... ... @@ -1,5 +1,5 @@
1 1  (% data-numbered-headings-start="3" style="--numbered-headings-start: 2;font-size: 0px;color: rgba(0, 0, 0, 0.0);margin-bottom: 0px; margin-top: 0px;" %)
2 -= Settings =
2 += Configuration =
3 3  
4 4  (% data-numbered-headings-start="3" style="--numbered-headings-start: 2;font-size: 0px;color: rgba(0, 0, 0, 0.0);margin-bottom: 0px; margin-top: 0px;" %)
5 5  == Control ==
... ... @@ -21,7 +21,7 @@
21 21  ** Summation of cell voltages – the overall voltage is calculated as on sum of all cells in the battery;
22 22  ** Using voltage before contactors – the overall voltage is estimated as voltage before contactors measured by BMS.
23 23  
24 -The values “Capacity”, “Resistance”, “Cycles” are used to calculate the SOC of cells and the battery.
24 +The values “Capacity” and “Resistance” are used to calculate the SOC of cells and the battery.
25 25  
26 26  The values of “Relax time” are used to determine the state of the battery. If the battery is in a state of relaxation, the system recalculates the voltage on the cells to the state of charge of the battery.
27 27  
... ... @@ -70,8 +70,8 @@
70 70  
71 71  * Minimal SOC – the battery SOC is assumed to be the minimum SOC among the cells;
72 72  * Average SOC – the battery SOC is taken equal to the arithmetic average of the cell SOC;
73 -* Min-Max SOC – the battery SOC is calculated based on the minimum and maximum SOC of the cells. Final SOC will be a) 100% if any cell have 100% SOC, b) 0% if any cell have 0% SOC;
74 -* Max-Min SOC – the battery SOC is calculated based on the minimum and maximum SOC of the cells. Final SOC will be a) 100% if all cells have 100% SOC, b) 0% if all cells have 0% SOC;
73 +* Min-Max SOC – the battery SOC is calculated based on the minimum and maximum SOC of the cells. Final SOC will be a) 100% if any cell has 100% SOC, b) 0% if any cell has 0% SOC;
74 +* Max-Min SOC – the battery SOC is calculated based on the minimum and maximum SOC of the cells. Final SOC will be a) 100% if all cells have 100% SOC, b) 0% if all cells have 0% SOC.
75 75  
76 76  Other parameters:
77 77  
... ... @@ -106,7 +106,7 @@
106 106  
107 107  Calculation of the resistance of cells is carried out in two ways. The first method is used when the battery passes from a relaxation state to a charge or discharge state, wherein the cell resistance value
108 108  
109 -{{formula fontSize="NORMAL" imageType="PNG"}}
109 +{{formula fontSize="SMALL" imageType="PNG"}}
110 110  R = \frac{U-U_{ocv}}{I_{stable}}
111 111  {{/formula}}
112 112  
... ... @@ -114,16 +114,18 @@
114 114  
115 115  The second method is used for a stepwise change in the current through the cell, while the value of the cell resistance:
116 116  
117 -R = (U,,2,,-U,,1,,) / (I,,stable2,,-I,,stable1,,) provided that | I,,stable2,,-I,,stable1,, | > 0.2 × Q,,max,,
118 -
119 -{{formula}}
120 -R = frac\{U_2-U_1}{I_{stable2}-I_{stable1}}
117 +{{formula fontSize="SMALL"}}
118 +R = \frac{U_2-U_1}{I_{stable2}-I_{stable1}}
121 121  {{/formula}}
122 122  
123 -(Q,,max,, is the maximum cell capacity),
121 +provided that
124 124  
125 -where U,,2,, is the voltage on the cell at the moment when the stabilized current I,,stable2,, is flowing through it; U,,1,, – the voltage on the cell at the moment when the stabilized current I,,stable1,, flowing through it.
123 +{{formula fontSize="SMALL"}}
124 +| I_{stable2}-I_{stable1} | > 0.2 × Qmax
125 +{{/formula}}
126 126  
127 +where Q,,max,, — the maximum cell capacity,U,,2,, — voltage on the cell at the moment when the stabilized current I,,stable2,, is flowing through it; U,,1,, — the voltage on the cell at the moment when the stabilized current I,,stable1,, flowing through it.
128 +
127 127  The stabilized current I,,stable,, = I, if during the stabilization time the instantaneous current I is in the range from 0.95 × I to 1.05 × I.
128 128  
129 129  To change parameters of the algorithm for calculating the cell resistance, select the "Control → Resistance estimation" section:
... ... @@ -138,7 +138,7 @@
138 138  * Minimum SOC – minimum cell SOC value for resistance calculation;
139 139  * Maximum SOC – maximum cell SOC value for resistance calculation.
140 140  
141 -The calculated resistance is accepted by the system as valid (and therefore updated) if its value is in the range from Resistance/2 to “Maximum resistance factor” × Resistance, where "Resistance" is the nominal resistance of the cell (see [[Common settings>>doc:||anchor="HCommonsettings"]]). If the calculated resistance value is greater than the value (Maximum resistance factor × Resistance), the updated resistance value will be equal to the value (Maximum resistance factor × Resistance).
