... ... @@ -407,9 +407,9 @@
407 407  
408 408  or one of the signals:
409 409  
410 -* Service reset
411 -* Power down request
412 -* Inhibit charging
410 +* Service reset;
411 +* Power down request;
412 +* Inhibit charging,
413 413  
414 414  both contactors are open (no current flows).
415 415  
... ... @@ -427,7 +427,10 @@
427 427  * If in the process of charging the voltage on the cell exceeds the “Ready to charge” level, the allow charging contactor opens (while the charging contactor remains closed);
428 428  * If errors in the list above occur the charging contactor and allow charging contactor open.
429 429  
430 -Note – When errors occur in the system, the charging contactor opens either immediately or with the delay T,,off,, (depends on the settings described below).
430 +(% class="box infomessage" %)
431 +(((
432 +Note: when errors occur in the system, the **charging **contactor opens either immediately or with the delay T,,off,, (depends on the settings described below).
433 +)))
431 431  
432 432  To change the parameters of the battery charge control algorithm, select the "Control → Charge" section:
433 433  
... ... @@ -445,10 +445,10 @@
445 445  * Current corresponding to no charging – a current level to clear the "Charging current present" signal, A;
446 446  * Delay before starting charging – a time delay T,,on,, before closing the charging contactor and the allow charging contactor, millisecond;
447 447  * Delay before stopping charging – a time delay T,,off,, before opening the charging contactor, millisecond;
448 -* Control the precharging contactor – a flag that allows control of the precharging contactor;
449 -* Errors 1, 2 
451 +* Control the precharging contactor – a flag that allows control of the precharging contactor while closing the charge contactor;
452 +* Errors 1, 2 to open the charging contactor – bitfields to choose the errors which will open the charging contactor;
450 450  * Use custom delays before stopping charging (on errors) – a flag to enable manual settings of time delays T,,off,, for specific errors;
451 -* Custom delay: <error> – specific error delay, millisecond;
454 +* Custom delay: <error> – delay for specific error, millisecond;
452 452  * Switch off the charging contactor on errors without delay – a flag to protectively open the charging contactor without a delay. In the opposite case, when an error is detected, the charging contactor opens always with the delay “Delay before stopping charging”;
453 453  
454 454  === Discharge ===
... ... @@ -497,7 +497,10 @@
497 497  * if there is signal “Discharge request”, the charging contactor is open and there are no errors (see the list above), then through the delay time T,,on,, the discharging contactor closes;
498 498  * If the signal “Discharge request” disappears or errors occur (see the list above), then after the delay time T,,off,, the discharging contactor opens.
499 499  
500 -Note – In case of errors in the system operation, the opening of the discharging contactor is performed either immediately or with a delay T,,off,, (depends on the settings described below).
503 +(% class="box infomessage" %)
504 +(((
505 +**Note:** in case of errors in the system operation, **discharging **contactor opens either immediately or with a delay T,,off,, (depends on the settings described below).
506 +)))
501 501  
502 502  The device supports controlling the precharging contactor. The duration of switching on the precharging contactor before closing the discharging (load) contactor is adjusted.
503 503  
... ... @@ -516,12 +516,11 @@
516 516  * Current indicating no discharging – a current level to clear the "Discharging current present" signal, А;
517 517  * Delay before starting discharging – a time delay T,,on,, before closing the discharging contactor, millisecond;
518 518  * Delay before stopping discharging – a time delay T,,off,, before opening the discharging contactor, millisecond;
525 +* Control the precharging contactor – a flag that allows control of the precharging contactor while closing the discharge contactor;
526 +* Errors 1, 2 to open the discharging contactor – bitfields to choose the errors which will open the charging contactor;
519 519  * Use custom delays before stopping discharging (on errors) – a flag to enable manual settings of time delays T,,off,, for specific errors;
520 520  * Custom delay: <error> – specific error delay, millisecond;
521 521  * Switch off the discharging contactor on errors without delay – a flag to protectively open the discharging contactor without a delay. In the opposite case, when an error is detected, the discharging contactor opens always with the delay “Delay before stopping discharging”.
522 -* Precharge time – a duration of closing the precharge contactor before closing the discharging contactor, millisecond;
523 -* Check voltages before and after contactors to finish precharging – a flag to check the voltages before and after contactors to ensure that precharge process has finished and it is allowed to close the discharging contactor;
524 -* Minimum voltage difference to finish precharging – minimal voltage difference before and after contactors at which precharge process is meant to be finished, V;
525 525  
526 526  === Charge/Discharge ===
527 527  