Changes for page 3.3 Control
Last modified by Admin on 2025/04/09 12:14
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -407,8 +407,8 @@ 407 407 408 408 or one of the signals: 409 409 410 -* Service reset 411 -* Power down request 410 +* Service reset; 411 +* Power down request; 412 412 * Inhibit charging, 413 413 414 414 both contactors are open (no current flows). ... ... @@ -500,7 +500,10 @@ 500 500 * if there is signal “Discharge request”, the charging contactor is open and there are no errors (see the list above), then through the delay time T,,on,, the discharging contactor closes; 501 501 * If the signal “Discharge request” disappears or errors occur (see the list above), then after the delay time T,,off,, the discharging contactor opens. 502 502 503 -Note – In case of errors in the system operation, the opening of the discharging contactor is performed either immediately or with a delay T,,off,, (depends on the settings described below). 503 +(% class="box infomessage" %) 504 +((( 505 +**Note:** in case of errors in the system operation, **discharging **contactor opens either immediately or with a delay T,,off,, (depends on the settings described below). 506 +))) 504 504 505 505 The device supports controlling the precharging contactor. The duration of switching on the precharging contactor before closing the discharging (load) contactor is adjusted. 506 506