143 +The calculated resistance is accepted by the system as valid (and therefore updated) if its value is in the range from Resistance / 2 to “Maximum resistance factor” × Resistance, where "Resistance" is the nominal resistance of the cell (see [[Common settings>>doc:||anchor="HCommonsettings"]]). If the calculated resistance value is greater than the value (Maximum resistance factor × Resistance), the updated resistance value will be equal to the value (Maximum resistance factor × Resistance).
142 142  
143 143  === Low SOC (signal) ===
144 144  
... ... @@ -163,7 +163,10 @@
163 163  
164 164  * the battery SOC is greater than the “Tolerant SOC” during the “Delay before clearing the signal” time.
165 165  
168 +(% class="box infomessage" %)
169 +(((
166 166  The "Low SOC signal" is indicative and can be output to a discrete output or a power switch.
171 +)))
167 167  
168 168  === High charging current (signal) ===
169 169  
... ... @@ -188,7 +188,10 @@
188 188  
189 189  * the measured current is less than the “Tolerant charging current” value during the “Delay before clearing the signal” time.
190 190  
196 +(% class="box infomessage" %)
197 +(((
191 191  The "High charging current" signal is indicative and can be output to a discrete output or a power switch.
199 +)))
192 192  
193 193  === Charge map ===
194 194  
... ... @@ -198,7 +198,7 @@
198 198  
199 199  To configure parameters for determining the charge current limit, select the "Control → Charge map" section:
200 200  
201 -[[image:1733322637793-171.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="177" width="800"]]
209 +[[image:1735064362593-844.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="153" width="800"]]
202 202  
203 203  In this section:
204 204  
... ... @@ -205,18 +205,18 @@
205 205  * Enable – a flag to start calculation of the charge current limit;
206 206  * Maximum charge current – a maximum allowable value of the charge current (under normal conditions), A;
207 207  * Rate of change – a rate of change the current limit to a new value (0 is for immediate change), A/s;
208 -* Option 1: Limit charge current by the battery SOC and temperature – a flag to enable correction of maximum allowable charging current Kcs depending on SOC and battery temperature;
216 +* Option 1: Limit charge current by the battery SOC and temperature – a flag to enable correction of maximum allowable charging current** Kcs** depending on SOC and battery temperature;
209 209  * Option 1: SOC x Temperature x Factor – the dependence of the correction factor on SOC and battery temperature;
210 -* Option 2: Limit charge current by the contactor temperature – a flag to enable correction of maximum allowable charging current Kcc depending on contactor temperature;
218 +* Option 2: Limit charge current by the contactor temperature – a flag to enable correction of maximum allowable charging current **Kcc** depending on contactor temperature;
211 211  * Option 2: Contactor temperature x Factor – the dependence of the correction factor on SOC and contactor temperature;
212 -* Option 3: Limit charge current by the maximum cell voltage - a flag to enable correction of maximum allowable charging current Kcv depending on maximum cell voltage;
220 +* Option 3: Limit charge current by the maximum cell voltage - a flag to enable correction of maximum allowable charging current **Kcv** depending on maximum cell voltage;
213 213  * Option 3: Cell voltage x Factor – the dependence of the correction factor on maximum cell voltage;
214 -* Option 4: Limit charge current by the cell temperature - a flag to enable correction of maximum allowable charging current Kct depending on maximum cell temperature;
222 +* Option 4: Limit charge current by the cell temperature - a flag to enable correction of maximum allowable charging current **Kct** depending on maximum cell temperature;
215 215  * Option 4: Cell temperature x Factor – the dependence of the correction factor on maximum cell temperature.
216 216  
217 217  Value of the charge current limit at given SOC, temperature, contactors temperature, maximum cell voltage and maximum cell temperature is calculated as follows:
218 218  
219 -Charging current limit = Maximum charging current × Kcs × Kcc × Kcv × Kct
227 +**Charge current limit = Maximum charge current × Kcs × Kcc × Kcv × Kct**
220 220  
221 221  === Discharge map ===
222 222  
... ... @@ -226,7 +226,7 @@
226 226  
227 227  To configure parameters for determining the discharge current limit, select the "Control → Discharge map" section:
228 228  
229 -[[image:1733322637795-310.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="178" width="800"]]
237 +[[image:1735064399985-526.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="152" width="800"]]
230 230  
231 231  In this section:
232 232  
... ... @@ -233,18 +233,18 @@
233 233  * Enable – a flag to start calculation of the discharge current limit;
234 234  * Maximum discharge current – a maximum allowable value of the discharge current (under normal conditions), A;
235 235  * Rate of change – a rate of change the current limit to a new value (0 is for immediate change), A/s;
236 -* Option 1: Limit discharging current by the battery SOC and temperature – a flag to enable correction of maximum allowable discharging current Kds depending on SOC and temperature;
244 +* Option 1: Limit discharging current by the battery SOC and temperature – a flag to enable correction of maximum allowable discharging current **Kds **depending on SOC and temperature;
237 237  * Option 1: SOC x Temperature x Factor – the dependence of the correction factor on SOC and battery temperature;
238 -* Option 2: Limit discharge current by the contactor temperature – a flag to enable correction of maximum allowable discharging current Kdc depending on contactor temperature;
246 +* Option 2: Limit discharge current by the contactor temperature – a flag to enable correction of maximum allowable discharging current **Kdc** depending on contactor temperature;
239 239  * Option 2: Contactor temperature x Factor – the dependence of the correction factor on SOC and contactor temperature;
240 -* Option 3: Limit discharge current by the cell voltage - a flag to enable correction of maximum allowable discharging current Kdv depending on minimum cell voltage;
248 +* Option 3: Limit discharge current by the cell voltage - a flag to enable correction of maximum allowable discharging current **Kdv** depending on minimum cell voltage;
241 241  * Option 3: Cell voltage x Factor – the dependence of the correction factor on minimum cell voltage;
242 -* Option 4: Limit discharge current by the cell temperature - a flag to enable correction of maximum allowable discharging current Kdt depending on maximum cell temperature;
250 +* Option 4: Limit discharge current by the cell temperature - a flag to enable correction of maximum allowable discharging current **Kdt** depending on maximum cell temperature;
243 243  * Option 4: Cell voltage x Factor – the dependence of the correction factor on minimum cell temperature.
