... ... @@ -304,72 +304,12 @@
304 304  
305 305  === Main contactor ===
306 306  
307 -The BMS Main 3 device controls the main contactor. The main contactor is usually placed in the common (minus) battery line for opening the charge and discharge circuits in case of sealing of the charging or discharging contactors.
307 +TBA
308 308  
309 -The Main contactor algorithm supports the following modes:
310 -
311 -* Always on;
312 -* Automatic;
313 -* On demand.
314 -
315 -In “Always on” mode main contactor closes if all the following is true:
316 -
317 -* Charging contactor is open;
318 -* Discharging contactor is open;
319 -* There are no errors from the list below:
320 -** Overcurrent;
321 -** Undervoltage;
322 -** Overvoltage;
323 -** High temperature (CH);
324 -** High temperature (DCH);
325 -** Unallowable charging;
326 -** Critical error.
327 -
328 -In “Always on” mode main contactor opens if all the following is true:
329 -
330 -* Charging contactor is open;
331 -* Discharging contactor is open;
332 -* There is an error from the list below:
333 -** Overcurrent;
334 -** Undervoltage;
335 -** Overvoltage;
336 -** High temperature (CH);
337 -** High temperature (DCH);
338 -** Unallowable charging;
339 -** Critical error.
340 -
341 -In “Automatic” mode, the main contactor closes by internal charging and discharging algorithms at the same time with Precharging, Charging and Discharging contactors.
342 -
343 -In “On demand” mode, the main contactor closes by external the “Close Main contactor” request.
344 -
345 -To change the parameters of the main contactor, select the "Control → Main contactor" section:
346 -
347 -[[image:1733322872744-536.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="105" width="800"]]
348 -
349 -In this section:
350 -
351 -* Enable – a flag to enable the main contactor control;
352 -* Algorithm – main contactor control algorithm:
353 -** Always on – contactor is always closed;
354 -** Automatic – contactor closes by internal charge and discharge algorithms;
355 -** On demand – contactor is closed by an external request;
356 -* Time to keep the contactor closed before closing the others – a time for other contactors to be open after the main contactor is closed;
357 -* Delay before opening the contactor – a time which is used to detect conditions for opening the contactor, s;
358 -* Keep the contactor open until the device is restarted – a flag for keeping the main contactor open until the system is reset.
359 -
360 360  === Charging status ===
361 361  
362 -* Voltage to clear the “Ready to charge” – a threshold voltage level on the cell, V; if the voltage of any cell is above this level, the “Ready to charge” (hence, the “Allow charging”) signal is cleared;
363 -* Voltage to reset the “Ready to charge” – a tolerant voltage level on the cell, V; if all cell voltages are below the tolerant level, the “Ready to charge” (hence, the “Allow charging”) signal is set;
364 -* Delay before recharging – a time after which the previously opened the allow charging contactor closes again, minute; to disable the operation by timeout set "Delay before recharging" to 0.
311 +TBA
365 365  
366 -(% class="box infomessage" %)
367 -(((
368 -**Note:** The allow charging ышптфд closes under two independent conditions:
369 -1) the voltage on the cells reaches the “Voltage to reset the “Ready to charge"” level and
370 -2) the "Delay before recharging" time has passed since the opening of the allow charging contactor.
