... ... @@ -106,7 +106,7 @@
106 106  
107 107  Calculation of the resistance of cells is carried out in two ways. The first method is used when the battery passes from a relaxation state to a charge or discharge state, wherein the cell resistance value
108 108  
109 -{{formula fontSize="NORMAL" imageType="PNG"}}
109 +{{formula fontSize="SMALL" imageType="PNG"}}
110 110  R = \frac{U-U_{ocv}}{I_{stable}}
111 111  {{/formula}}
112 112  
... ... @@ -114,20 +114,18 @@
114 114  
115 115  The second method is used for a stepwise change in the current through the cell, while the value of the cell resistance:
116 116  
117 -{{formula}}
117 +{{formula fontSize="SMALL"}}
118 118  R = \frac{U_2-U_1}{I_{stable2}-I_{stable1}}
119 119  {{/formula}}
120 120  
121 121  provided that
122 122  
123 -{{formula}}
124 -|I_{stable2}-I_{stable1}| > 0.2 × Qmax
123 +{{formula fontSize="SMALL"}}
124 +| I_{stable2}-I_{stable1} | > 0.2 × Qmax
125 125  {{/formula}}
126 126  
127 -(Q,,max,, is the maximum cell capacity),
127 +where Q,,max,, the maximum cell capacity,U,,2,, — voltage on the cell at the moment when the stabilized current I,,stable2,, is flowing through it; U,,1,, — the voltage on the cell at the moment when the stabilized current I,,stable1,, flowing through it.
128 128  
129 -where U,,2,, is the voltage on the cell at the moment when the stabilized current I,,stable2,, is flowing through it; U,,1,, – the voltage on the cell at the moment when the stabilized current I,,stable1,, flowing through it.
130 -
131 131  The stabilized current I,,stable,, = I, if during the stabilization time the instantaneous current I is in the range from 0.95 × I to 1.05 × I.
132 132  
133 133  To change parameters of the algorithm for calculating the cell resistance, select the "Control → Resistance estimation" section:
... ... @@ -142,7 +142,7 @@
142 142  * Minimum SOC – minimum cell SOC value for resistance calculation;
143 143  * Maximum SOC – maximum cell SOC value for resistance calculation.
144 144  
145 -The calculated resistance is accepted by the system as valid (and therefore updated) if its value is in the range from Resistance/2 to “Maximum resistance factor” × Resistance, where "Resistance" is the nominal resistance of the cell (see [[Common settings>>doc:||anchor="HCommonsettings"]]). If the calculated resistance value is greater than the value (Maximum resistance factor × Resistance), the updated resistance value will be equal to the value (Maximum resistance factor × Resistance).
143 +The calculated resistance is accepted by the system as valid (and therefore updated) if its value is in the range from Resistance / 2 to “Maximum resistance factor” × Resistance, where "Resistance" is the nominal resistance of the cell (see [[Common settings>>doc:||anchor="HCommonsettings"]]). If the calculated resistance value is greater than the value (Maximum resistance factor × Resistance), the updated resistance value will be equal to the value (Maximum resistance factor × Resistance).
146 146  
147 147  === Low SOC (signal) ===
148 148  
... ... @@ -277,7 +277,6 @@
277 277  
278 278  I,,continuous,, = Maximum CONTINUOUS charge current × K,,cc,,
279 279  
280 -
281 281  === Discharge map (PEAK & CONTINUOUS) ===
282 282  
283 283  The BMS Main 3 has an alternative algorithm for the maximum allowed discharging current based on peak and continuous battery operating modes.
... ... @@ -305,6 +305,75 @@
305 305  
306 306  I,,continuous,, = Maximum CONTINUOUS discharge current × K,,dc,,
307 307  
305 +
306 +
307 +=== Main contactor ===
308 +
309 +The BMS Main 3 device controls the main contactor. The main contactor is usually placed in the common (minus) battery line for opening the charge and discharge circuits in case of sealing of the charging or discharging contactors.
310 +
311 +The Main contactor algorithm supports the following modes:
312 +
313 +* Always on;
314 +* Automatic;
315 +* On demand.
316 +
317 +In “Always on” mode main contactor closes if all the following is true:
318 +
319 +* Charging contactor is open;
320 +* Discharging contactor is open;
321 +* There are no errors from the list below:
322 +** Overcurrent;
323 +** Undervoltage;
324 +** Overvoltage;
325 +** High temperature (CH);
326 +** High temperature (DCH);
327 +** Unallowable charging;
328 +** Critical error.