244 244  
245 245  Value of the discharge current limit at given SOC, temperature, contactors temperature, minimum cell voltage and maximum cell temperature is calculated as follows:
246 246  
247 -Discharging current limit = Maximum discharging current × Kds × Kdc × Kdv × Kdt
255 +**Discharge current limit = Maximum discharge current × Kds × Kdc × Kdv × Kdt**
248 248  
249 249  === Charge map (PEAK & CONTINUOUS) ===
250 250  
... ... @@ -252,7 +252,7 @@
252 252  
253 253  To configure parameters for determining the charge current limit, select the "Control → Charge map (PEAK & CONTINUOUS)" section:
254 254  
255 -[[image:1733322637796-187.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="145" width="800"]]
263 +[[image:1735064434321-430.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="124" width="800"]]
256 256  
257 257  In this section:
258 258  
... ... @@ -273,7 +273,6 @@
273 273  
274 274  I,,continuous,, = Maximum CONTINUOUS charge current × K,,cc,,
275 275  
276 -
277 277  === Discharge map (PEAK & CONTINUOUS) ===
278 278  
279 279  The BMS Main 3 has an alternative algorithm for the maximum allowed discharging current based on peak and continuous battery operating modes.
... ... @@ -280,7 +280,7 @@
280 280  
281 281  To configure parameters for determining the discharge current limit, select the "Control → Discharge map (PEAK & CONTINUOUS)" section:
282 282  
283 -[[image:1733322735595-661.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="145" width="800"]]
290 +[[image:1735064454708-345.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="124" width="800"]]
284 284  
285 285  In this section:
286 286  
... ... @@ -301,6 +301,118 @@
301 301  
302 302  I,,continuous,, = Maximum CONTINUOUS discharge current × K,,dc,,
303 303  
311 +=== Main contactor ===
312 +
313 +The BMS Main 3 device controls the main contactor. The main contactor is usually placed in the common (minus) battery line for opening the charge and discharge circuits in case of sealing of the charging or discharging contactors.
314 +
315 +The Main contactor algorithm supports the following modes:
316 +
317 +* Always on;
318 +* Automatic.
319 +
320 +In “Always on” mode main contactor closes if all the following is true:
321 +
322 +* Other contactors are open;
323 +* There are no errors from the "Errors 1, 2 ..." bitfileds.
324 +
325 +In “Always on” mode main contactor opens if all the following is true:
326 +
327 +* Other contactors are open;
328 +* There is an error from the the "Errors 1, 2 ..." bitfileds.
329 +
330 +In “Automatic” mode, the main contactor closes by internal algorithms at the same time with other contactors.
331 +
332 +In “On demand” mode, the main contactor closes by external the “Close Main contactor” request.
333 +
334 +(% class="box infomessage" %)
335 +(((
336 +**Note: **when errors occur in the system, the **Main **contactor opens either immediately or with the delay T,,off,, (depends on the settings described below).
337 +)))
338 +
339 +To change the parameters of the main contactor, select the "Control → Main contactor" section:
340 +
341 +[[image:1735064488658-863.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="112" width="800"]]
342 +
343 +In this section:
344 +
345 +* Enable – a flag to enable the main contactor control;
346 +* Algorithm – main contactor control algorithm:
347 +** Always on – contactor is always closed;
348 +** Automatic – contactor closes by internal charge and discharge algorithms;
349 +** On demand – contactor is closed by an external request;
350 +* Time to keep the contactor closed before closing the others – a time for other contactors to be open after the main contactor is closed;
351 +* Delay before opening the contactor – a time which is used to detect conditions for opening the contactor, s;
352 +* Keep the contactor open until the device is restarted – a flag for keeping the main contactor open until the system is reset;
353 +* Errors 1, 2 to open the main contactor – bitfields to choose the errors which will open the main contactor.
