... ... @@ -359,17 +359,8 @@
359 359  
360 360  === Charging status ===
361 361  
362 -* Voltage to clear the “Ready to charge” – a threshold voltage level on the cell, V; if the voltage of any cell is above this level, the “Ready to charge” (hence, the “Allow charging”) signal is cleared;
363 -* Voltage to reset the “Ready to charge” – a tolerant voltage level on the cell, V; if all cell voltages are below the tolerant level, the “Ready to charge” (hence, the “Allow charging”) signal is set;
364 -* Delay before recharging – a time after which the previously opened the allow charging contactor closes again, minute; to disable the operation by timeout set "Delay before recharging" to 0.
362 +TBA
365 365  
366 -(% class="box infomessage" %)
367 -(((
368 -**Note:** The allow charging ышптфд closes under two independent conditions:
369 -1) the voltage on the cells reaches the “Voltage to reset the “Ready to charge"” level and
370 -2) the "Delay before recharging" time has passed since the opening of the allow charging contactor.
371 -)))
372 -
373 373  === Discharging status ===
374 374  
375 375  TBA
... ... @@ -443,11 +443,16 @@
443 443  * Current corresponding to no charging – a current level to clear the "Charging current present" signal, A;
444 444  * Delay before starting charging – a time delay T,,on,, before closing the charging contactor and the allow charging contactor, millisecond;
445 445  * Delay before stopping charging – a time delay T,,off,, before opening the charging contactor, millisecond;
446 -* Control the precharging contactor – a flag that allows control of the precharging contactor;
447 447  * Use custom delays before stopping charging (on errors) – a flag to enable manual settings of time delays T,,off,, for specific errors;
448 448  * Custom delay: <error> – specific error delay, millisecond;
449 449  * Switch off the charging contactor on errors without delay – a flag to protectively open the charging contactor without a delay. In the opposite case, when an error is detected, the charging contactor opens always with the delay “Delay before stopping charging”;
440 +* Control the precharging contactor – a flag that allows control of the precharging contactor;
441 +* Voltage to clear the “Ready to charge” – a threshold voltage level on the cell, V; if the voltage of any cell is above this level, the “Ready to charge” (hence, the “Allow charging”) signal is cleared;
442 +* Voltage to reset the “Ready to charge” – a tolerant voltage level on the cell, V; if all cell voltages are below the tolerant level, the “Ready to charge” (hence, the “Allow charging”) signal is set;
443 +* Delay before recharging – a time after which the previously opened the allow charging contactor closes again, minute; to disable the operation by timeout set "Delay before recharging" to 0.
450 450  
445 +Note – The allow charging contactor closes under two independent conditions: 1) the voltage on the cells reaches the “Voltage to reset the “Ready to charge"” level and 2) the "Delay before recharging" time has passed since the opening of the allow charging contactor.
446 +
451 451  === Discharge ===
452 452  
453 453  The device controls the discharging contactor to connect battery to the load.