Changes for page 3.3 Control

Last modified by Admin on 2025/04/09 12:14

From version 11.2
edited by Admin
on 2024/12/24 17:38
Change comment: There is no comment for this version
To version 11.3
edited by Admin
on 2024/12/24 18:05
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -359,8 +359,17 @@
359 359  
360 360  === Charging status ===
361 361  
362 -TBA
362 +* Voltage to clear the “Ready to charge” – a threshold voltage level on the cell, V; if the voltage of any cell is above this level, the “Ready to charge” (hence, the “Allow charging”) signal is cleared;
363 +* Voltage to reset the “Ready to charge” – a tolerant voltage level on the cell, V; if all cell voltages are below the tolerant level, the “Ready to charge” (hence, the “Allow charging”) signal is set;
364 +* Delay before recharging – a time after which the previously opened the allow charging contactor closes again, minute; to disable the operation by timeout set "Delay before recharging" to 0.
363 363  
366 +(% class="box infomessage" %)
367 +(((
368 +**Note:** The allow charging ышптфд closes under two independent conditions:
369 +1) the voltage on the cells reaches the “Voltage to reset the “Ready to charge"” level and
370 +2) the "Delay before recharging" time has passed since the opening of the allow charging contactor.
371 +)))
372 +
364 364  === Discharging status ===
365 365  
366 366  TBA
... ... @@ -434,16 +434,11 @@
434 434  * Current corresponding to no charging – a current level to clear the "Charging current present" signal, A;
435 435  * Delay before starting charging – a time delay T,,on,, before closing the charging contactor and the allow charging contactor, millisecond;
436 436  * Delay before stopping charging – a time delay T,,off,, before opening the charging contactor, millisecond;
446 +* Control the precharging contactor – a flag that allows control of the precharging contactor;
437 437  * Use custom delays before stopping charging (on errors) – a flag to enable manual settings of time delays T,,off,, for specific errors;
438 438  * Custom delay: <error> – specific error delay, millisecond;
439 439  * Switch off the charging contactor on errors without delay – a flag to protectively open the charging contactor without a delay. In the opposite case, when an error is detected, the charging contactor opens always with the delay “Delay before stopping charging”;
440 -* Control the precharging contactor – a flag that allows control of the precharging contactor;
441 -* Voltage to clear the “Ready to charge” – a threshold voltage level on the cell, V; if the voltage of any cell is above this level, the “Ready to charge” (hence, the “Allow charging”) signal is cleared;
442 -* Voltage to reset the “Ready to charge” – a tolerant voltage level on the cell, V; if all cell voltages are below the tolerant level, the “Ready to charge” (hence, the “Allow charging”) signal is set;
443 -* Delay before recharging – a time after which the previously opened the allow charging contactor closes again, minute; to disable the operation by timeout set "Delay before recharging" to 0.
444 444  
445 -Note – The allow charging contactor closes under two independent conditions: 1) the voltage on the cells reaches the “Voltage to reset the “Ready to charge"” level and 2) the "Delay before recharging" time has passed since the opening of the allow charging contactor.
446 -
447 447  === Discharge ===
448 448  
449 449  The device controls the discharging contactor to connect battery to the load.