354 +
355 +=== Charging status ===
356 +
357 +To change the parameters of charging process status, select the "Control → Charging status" section:
358 +
359 +[[image:1735064935499-941.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="110" width="800"]]In this section:
360 +
361 +* Current to set the "Charging current present" – a current level to generate the "Charging current present" signal, A;
362 +* Current to clear the "Charging current present" – a current level to clear the "Charging current present" signal, A;
363 +* Voltage to clear the “Ready to charge” – a threshold voltage level on the cell, V; if the voltage of any cell is above this level, the “Ready to charge” (hence, the “Allow charging”) signal is cleared;
364 +* Voltage to reset the “Ready to charge” – a tolerant voltage level on the cell, V; if all cell voltages are below the tolerant level, the “Ready to charge” (hence, the “Allow charging”) signal is set;
365 +* Delay before recharging – a time after which the previously opened the allow charging contactor closes again, minute; to disable the operation by timeout set "Delay before recharging" to 0;
366 +* Errors 1, 2 to clear the "Ready to charge" – bitfields to choose the errors which will clear the "Ready to charge" signal.
367 +
368 +(% class="box infomessage" %)
369 +(((
370 +**Note:** The "Allow charging" signal activates under two independent conditions:
371 +1) the voltage on the cells reaches the “Voltage to reset the “Ready to charge"” level and
372 +2) the "Delay before recharging" time has passed since the opening of the allow charging contactor.
373 +)))
374 +
375 +=== Discharging status ===
376 +
377 +To change the parameters of discharging process status, select the "Control → Discharging status" section:
378 +
379 +[[image:1735064980481-209.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="102" width="800"]]In this section:
380 +
381 +* Current to set the "Discharging current present" – a current level to generate the "Discharging current present" signal, А;
382 +* Current to clear the "Discharging current present" – a current level to clear the "Discharging current present" signal, А;
383 +* Voltage to clear the “Ready to discharge” – a threshold voltage level on the cell, V; if the voltage of any cell is below this level, the “Ready to discharge” signal is cleared;
384 +* Voltage to reset the “Ready to discharge” – a tolerant voltage level on the cell, V; if all cells voltages are above the tolerant level, the “Ready to discharge” signal is set;
385 +* Errors 1, 2 to clear the "Ready to discharge" – bitfields to choose the errors which will clear the "Ready to discharge" signal.
386 +
387 +=== Precharge ===
388 +
389 +The BMS Main 3 device can control the precharge contactor. The precharge contactor is used to charge the intermediate capacity with low current and usually placed with the limiting resistor in parallel to charging or discharging contactor.
390 +
391 +BMS Main 3 device detects errors while pre-charging the load capacity by monitoring the current and voltage difference before and after contactors. Also BMS can measure the power dissipated on precharge resistor and generate an error if it greater than configured limit.
392 +
393 +TBA
394 +
395 +To change the parameters of precharge contactor, select the "Control → Precharge" section:
396 +
397 +[[image:1735065073836-743.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="160" width="800"]]
398 +
399 +* Precharge current threshold to finish precharging – a minimum current value at which precharging process assumed to be finished, A;
400 +* Check voltages before and after contactors to finish precharging – a flag to check the voltages before and after contactors to ensure that precharge process has finished and it is allowed to close the discharging contactor;
401 +* Minimum voltage difference to finish precharging – minimal voltage difference before and after contactors at which precharge process is meant to be finished, V;
402 +* Number of precharging attempts – maximum number of precharging attempts before setting the "Precharge error";
403 +* Precharge time – a duration of closing the precharge contactor before closing the discharging contactor, millisecond;
404 +* Relaxation between attempts – a duration between precharge attempts, millisecond;
405 +* Check the power dissipated in the preacharge resistor - a flag to enable the calculation of power dissipated in precharge resistor;
406 +* Precharge resistor resistance, Ohm;
407 +* Maximum allowable power dissipated in the resistor, W;
408 +* Delay before setting the "Precharge error" when checking power, millisecond;
409 +* Delay before clearing the "Precharge error", second;
410 +* Lock the "Precharge error" – a flag to block the error until the device is restarted.
411 +
412 +“Precharge error” generation conditions if any of the following is true:
413 +
414 +* the precharge current does not decrease during the "Precharge time" after "Number of precharging attempts";
415 +* voltages before and after contactors are not equal during the "Precharge time" after "Number of precharging attempts";
416 +* power dissipated on the precharge resistor is above the maximum value during the “Delay before setting the 'Precharge error' when checking power” time.
417 +
418 +(% class="box warningmessage" %)
419 +(((
420 +Behavior of contactors at “Precharge error” is configured in corresponding contactor settings!
421 +)))
422 +
304 304  === Charge ===
305 305  
306 306  There are two contactors that serve charging the battery: a charging contactor and an allow charging contactor. With the help of the allow charging contactor, the BMS commands the charger to start or stop charging.
... ... @@ -311,49 +311,36 @@
311 311  * On charger connected – charging is allowed when there is a signal “Charger connected”;
312 312  * On charge request – charging is allowed when there is a signal “Charge request”.
313 313  
314 -If the "**Always on**" algorithm is selected, the charging contactor and the allow charging contactor are always closed. If at least one of the errors appears:
433 +If the "**Always on**" algorithm is selected, the charging contactor and the allow charging contactor are always closed. If at least one of the errors from the "Errors 1, 2 ..." bitfields appears or one of the signals:
315 315  
316 -* Overvoltage;
317 -* Overcurrent;
318 -* High temperature (CH);
319 -* Low temperature (CH);
320 -* HYG offline (optional);
321 -* Combilift offline (optional);
322 -* Spirit offline (optional);
323 -* Spirit charger error (optional);
324 -* Short circuit (optional);
325 -* High contactor temperature (optional);
326 -* CH contactor cycles error;
327 -* Precharge error (optional);
328 -* Critical error
435 +* Service reset;
436 +* Power down request;
437 +* Inhibit charging,
329 329  
330 -or one of the signals:
331 -
332 -* Service reset
333 -* Power down request
334 -* Inhibit charging
335 -
336 336  both contactors are open (no current flows).
