... ... @@ -165,10 +165,7 @@
165 165  
166 166  * the battery SOC is greater than the “Tolerant SOC” during the “Delay before clearing the signal” time.
167 167  
168 -(% class="box infomessage" %)
169 -(((
170 170  The "Low SOC signal" is indicative and can be output to a discrete output or a power switch.
171 -)))
172 172  
173 173  === High charging current (signal) ===
174 174  
... ... @@ -193,10 +193,7 @@
193 193  
194 194  * the measured current is less than the “Tolerant charging current” value during the “Delay before clearing the signal” time.
195 195  
196 -(% class="box infomessage" %)
197 -(((
198 198  The "High charging current" signal is indicative and can be output to a discrete output or a power switch.
199 -)))
200 200  
201 201  === Charge map ===
202 202  
... ... @@ -224,7 +224,7 @@
224 224  
225 225  Value of the charge current limit at given SOC, temperature, contactors temperature, maximum cell voltage and maximum cell temperature is calculated as follows:
226 226  
227 -**Charging current limit = Maximum charging current × Kcs × Kcc × Kcv × Kct**
221 +Charging current limit = Maximum charging current × Kcs × Kcc × Kcv × Kct
228 228  
229 229  === Discharge map ===
230 230  
... ... @@ -252,7 +252,7 @@
252 252  
253 253  Value of the discharge current limit at given SOC, temperature, contactors temperature, minimum cell voltage and maximum cell temperature is calculated as follows:
254 254  
255 -**Discharging current limit = Maximum discharging current × Kds × Kdc × Kdv × Kdt**
249 +Discharging current limit = Maximum discharging current × Kds × Kdc × Kdv × Kdt
256 256  
257 257  === Charge map (PEAK & CONTINUOUS) ===
258 258  
... ... @@ -391,7 +391,7 @@
391 391  
392 392  === Discharging status ===
393 393  
394 -To change the parameters of discharging process status, select the "Control → Discharging status" section:
388 +To change the parameters of charging process status, select the "Control → Discharging status" section:
395 395  
396 396  [[image:1735064980481-209.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="102" width="800"]]In this section:
397 397  
... ... @@ -407,8 +407,6 @@
407 407  
408 408  BMS Main 3 device detects errors while pre-charging the load capacity by monitoring the current and voltage difference before and after contactors. Also BMS can measure the power dissipated on precharge resistor and generate an error if it greater than configured limit.
409 409  
410 -TBA
411 -
412 412  To change the parameters of precharge contactor, select the "Control → Precharge" section:
413 413  
414 414  [[image:1735065073836-743.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="160" width="800"]]
... ... @@ -593,8 +593,6 @@
593 593  * Independent (Always) - Charge/Discharge contactor is always closed if there is no errors;
594 594  * Independent (on Charge request or Discharge request) - Charge/Discharge contactor is based on its own controller that listen to Charge and Discharge requests and closes if one of these signals occurs.
595 595  
596 -TBA
597 -
598 598  (% class="box infomessage" %)
599 599  (((