... ... @@ -407,9 +407,9 @@
407 407  
408 408  or one of the signals:
409 409  
410 -* Service reset;
411 -* Power down request;
412 -* Inhibit charging,
410 +* Service reset
411 +* Power down request
412 +* Inhibit charging
413 413  
414 414  both contactors are open (no current flows).
415 415  
... ... @@ -427,10 +427,7 @@
427 427  * If in the process of charging the voltage on the cell exceeds the “Ready to charge” level, the allow charging contactor opens (while the charging contactor remains closed);
428 428  * If errors in the list above occur the charging contactor and allow charging contactor open.
429 429  
430 -(% class="box infomessage" %)
431 -(((
432 -Note: when errors occur in the system, the **charging **contactor opens either immediately or with the delay T,,off,, (depends on the settings described below).
433 -)))
430 +Note – When errors occur in the system, the charging contactor opens either immediately or with the delay T,,off,, (depends on the settings described below).
434 434  
435 435  To change the parameters of the battery charge control algorithm, select the "Control → Charge" section:
436 436  
... ... @@ -449,9 +449,9 @@
449 449  * Delay before starting charging – a time delay T,,on,, before closing the charging contactor and the allow charging contactor, millisecond;
450 450  * Delay before stopping charging – a time delay T,,off,, before opening the charging contactor, millisecond;
451 451  * Control the precharging contactor – a flag that allows control of the precharging contactor;
452 -* Errors 1, 2 to open the charging contactor – bitfields to choose the errors which will open the charging contactor;
449 +* Errors 1, 2 
453 453  * Use custom delays before stopping charging (on errors) – a flag to enable manual settings of time delays T,,off,, for specific errors;
454 -* Custom delay: <error> – delay for specific error, millisecond;
451 +* Custom delay: <error> – specific error delay, millisecond;
455 455  * Switch off the charging contactor on errors without delay – a flag to protectively open the charging contactor without a delay. In the opposite case, when an error is detected, the charging contactor opens always with the delay “Delay before stopping charging”;
456 456  
457 457  === Discharge ===
... ... @@ -500,10 +500,7 @@
500 500  * if there is signal “Discharge request”, the charging contactor is open and there are no errors (see the list above), then through the delay time T,,on,, the discharging contactor closes;
501 501  * If the signal “Discharge request” disappears or errors occur (see the list above), then after the delay time T,,off,, the discharging contactor opens.
502 502  
503 -(% class="box infomessage" %)
504 -(((
505 -**Note:** in case of errors in the system operation, **discharging **contactor opens either immediately or with a delay T,,off,, (depends on the settings described below).
506 -)))
500 +Note – In case of errors in the system operation, the opening of the discharging contactor is performed either immediately or with a delay T,,off,, (depends on the settings described below).
507 507  
508 508  The device supports controlling the precharging contactor. The duration of switching on the precharging contactor before closing the discharging (load) contactor is adjusted.