329 -** High temperature (CH);
330 -** High temperature (DCH);
331 -** Unallowable charging;
332 -** Critical error.
323 +* Other contactors are open;
324 +* There are no errors from the "Errors 1, 2 ..." bitfileds.
333 333  
334 334  In “Always on” mode main contactor opens if all the following is true:
335 335  
336 -* Charging contactor is open;
337 -* Discharging contactor is open;
338 -* There is an error from the list below:
339 -** Overcurrent;
340 -** Undervoltage;
341 -** Overvoltage;
342 -** High temperature (CH);
343 -** High temperature (DCH);
344 -** Unallowable charging;
345 -** Critical error.
328 +* Other contactors are open;
329 +* There is an error from the the "Errors 1, 2 ..." bitfileds.
346 346  
347 -In “Automatic” mode, the main contactor closes by internal charging and discharging algorithms at the same time with Precharging, Charging and Discharging contactors.
331 +In “Automatic” mode, the main contactor closes by internal algorithms at the same time with other contactors.
348 348  
349 349  In “On demand” mode, the main contactor closes by external the “Close Main contactor” request.