Summary

Details

Page properties
Content
... ... @@ -1,5 +1,5 @@
1 1  (% data-numbered-headings-start="3" style="--numbered-headings-start: 2;font-size: 0px;color: rgba(0, 0, 0, 0.0);margin-bottom: 0px; margin-top: 0px;" %)
2 -= Configuration =
2 += Settings =
3 3  
4 4  (% data-numbered-headings-start="3" style="--numbered-headings-start: 2;font-size: 0px;color: rgba(0, 0, 0, 0.0);margin-bottom: 0px; margin-top: 0px;" %)
5 5  == Control ==
... ... @@ -165,10 +165,7 @@
165 165  
166 166  * the battery SOC is greater than the “Tolerant SOC” during the “Delay before clearing the signal” time.
167 167  
168 -(% class="box infomessage" %)
169 -(((
170 170  The "Low SOC signal" is indicative and can be output to a discrete output or a power switch.
171 -)))
172 172  
173 173  === High charging current (signal) ===
174 174  
... ... @@ -193,10 +193,7 @@
193 193  
194 194  * the measured current is less than the “Tolerant charging current” value during the “Delay before clearing the signal” time.
195 195  
196 -(% class="box infomessage" %)
197 -(((
198 198  The "High charging current" signal is indicative and can be output to a discrete output or a power switch.
199 -)))
200 200  
201 201  === Charge map ===
202 202  
... ... @@ -213,18 +213,18 @@
213 213  * Enable – a flag to start calculation of the charge current limit;
214 214  * Maximum charge current – a maximum allowable value of the charge current (under normal conditions), A;
215 215  * Rate of change – a rate of change the current limit to a new value (0 is for immediate change), A/s;
216 -* Option 1: Limit charge current by the battery SOC and temperature – a flag to enable correction of maximum allowable charging current** Kcs** depending on SOC and battery temperature;
210 +* Option 1: Limit charge current by the battery SOC and temperature – a flag to enable correction of maximum allowable charging current Kcs depending on SOC and battery temperature;
217 217  * Option 1: SOC x Temperature x Factor – the dependence of the correction factor on SOC and battery temperature;
218 -* Option 2: Limit charge current by the contactor temperature – a flag to enable correction of maximum allowable charging current **Kcc** depending on contactor temperature;
212 +* Option 2: Limit charge current by the contactor temperature – a flag to enable correction of maximum allowable charging current Kcc depending on contactor temperature;
219 219  * Option 2: Contactor temperature x Factor – the dependence of the correction factor on SOC and contactor temperature;
220 -* Option 3: Limit charge current by the maximum cell voltage - a flag to enable correction of maximum allowable charging current **Kcv** depending on maximum cell voltage;
214 +* Option 3: Limit charge current by the maximum cell voltage - a flag to enable correction of maximum allowable charging current Kcv depending on maximum cell voltage;
221 221  * Option 3: Cell voltage x Factor – the dependence of the correction factor on maximum cell voltage;
222 -* Option 4: Limit charge current by the cell temperature - a flag to enable correction of maximum allowable charging current **Kct** depending on maximum cell temperature;
216 +* Option 4: Limit charge current by the cell temperature - a flag to enable correction of maximum allowable charging current Kct depending on maximum cell temperature;
223 223  * Option 4: Cell temperature x Factor – the dependence of the correction factor on maximum cell temperature.
224 224  
225 225  Value of the charge current limit at given SOC, temperature, contactors temperature, maximum cell voltage and maximum cell temperature is calculated as follows:
226 226  
227 -**Charge current limit = Maximum charge current × Kcs × Kcc × Kcv × Kct**
221 +Charging current limit = Maximum charging current × Kcs × Kcc × Kcv × Kct
228 228  
229 229  === Discharge map ===
230 230  
... ... @@ -241,18 +241,18 @@
241 241  * Enable – a flag to start calculation of the discharge current limit;
242 242  * Maximum discharge current – a maximum allowable value of the discharge current (under normal conditions), A;
243 243  * Rate of change – a rate of change the current limit to a new value (0 is for immediate change), A/s;
244 -* Option 1: Limit discharging current by the battery SOC and temperature – a flag to enable correction of maximum allowable discharging current **Kds **depending on SOC and temperature;
238 +* Option 1: Limit discharging current by the battery SOC and temperature – a flag to enable correction of maximum allowable discharging current Kds depending on SOC and temperature;
245 245  * Option 1: SOC x Temperature x Factor – the dependence of the correction factor on SOC and battery temperature;
246 -* Option 2: Limit discharge current by the contactor temperature – a flag to enable correction of maximum allowable discharging current **Kdc** depending on contactor temperature;
240 +* Option 2: Limit discharge current by the contactor temperature – a flag to enable correction of maximum allowable discharging current Kdc depending on contactor temperature;
247 247  * Option 2: Contactor temperature x Factor – the dependence of the correction factor on SOC and contactor temperature;
248 -* Option 3: Limit discharge current by the cell voltage - a flag to enable correction of maximum allowable discharging current **Kdv** depending on minimum cell voltage;
242 +* Option 3: Limit discharge current by the cell voltage - a flag to enable correction of maximum allowable discharging current Kdv depending on minimum cell voltage;
249 249  * Option 3: Cell voltage x Factor – the dependence of the correction factor on minimum cell voltage;
250 -* Option 4: Limit discharge current by the cell temperature - a flag to enable correction of maximum allowable discharging current **Kdt** depending on maximum cell temperature;
244 +* Option 4: Limit discharge current by the cell temperature - a flag to enable correction of maximum allowable discharging current Kdt depending on maximum cell temperature;
251 251  * Option 4: Cell voltage x Factor – the dependence of the correction factor on minimum cell temperature.