337 337  
338 338  When the algorithm "**On charger connected**" is selected, the control is performed as follows:
339 339  
340 -* If there is a signal “Charger connected” and there are no errors (see the list above), then through the delay time T,,on,, the charging contactor and the allow charging contactor close;
443 +* If there is a signal “Charger connected” and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the charging contactor and the allow charging contactor close;
341 341  * If the signal “Charger connected” disappears, the allow charging contactor opens and after the delay time T,,off,, the charging contactor opens;
342 342  * If in the process of charging the voltage on the cell exceeds the “Ready to charge” level, the allow charging contactor opens (while the charging contactor remains closed);
343 -* If errors in the list above occur the charging contactor and allow charging contactor open.
446 +* If errors from the "Errors 1, 2 ..." bitfields occur the charging contactor and allow charging contactor open.
344 344  
345 345  When the "**On charge request**" algorithm selected, the control is performed as follows:
346 346  
347 -* If there is a signal “Charge request” and there are no errors (see the list above), then through the delay time T,,on,, the charging contactor and the allow charging contactor close;
450 +* If there is a signal “Charge request” and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the charging contactor and the allow charging contactor close;
348 348  * If the signal “Charge request” disappears, the allow charging contactor opens and after the delay time T,,off,, the charging contactor opens;
349 349  * If in the process of charging the voltage on the cell exceeds the “Ready to charge” level, the allow charging contactor opens (while the charging contactor remains closed);
350 -* If errors in the list above occur the charging contactor and allow charging contactor open.
453 +* If errors from the "Errors 1, 2 ..." bitfields occur the charging contactor and allow charging contactor open.
351 351  
352 -Note – When errors occur in the system, the charging contactor opens either immediately or with the delay T,,off,, (depends on the settings described below).
455 +(% class="box infomessage" %)
456 +(((
457 +**Note: **when errors occur in the system, the **Charge **contactor opens either immediately or with the delay T,,off,, (depends on the settings described below).
458 +)))
353 353  
354 354  To change the parameters of the battery charge control algorithm, select the "Control → Charge" section:
355 355  
356 -[[image:1733322798914-813.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="327" width="800"]]
462 +[[image:1735063563460-549.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="262" width="800"]]
357 357  
358 358  In this section:
359 359  
... ... @@ -362,20 +362,15 @@
362 362  ** Always on – charging is always allowed;
363 363  ** On charger connected – charging is allowed when there is a signal “Charger connected”;
364 364  ** On charge request – charging is allowed when there is a signal “Charge request”;
365 -* Current corresponding to charging – a current level to generate the "Charging current present" signal, A;
366 -* Current corresponding to no charging – a current level to clear the "Charging current present" signal, A;
471 +* Allow charging only when the "Ready to charge" signal is set – charging contactor will open if "Ready to charge" signal is cleared;
367 367  * Delay before starting charging – a time delay T,,on,, before closing the charging contactor and the allow charging contactor, millisecond;
368 368  * Delay before stopping charging – a time delay T,,off,, before opening the charging contactor, millisecond;
474 +* Control the precharging contactor – a flag that allows control of the precharging contactor while closing the charge contactor (see [[Precharge>>path:#HPrecharge]]);
475 +* Errors 1, 2 to open the charging contactor – bitfields to choose the errors which will open the charging contactor;
369 369  * Use custom delays before stopping charging (on errors) – a flag to enable manual settings of time delays T,,off,, for specific errors;
370 -* Custom delay: <error> – specific error delay, millisecond;
477 +* Custom delay: <error> – delay for specific error, millisecond;
371 371  * Switch off the charging contactor on errors without delay – a flag to protectively open the charging contactor without a delay. In the opposite case, when an error is detected, the charging contactor opens always with the delay “Delay before stopping charging”;
372 -* Control the precharging contactor – a flag that allows control of the precharging contactor;
373 -* Voltage to clear the “Ready to charge” – a threshold voltage level on the cell, V; if the voltage of any cell is above this level, the “Ready to charge” (hence, the “Allow charging”) signal is cleared;
374 -* Voltage to reset the “Ready to charge” – a tolerant voltage level on the cell, V; if all cell voltages are below the tolerant level, the “Ready to charge” (hence, the “Allow charging”) signal is set;
375 -* Delay before recharging – a time after which the previously opened the allow charging contactor closes again, minute; to disable the operation by timeout set "Delay before recharging" to 0.
376 376  
377 -Note – The allow charging contactor closes under two independent conditions: 1) the voltage on the cells reaches the “Voltage to reset the “Ready to charge"” level and 2) the "Delay before recharging" time has passed since the opening of the allow charging contactor.
378 -
379 379  === Discharge ===
380 380  
381 381  The device controls the discharging contactor to connect battery to the load.
