Changes for page 3.3 Control
Last modified by Admin on 2025/04/09 12:14
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -419,9 +419,9 @@ 419 419 * voltages before and after contactors are not equal after "Number of precharging attempts"; 420 420 * power dissipated on the precharge resistor is above the maximum value during the “Delay before setting the 'Precharge error' when checking power” time. 421 421 422 -(% class="box warningmessage" %)422 +(% class="box infomessage" %) 423 423 ((( 424 - Behavior ofcontactorsat “Precharge error”isconfiguredin corresponding contactorttings!424 +If there is the “Precharge error”, **charging **and **discharging **contactors open. 425 425 ))) 426 426 427 427 === Charge === ... ... @@ -474,7 +474,7 @@ 474 474 475 475 (% class="box infomessage" %) 476 476 ((( 477 - **Note:**when errors occur in the system, the **charging **contactor opens either immediately or with the delay T,,off,, (depends on the settings described below).477 +Note: when errors occur in the system, the **charging **contactor opens either immediately or with the delay T,,off,, (depends on the settings described below). 478 478 ))) 479 479 480 480 To change the parameters of the battery charge control algorithm, select the "Control → Charge" section: ... ... @@ -580,11 +580,6 @@ 580 580 * Independent (Always) - Charge/Discharge contactor is always closed if there is no errors; 581 581 * Independent (on Charge request or Discharge request) - Charge/Discharge contactor is based on its own controller that listen to Charge and Discharge requests and closes if one of these signals occurs. 582 582 583 -(% class="box infomessage" %) 584 -((( 585 -**Note: **when errors occur in the system, the **charge/discharge **contactor opens either immediately or with the delay T,,off,, (depends on the settings described below). 586 -))) 587 - 588 588 The charging/discharging contactor control is configured in the “Control – Charge/Discharge” section: 589 589 590 590 [[image:1735122153011-166.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="162" width="800"]] ... ... @@ -617,11 +617,6 @@ 617 617 * the battery voltage is out of range; 618 618 * the battery system errors are detected. 619 619 620 -(% class="box infomessage" %) 621 -((( 622 -**Note: **when errors occur in the system, the **Discharge (AUX) **contactor opens either immediately or with the delay T,,off,, (depends on the settings described below). 623 -))) 624 - 625 625 To change the parameters of the powering of external equipment, select the "Control → Discharge (AUX)" section: 626 626 627 627 [[image:1735066190419-838.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="161" width="800"]] ... ... @@ -684,7 +684,7 @@ 684 684 * Minimum cell voltage to start balancing, V; 685 685 * Voltage deviation to start balancing; 686 686 * Voltage deviation to stop balancing; 687 -* Voltage for forced balancing – if cell voltage is above this value, it will start discharg ingthrough balancing resistor;677 +* Voltage for forced balancing – if cell voltage is above this value, it will start discharge through balancing resistor; 688 688 * Maximum allowable temperature of BMS Logic devices, ºC; 689 689 * Command to discharge all cells – a flag to force the balancing of all cells. 690 690