252 252  
253 253  Value of the discharge current limit at given SOC, temperature, contactors temperature, minimum cell voltage and maximum cell temperature is calculated as follows:
254 254  
255 -**Discharge current limit = Maximum discharge current × Kds × Kdc × Kdv × Kdt**
249 +Discharging current limit = Maximum discharging current × Kds × Kdc × Kdv × Kdt
256 256  
257 257  === Charge map (PEAK & CONTINUOUS) ===
258 258  
... ... @@ -348,11 +348,6 @@
348 348  
349 349  In “On demand” mode, the main contactor closes by external the “Close Main contactor” request.
350 350  
351 -(% class="box infomessage" %)
352 -(((
353 -**Note: **when errors occur in the system, the **Main **contactor opens either immediately or with the delay T,,off,, (depends on the settings described below).
354 -)))
355 -
356 356  To change the parameters of the main contactor, select the "Control → Main contactor" section:
357 357  
358 358  [[image:1735064488658-863.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="112" width="800"]]
... ... @@ -391,7 +391,7 @@
391 391  
392 392  === Discharging status ===
393 393  
394 -To change the parameters of discharging process status, select the "Control → Discharging status" section:
383 +To change the parameters of charging process status, select the "Control → Discharging status" section:
395 395  
396 396  [[image:1735064980481-209.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="102" width="800"]]In this section:
397 397  
... ... @@ -407,8 +407,6 @@
407 407  
408 408  BMS Main 3 device detects errors while pre-charging the load capacity by monitoring the current and voltage difference before and after contactors. Also BMS can measure the power dissipated on precharge resistor and generate an error if it greater than configured limit.
409 409  
410 -TBA
411 -
412 412  To change the parameters of precharge contactor, select the "Control → Precharge" section:
413 413  
414 414  [[image:1735065073836-743.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="160" width="800"]]
... ... @@ -432,9 +432,9 @@
432 432  * voltages before and after contactors are not equal after "Number of precharging attempts";
433 433  * power dissipated on the precharge resistor is above the maximum value during the “Delay before setting the 'Precharge error' when checking power” time.
434 434  
435 -(% class="box warningmessage" %)
422 +(% class="box infomessage" %)
436 436  (((
437 -Behavior of contactors at “Precharge error” is configured in corresponding contactor settings!
424 +If there is the “Precharge error”, **charging **and **discharging **contactors open.
438 438  )))
439 439  
440 440  === Charge ===
... ... @@ -487,7 +487,7 @@
487 487  
488 488  (% class="box infomessage" %)
489 489  (((
490 -**Note: **when errors occur in the system, the **Charge **contactor opens either immediately or with the delay T,,off,, (depends on the settings described below).
477 +Note: when errors occur in the system, the **charging **contactor opens either immediately or with the delay T,,off,, (depends on the settings described below).
491 491  )))
492 492  
493 493  To change the parameters of the battery charge control algorithm, select the "Control → Charge" section:
... ... @@ -558,7 +558,7 @@
558 558  
559 559  (% class="box infomessage" %)
560 560  (((
561 -**Note: **when errors occur in the system, the **Discharge **contactor opens either immediately or with the delay T,,off,, (depends on the settings described below).
548 +**Note:** in case of errors in the system operation, **discharging **contactor opens either immediately or with a delay T,,off,, (depends on the settings described below).
562 562  )))
563 563  
564 564  The device supports controlling the precharging contactor. The duration of switching on the precharging contactor before closing the discharging (load) contactor is adjusted.
... ... @@ -593,13 +593,6 @@
593 593  * Independent (Always) - Charge/Discharge contactor is always closed if there is no errors;
594 594  * Independent (on Charge request or Discharge request) - Charge/Discharge contactor is based on its own controller that listen to Charge and Discharge requests and closes if one of these signals occurs.
595 595  
596 -TBA
597 -
598 -(% class="box infomessage" %)
599 -(((
600 -**Note: **when errors occur in the system, the **Charge/Discharge **contactor opens either immediately or with the delay T,,off,, (depends on the settings described below).
601 -)))
602 -
603 603  The charging/discharging contactor control is configured in the “Control – Charge/Discharge” section:
604 604  
605 605  [[image:1735122153011-166.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="162" width="800"]]
... ... @@ -632,11 +632,6 @@
632 632  * the battery voltage is out of range;
633 633  * the battery system errors are detected.
634 634  
635 -(% class="box infomessage" %)
636 -(((
637 -**Note: **when errors occur in the system, the **Discharge (AUX) **contactor opens either immediately or with the delay T,,off,, (depends on the settings described below).
638 -)))
639 -
640 640  To change the parameters of the powering of external equipment, select the "Control → Discharge (AUX)" section:
641 641  
642 642  [[image:1735066190419-838.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="161" width="800"]]
... ... @@ -699,7 +699,7 @@
699 699  * Minimum cell voltage to start balancing, V;
700 700  * Voltage deviation to start balancing;
701 701  * Voltage deviation to stop balancing;
702 -* Voltage for forced balancing – if cell voltage is above this value, it will start discharging through balancing resistor;
677 +* Voltage for forced balancing – if cell voltage is above this value, it will start discharge through balancing resistor;
703 703  * Maximum allowable temperature of BMS Logic devices, ºC;
704 704  * Command to discharge all cells – a flag to force the balancing of all cells.
705 705  
... ... @@ -825,7 +825,7 @@
825 825  
826 826  (% class="box warningmessage" %)
827 827  (((
828 -If there is the “High voltage fault”, **the “Critical error” is generated.**
803 +If there is the “High voltage fault”, **the “Critical error” is generated and all contactors open.**
829 829  )))
830 830  
831 831  === Cell analysis ===