... ... @@ -386,26 +386,8 @@
386 386  * On charger disconnected – load is connected when there is no signal “Charger connected”;
387 387  * On discharge request – load is connected when there is signal “Discharge request”.
388 388  
389 -When the algorithm "**Always on**" is selected, the discharging contactor is always closed. If at least one of the errors appears:
490 +When the algorithm "**Always on**" is selected, the discharging contactor is always closed. If at least one of the errors from the "Errors 1, 2 ..." bitfields appears or one of the signals:
390 390  
391 -* Undervoltage;
392 -* Overvoltage (optional);
393 -* Overcurrent;
394 -* High temperature (DCH);
395 -* Low temperature (DCH) (optional);
396 -* HYG offline (optional);
397 -* Combilift offline (optional);
398 -* Spirit offline (optional);
399 -* Spirit charger error (optional);
400 -* Short circuit (optional);
401 -* High contactor temperature (optional);
402 -* Unallowable charging;
403 -* DCH contactor cycles error;
404 -* Precharge error (optional);
405 -* Critical error
406 -
407 -or one of the signals:
408 -
409 409  * Service reset
410 410  * Power down request
411 411  * Inhibit discharging
... ... @@ -414,21 +414,22 @@
414 414  
415 415  If the algorithm "**On charger disconnected**" is selected, the control is performed as follows:
416 416  
417 -* if there is no signal “Charger connected”, the charging contactor is open and there are no errors (see the list above), then through the delay time T,,on,, the discharging contactor closes;
418 -* If the signal “Charger connected” appears or errors occur (see the list above), then after the delay time T,,off,, the discharging contactor opens.
500 +* if there is no signal “Charger connected”, the charging contactor is open and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the discharging contactor closes;
501 +* If the signal “Charger connected” appears or errors occur (see the "Errors 1, 2 ..." bitfields), then after the delay time T,,off,, the discharging contactor opens.
419 419  
420 420  When the "**On discharge request**" algorithm selected, the control is performed as follows:
421 421  
422 -* if there is signal “Discharge request”, the charging contactor is open and there are no errors (see the list above), then through the delay time T,,on,, the discharging contactor closes;
423 -* If the signal “Discharge request” disappears or errors occur (see the list above), then after the delay time T,,off,, the discharging contactor opens.
505 +* if there is signal “Discharge request”, the charging contactor is open and there are no errors (see the "Errors 1, 2 ..." bitfields), then through the delay time T,,on,, the discharging contactor closes;
506 +* If the signal “Discharge request” disappears or errors occur (see the "Errors 1, 2 ..." bitfields), then after the delay time T,,off,, the discharging contactor opens.
424 424  
425 -Note – In case of errors in the system operation, the opening of the discharging contactor is performed either immediately or with a delay T,,off,, (depends on the settings described below).
508 +(% class="box infomessage" %)
509 +(((
510 +**Note: **when errors occur in the system, the **Discharge **contactor opens either immediately or with the delay T,,off,, (depends on the settings described below).
511 +)))
426 426  
427 -The device supports controlling the precharging contactor. The duration of switching on the precharging contactor before closing the discharging (load) contactor is adjusted.
428 -
429 429  To change the parameters of the battery discharge control algorithm, select the "Control → Discharge" section:
430 430  
431 -[[image:1733323750262-841.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="360" width="800"]]
515 +[[image:1735064038329-836.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="273" width="800"]]
432 432  
433 433  In this section:
434 434  
... ... @@ -437,30 +437,51 @@
437 437  ** Always on – load is always connected;
438 438  ** On charger disconnected – load is connected when there is no signal “Charger connected”;
439 439  ** On discharge request – load is connected when there is signal “Discharge request”;
440 -* Current corresponding to discharging – a current level to generate the "Discharging current present" signal, А;
441 -* Current indicating no discharging – a current level to clear the "Discharging current present" signal, А;
524 +* Allow charging only when the "Ready to discharge" signal is set – discharging contactor will open if "Ready to discharge" signal is cleared;
442 442  * Delay before starting discharging – a time delay T,,on,, before closing the discharging contactor, millisecond;
443 443  * Delay before stopping discharging – a time delay T,,off,, before opening the discharging contactor, millisecond;
527 +* Control the precharging contactor – a flag that allows control of the precharging contactor while closing the discharge contactor (see [[Precharge>>doc:||anchor="HPrecharge"]]);
528 +* Errors 1, 2 to open the discharging contactor – bitfields to choose the errors which will open the discharging contactor;
444 444  * Use custom delays before stopping discharging (on errors) – a flag to enable manual settings of time delays T,,off,, for specific errors;
445 445  * Custom delay: <error> – specific error delay, millisecond;
446 446  * Switch off the discharging contactor on errors without delay – a flag to protectively open the discharging contactor without a delay. In the opposite case, when an error is detected, the discharging contactor opens always with the delay “Delay before stopping discharging”.
