... ... @@ -407,8 +407,8 @@
407 407  
408 408  or one of the signals:
409 409  
410 -* Service reset;
411 -* Power down request;
410 +* Service reset
411 +* Power down request
412 412  * Inhibit charging,
413 413  
414 414  both contactors are open (no current flows).
... ... @@ -448,7 +448,7 @@
448 448  * Current corresponding to no charging – a current level to clear the "Charging current present" signal, A;
449 449  * Delay before starting charging – a time delay T,,on,, before closing the charging contactor and the allow charging contactor, millisecond;
450 450  * Delay before stopping charging – a time delay T,,off,, before opening the charging contactor, millisecond;
451 -* Control the precharging contactor – a flag that allows control of the precharging contactor while closing the charge contactor;
451 +* Control the precharging contactor – a flag that allows control of the precharging contactor;
452 452  * Errors 1, 2 to open the charging contactor – bitfields to choose the errors which will open the charging contactor;
453 453  * Use custom delays before stopping charging (on errors) – a flag to enable manual settings of time delays T,,off,, for specific errors;
454 454  * Custom delay: <error> – delay for specific error, millisecond;
... ... @@ -500,16 +500,13 @@
500 500  * if there is signal “Discharge request”, the charging contactor is open and there are no errors (see the list above), then through the delay time T,,on,, the discharging contactor closes;
501 501  * If the signal “Discharge request” disappears or errors occur (see the list above), then after the delay time T,,off,, the discharging contactor opens.
502 502  
503 -(% class="box infomessage" %)
504 -(((
505 -**Note:** in case of errors in the system operation, **discharging **contactor opens either immediately or with a delay T,,off,, (depends on the settings described below).
506 -)))
503 +Note – In case of errors in the system operation, the opening of the discharging contactor is performed either immediately or with a delay T,,off,, (depends on the settings described below).
507 507  
508 508  The device supports controlling the precharging contactor. The duration of switching on the precharging contactor before closing the discharging (load) contactor is adjusted.
509 509  
510 510  To change the parameters of the battery discharge control algorithm, select the "Control → Discharge" section:
511 511  
512 -[[image:1735064038329-836.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="273" width="800"]]
509 +[[image:1733323750262-841.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="360" width="800"]]
513 513  
514 514  In this section:
515 515  
... ... @@ -518,16 +518,16 @@
518 518  ** Always on – load is always connected;
519 519  ** On charger disconnected – load is connected when there is no signal “Charger connected”;
520 520  ** On discharge request – load is connected when there is signal “Discharge request”;
521 -* Allow charging only when the "Ready to discharge" signal is set – charging contactor will open if "Ready to charge" signal is cleared;
522 522  * Current corresponding to discharging – a current level to generate the "Discharging current present" signal, А;
523 523  * Current indicating no discharging – a current level to clear the "Discharging current present" signal, А;
524 524  * Delay before starting discharging – a time delay T,,on,, before closing the discharging contactor, millisecond;
525 525  * Delay before stopping discharging – a time delay T,,off,, before opening the discharging contactor, millisecond;
526 -* Control the precharging contactor – a flag that allows control of the precharging contactor while closing the discharge contactor;
527 -* Errors 1, 2 to open the discharging contactor – bitfields to choose the errors which will open the discharging contactor;
528 528  * Use custom delays before stopping discharging (on errors) – a flag to enable manual settings of time delays T,,off,, for specific errors;
529 529  * Custom delay: <error> – specific error delay, millisecond;
530 530  * Switch off the discharging contactor on errors without delay – a flag to protectively open the discharging contactor without a delay. In the opposite case, when an error is detected, the discharging contactor opens always with the delay “Delay before stopping discharging”.
525 +* Precharge time – a duration of closing the precharge contactor before closing the discharging contactor, millisecond;
526 +* Check voltages before and after contactors to finish precharging – a flag to check the voltages before and after contactors to ensure that precharge process has finished and it is allowed to close the discharging contactor;
527 +* Minimum voltage difference to finish precharging – minimal voltage difference before and after contactors at which precharge process is meant to be finished, V;
531 531  
532 532  === Charge/Discharge ===
533 533  