371 -)))
372 -
373 373  === Discharging status ===
374 374  
375 375  TBA
... ... @@ -376,7 +376,6 @@
376 376  
377 377  === Precharge ===
378 378  
379 -TBA
380 380  
381 381  === Charge ===
382 382  
... ... @@ -443,11 +443,16 @@
443 443  * Current corresponding to no charging – a current level to clear the "Charging current present" signal, A;
444 444  * Delay before starting charging – a time delay T,,on,, before closing the charging contactor and the allow charging contactor, millisecond;
445 445  * Delay before stopping charging – a time delay T,,off,, before opening the charging contactor, millisecond;
446 -* Control the precharging contactor – a flag that allows control of the precharging contactor;
447 447  * Use custom delays before stopping charging (on errors) – a flag to enable manual settings of time delays T,,off,, for specific errors;
448 448  * Custom delay: <error> – specific error delay, millisecond;
449 449  * Switch off the charging contactor on errors without delay – a flag to protectively open the charging contactor without a delay. In the opposite case, when an error is detected, the charging contactor opens always with the delay “Delay before stopping charging”;
388 +* Control the precharging contactor – a flag that allows control of the precharging contactor;
389 +* Voltage to clear the “Ready to charge” – a threshold voltage level on the cell, V; if the voltage of any cell is above this level, the “Ready to charge” (hence, the “Allow charging”) signal is cleared;
390 +* Voltage to reset the “Ready to charge” – a tolerant voltage level on the cell, V; if all cell voltages are below the tolerant level, the “Ready to charge” (hence, the “Allow charging”) signal is set;
391 +* Delay before recharging – a time after which the previously opened the allow charging contactor closes again, minute; to disable the operation by timeout set "Delay before recharging" to 0.
450 450  
393 +Note – The allow charging contactor closes under two independent conditions: 1) the voltage on the cells reaches the “Voltage to reset the “Ready to charge"” level and 2) the "Delay before recharging" time has passed since the opening of the allow charging contactor.
394 +
451 451  === Discharge ===
452 452  
453 453  The device controls the discharging contactor to connect battery to the load.
... ... @@ -561,6 +561,61 @@
561 561  * Maximum voltage – maximum battery voltage, V;
562 562  * Switch off the discharging (AUX) contactor on errors – the auxiliary (AUX) discharging contactor opens if the following errors occur: Undervoltage, Overcurrent, High temperature (DCH), Short circuit, Critical error.
563 563  
508 +=== Main contactor ===
509 +
510 +The BMS Main 3 device controls the main contactor. The main contactor is usually placed in the common (minus) battery line for opening the charge and discharge circuits in case of sealing of the charging or discharging contactors.
511 +
512 +The Main contactor algorithm supports the following modes:
513 +
514 +* Always on;
515 +* Automatic;
516 +* On demand.
517 +
518 +In “Always on” mode main contactor closes if all the following is true:
519 +
520 +* Charging contactor is open;
521 +* Discharging contactor is open;
522 +* There are no errors from the list below:
523 +** Overcurrent;
524 +** Undervoltage;
525 +** Overvoltage;
526 +** High temperature (CH);
527 +** High temperature (DCH);
528 +** Unallowable charging;
529 +** Critical error.
530 +
531 +In “Always on” mode main contactor opens if all the following is true:
532 +
533 +* Charging contactor is open;
534 +* Discharging contactor is open;
535 +* There is an error from the list below:
536 +** Overcurrent;
537 +** Undervoltage;
538 +** Overvoltage;
539 +** High temperature (CH);
540 +** High temperature (DCH);
541 +** Unallowable charging;
542 +** Critical error.
543 +
544 +In “Automatic” mode, the main contactor closes by internal charging and discharging algorithms at the same time with Precharging, Charging and Discharging contactors.
545 +
546 +In “On demand” mode, the main contactor closes by external the “Close Main contactor” request.
547 +
548 +To change the parameters of the main contactor, select the "Control → Main contactor" section:
549 +
550 +[[image:1733322872744-536.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="105" width="800"]]
551 +
552 +In this section:
553 +
554 +* Enable – a flag to enable the main contactor control;
555 +* Algorithm – main contactor control algorithm:
556 +** Always on – contactor is always closed;
557 +** Automatic – contactor closes by internal charge and discharge algorithms;
558 +** On demand – contactor is closed by an external request;
559 +* Time to keep the contactor closed before closing the others – a time for other contactors to be open after the main contactor is closed;
560 +* Delay before opening the contactor – a time which is used to detect conditions for opening the contactor, s;
561 +* Keep the contactor open until the device is restarted – a flag for keeping the main contactor open until the system is reset.
562 +
564 564  === Cell balancing ===
565 565  
566 566  Balancing makes the voltage of all cells equal to the minimum cell voltage.