447 -* Precharge time – a duration of closing the precharge contactor before closing the discharging contactor, millisecond;
448 -* Check voltages before and after contactors to finish precharging – a flag to check the voltages before and after contactors to ensure that precharge process has finished and it is allowed to close the discharging contactor;
449 -* Minimum voltage difference to finish precharging – minimal voltage difference before and after contactors at which precharge process is meant to be finished, V;
450 -* Voltage to clear the “Ready to discharge” – a threshold voltage level on the cell, V; if the voltage of any cell is below this level, the “Ready to discharge” signal is cleared;
451 -* Voltage to reset the “Ready to discharge” – a tolerant voltage level on the cell, V; if all cells voltages are above the tolerant level, the “Ready to discharge” signal is set;
452 452  
453 453  === Charge/Discharge ===
454 454  
455 -The BMS Main 3 device can control the charging/discharging contactor, which combines algorithms of charging and discharging contactor. It behaves as a charging contactor when “Charge request” or “Charger connected” is set, otherwise – as a discharging contactor.
535 +The BMS Main 3 device can control the charge/discharge contactor, which combines algorithms of charging and discharging contactor.
456 456  
537 +Charge/Discharge contactor has three algorithms of operation:
538 +
539 +* Dependent (on Charging and Discharging signals) - Charge/Discharge contactor depends on Charge and Discharge algorithms and their signals and behaves as Charging contactor if Charging signal is set, otherwise – as Discharging contactor;
540 +* Independent (Always) - Charge/Discharge contactor is always closed if there is no errors;
541 +* Independent (on Charge request or Discharge request) - Charge/Discharge contactor is based on its own controller that listen to Charge and Discharge requests and closes if one of these signals occurs.
542 +
543 +TBA
544 +
545 +(% class="box infomessage" %)
546 +(((
547 +**Note: **when errors occur in the system, the **Charge/Discharge **contactor opens either immediately or with the delay T,,off,, (depends on the settings described below).
548 +)))
549 +
457 457  The charging/discharging contactor control is configured in the “Control – Charge/Discharge” section:
458 458  
459 -[[image:1733322827919-875.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="85" width="800"]]
552 +[[image:1735122153011-166.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="162" width="800"]]
460 460  
461 461  In this section:
462 462  
463 463  * Enable – a flag to enable the charge/discharge controller.
557 +* Algorithm:
558 +** Dependent (on Charging and Discharging signals) - Charge/Discharge contactor depends on Charge and Discharge algorithms and their signals and behaves as Charging contactor if Charging signal is set, otherwise – as Discharging contactor;
559 +** Independent (Always) - Charge/Discharge contactor is always closed if there is no errors;
560 +** Independent (on Charge request or Discharge request);
561 +* Delay before starting charging or discharging, millisecond;
562 +* Delay before stopping charging or discharging, millisecond;
563 +* Control the precharging contactor – a flag that enables control of precharging contactor while closing the charge/discharge contactor;
564 +* Emulate the "Charging" and "Discharging" signals – a flag to enable generation of "Charging" and "Discharging" signals when closing charge/discharge contactor;
565 +* Errors 1, 2 to prevent CHARGING through charging/discharging contactor, Errors 1, 2 to prevent DISCHARGING through charging/discharging contactor – bitfields to choose the errors which will open the charging/discharging contactor. This bitfields are combined by bitwise OR and intended to separate settings for charging and discharging processes;
566 +* Errors 1, 2 which affect the contactor only if battery CHARGING is detected – a bitfield to choose the errors which will trigger only if charging current is present. This bitfield is combined with "Errors 1, 2 to prevent CHARGING through charging/discharging contactor" by bitwise AND;
567 +* Errors 1, 2 which affect the contactor only if battery DISCHARGING is detected – a bitfield to choose the errors which will trigger only if discharging current is present. This bitfield is combined with "Errors 1, 2 to prevent DISCHARGING through charging/discharging contactor" by bitwise AND;
568 +* Switch off the charging/discharging contactor on errors without delay – a flag to protectively open the charging/discharging contactor without a delay. In the opposite case, when an error is detected, the charging/discharging contactor opens always with the delay “Delay before stopping discharging”.
464 464  
465 465  === Discharge (AUX) ===
466 466  
... ... @@ -472,11 +472,11 @@
472 472  
473 473  * the battery has low SOC;
474 474  * the battery voltage is out of range;
475 -* the battery system errors are detected.
580 +* the errors are detected (configured in the "Errors 1, 2 ..." bitfields).
476 476  
477 477  To change the parameters of the powering of external equipment, select the "Control → Discharge (AUX)" section:
478 478  
479 -[[image:1733322827920-878.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="130" width="800"]]
584 +[[image:1735066190419-838.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="161" width="800"]]
480 480  
481 481  In this section:
482 482  
... ... @@ -484,66 +484,14 @@
484 484  * Switch off the discharging (AUX) contactor if the SOC is too low;
485 485  * Minimum SOC – a minimum SOC value, when reached, the auxiliary (AUX) discharging contactor opens, %;
486 486  * Tolerant SOC – a permissive SOC value, upon reaching which the auxiliary (AUX) discharging contactor re-closes, %;
592 +* Switch off the discharging (AUX) contactor if the cell voltage is out of the range;
593 +* Minimum cell voltage, V;
594 +* Maximum cell voltage, V;
487 487  * Switch off the discharging (AUX) contactor if the battery voltage is out of the range;
488 -* Minimum voltage – minimum battery voltage, V;
489 -* Maximum voltage – maximum battery voltage, V;
490 -* Switch off the discharging (AUX) contactor on errors – the auxiliary (AUX) discharging contactor opens if the following errors occur: Undervoltage, Overcurrent, High temperature (DCH), Short circuit, Critical error.
