... ... @@ -578,8 +578,9 @@
578 578  
579 579  * Dependent (on Charging and Discharging signals) - Charge/Discharge contactor depends on Charge and Discharge algorithms and their signals and behaves as Charging contactor if Charging signal is set, otherwise – as Discharging contactor;
580 580  * Independent (Always) - Charge/Discharge contactor is always closed if there is no errors;
581 -* Independent (on Charge request or Discharge request) - Charge/Discharge contactor is based on its own controller that listen to Charge and Discharge requests and closes if one of these signals occurs.
581 +* Independent (on Charge request or Discharge request) - Charge/Discharge contactor is based on its own controller that listen to Charge and Discharge requests.
582 582  
583 +
583 583  The charging/discharging contactor control is configured in the “Control – Charge/Discharge” section:
584 584  
585 585  [[image:1735122153011-166.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="162" width="800"]]
... ... @@ -674,7 +674,7 @@
674 674  * Minimum cell voltage to start balancing, V;
675 675  * Voltage deviation to start balancing;
676 676  * Voltage deviation to stop balancing;
677 -* Voltage for forced balancing – if cell voltage is above this value, it will start discharging through balancing resistor;
678 +* Voltage for forced balancing – if cell voltage is above this value, it will discharge through balancing resistor;
678 678  * Maximum allowable temperature of BMS Logic devices, ºC;
679 679  * Command to discharge all cells – a flag to force the balancing of all cells.
680 680