329 +
330 +In “Always on” mode main contactor opens if all the following is true:
331 +
332 +* Charging contactor is open;
333 +* Discharging contactor is open;
334 +* There is an error from the list below:
335 +** Overcurrent;
336 +** Undervoltage;
337 +** Overvoltage;
338 +** High temperature (CH);
339 +** High temperature (DCH);
340 +** Unallowable charging;
341 +** Critical error.
342 +
343 +In “Automatic” mode, the main contactor closes by internal charging and discharging algorithms at the same time with Precharging, Charging and Discharging contactors.
344 +
345 +In “On demand” mode, the main contactor closes by external the “Close Main contactor” request.
346 +
347 +To change the parameters of the main contactor, select the "Control → Main contactor" section:
348 +
349 +[[image:1733322872744-536.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="105" width="800"]]
350 +
351 +In this section:
352 +
353 +* Enable – a flag to enable the main contactor control;
354 +* Algorithm – main contactor control algorithm:
355 +** Always on – contactor is always closed;
356 +** Automatic – contactor closes by internal charge and discharge algorithms;
357 +** On demand – contactor is closed by an external request;
358 +* Time to keep the contactor closed before closing the others – a time for other contactors to be open after the main contactor is closed;
359 +* Delay before opening the contactor – a time which is used to detect conditions for opening the contactor, s;
360 +* Keep the contactor open until the device is restarted – a flag for keeping the main contactor open until the system is reset.
361 +
362 +=== Charging status ===
363 +
364 +TBA
365 +
366 +=== Discharging status ===
367 +
368 +TBA
369 +
370 +=== Precharge ===
371 +
372 +TBA
373 +
308 308  === Charge ===
309 309  
310 310  There are two contactors that serve charging the battery: a charging contactor and an allow charging contactor. With the help of the allow charging contactor, the BMS commands the charger to start or stop charging.
... ... @@ -493,61 +493,6 @@
493 493  * Maximum voltage – maximum battery voltage, V;
494 494  * Switch off the discharging (AUX) contactor on errors – the auxiliary (AUX) discharging contactor opens if the following errors occur: Undervoltage, Overcurrent, High temperature (DCH), Short circuit, Critical error.
495 495  
496 -=== Main contactor ===
497 -
498 -The BMS Main 3 device controls the main contactor. The main contactor is usually placed in the common (minus) battery line for opening the charge and discharge circuits in case of sealing of the charging or discharging contactors.
499 -
500 -The Main contactor algorithm supports the following modes:
501 -
502 -* Always on;
503 -* Automatic;
504 -* On demand.
505 -
506 -In “Always on” mode main contactor closes if all the following is true:
507 -
508 -* Charging contactor is open;
509 -* Discharging contactor is open;
510 -* There are no errors from the list below:
511 -** Overcurrent;
512 -** Undervoltage;
513 -** Overvoltage;
514 -** High temperature (CH);
515 -** High temperature (DCH);
516 -** Unallowable charging;
517 -** Critical error.
518 -
519 -In “Always on” mode main contactor opens if all the following is true:
520 -
521 -* Charging contactor is open;
522 -* Discharging contactor is open;
523 -* There is an error from the list below:
524 -** Overcurrent;
525 -** Undervoltage;
526 -** Overvoltage;
527 -** High temperature (CH);
528 -** High temperature (DCH);
529 -** Unallowable charging;
530 -** Critical error.
531 -
532 -In “Automatic” mode, the main contactor closes by internal charging and discharging algorithms at the same time with Precharging, Charging and Discharging contactors.
533 -
534 -In “On demand” mode, the main contactor closes by external the “Close Main contactor” request.
535 -
536 -To change the parameters of the main contactor, select the "Control → Main contactor" section:
537 -
538 -[[image:1733322872744-536.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="105" width="800"]]
539 -
540 -In this section:
541 -
542 -* Enable – a flag to enable the main contactor control;
543 -* Algorithm – main contactor control algorithm:
544 -** Always on – contactor is always closed;
545 -** Automatic – contactor closes by internal charge and discharge algorithms;
546 -** On demand – contactor is closed by an external request;
547 -* Time to keep the contactor closed before closing the others – a time for other contactors to be open after the main contactor is closed;
548 -* Delay before opening the contactor – a time which is used to detect conditions for opening the contactor, s;
549 -* Keep the contactor open until the device is restarted – a flag for keeping the main contactor open until the system is reset.
550 -
551 551  === Cell balancing ===
552 552  
553 553  Balancing makes the voltage of all cells equal to the minimum cell voltage.