596 +* Minimum battery voltage, V;
597 +* Maximum battery voltage, V;
598 +* Errors 1, 2 to open the auxiliary discharging contactor bitfields to choose the errors which will open the auxiliary discharging contactor.
491 491  
492 -=== Main contactor ===
493 -
494 -The BMS Main 3 device controls the main contactor. The main contactor is usually placed in the common (minus) battery line for opening the charge and discharge circuits in case of sealing of the charging or discharging contactors.
495 -
496 -The Main contactor algorithm supports the following modes:
497 -
498 -* Always on;
499 -* Automatic;
500 -* On demand.
501 -
502 -In “Always on” mode main contactor closes if all the following is true:
503 -
504 -* Charging contactor is open;
505 -* Discharging contactor is open;
506 -* There are no errors from the list below:
507 -** Overcurrent;
508 -** Undervoltage;
509 -** Overvoltage;
510 -** High temperature (CH);
511 -** High temperature (DCH);
512 -** Unallowable charging;
513 -** Critical error.
514 -
515 -In “Always on” mode main contactor opens if all the following is true:
516 -
517 -* Charging contactor is open;
518 -* Discharging contactor is open;
519 -* There is an error from the list below:
520 -** Overcurrent;
521 -** Undervoltage;
522 -** Overvoltage;
523 -** High temperature (CH);
524 -** High temperature (DCH);
525 -** Unallowable charging;
526 -** Critical error.
527 -
528 -In “Automatic” mode, the main contactor closes by internal charging and discharging algorithms at the same time with Precharging, Charging and Discharging contactors.
529 -
530 -In “On demand” mode, the main contactor closes by external the “Close Main contactor” request.
531 -
532 -To change the parameters of the main contactor, select the "Control → Main contactor" section:
533 -
534 -[[image:1733322872744-536.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="105" width="800"]]
535 -
536 -In this section:
537 -
538 -* Enable – a flag to enable the main contactor control;
539 -* Algorithm – main contactor control algorithm:
540 -** Always on – contactor is always closed;
541 -** Automatic – contactor closes by internal charge and discharge algorithms;
542 -** On demand – contactor is closed by an external request;
543 -* Time to keep the contactor closed before closing the others – a time for other contactors to be open after the main contactor is closed;
544 -* Delay before opening the contactor – a time which is used to detect conditions for opening the contactor, s;
545 -* Keep the contactor open until the device is restarted – a flag for keeping the main contactor open until the system is reset.
546 -
547 547  === Cell balancing ===
548 548  
549 549  Balancing makes the voltage of all cells equal to the minimum cell voltage.
... ... @@ -557,20 +557,25 @@
557 557  A balancing resistor is connected to the cell if the following conditions are simultaneously met:
558 558  
559 559  * the voltage on the cell is higher than the balancing start voltage;
560 -* the difference between the voltage on the cell and the minimum voltage among the battery cells is greater than the balancing start threshold.
613 +* the difference between the voltage on the cell and the minimum voltage among the battery cells is greater than the balancing start threshold;
561 561  
562 562  A balancing resistor is disconnected from the cell if any of the following conditions are met:
563 563  
564 -* the voltage on the cell is less than the balancing start voltage;
617 +* the voltage on the cell is less than the balancing stop voltage;
565 565  * the difference between the voltage on the cell and the minimum voltage among the battery cells is less than the balancing stop threshold.
566 566  
620 +(% class="box infomessage" %)
621 +(((
567 567  If the “High logic temperature” occurs, then the balancing of the cells connected to the overheated BMS Logic device will not be performed.
623 +)))
568 568  
569 569  The BMS Main 3 can enable the cell balancing by the external “Balancing request” signal. Balancing process will be started to cells which the voltage is higher than the balancing start voltage and the difference between the cell voltage and the minimum voltage among all the cells is greater than the balancing stop threshold.
570 570  
627 +BMS Main 3 can force a cell balancing, if its voltage is higher than estimated value.
628 +
571 571  To change the cell balancing parameters, select the "Control → Cell balancing" section:
572 572  
573 -[[image:1733322883460-118.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="114" width="800"]]
631 +[[image:1735065702806-422.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="130" width="800"]]
574 574  
575 575  In this section:
576 576  
... ... @@ -579,12 +579,14 @@
579 579  ** Balance on charge – balancing is performed while and after the charging (in the “Charge ON” and “Charge OFF” states);
580 580  ** Balance on charge or relaxed - balancing is performed while and after the charging and in the relaxed state (in “Charge ON”, “Charge OFF”, “Relaxed (after charging)” and “Relaxed (after discharging)” states);
581 581  ** Balance always – balancing is always performed regardless the battery state;
582 -
583 -[[image:1733322883462-975.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="74" width="600"]]
584 -
640 +* Balancing condition:
641 +** Automatic – balancing will be performed automatically if needed conditions are met;
642 +** On balancing request – balancing will start only if a remote request is received. In this case cells will start to balance regardless the "Voltage deviation to start balancing" value;
585 585  * Minimum cell voltage to start balancing, V;
586 586  * Voltage deviation to start balancing;
587 587  * Voltage deviation to stop balancing;
646 +* Voltage for forced balancing – if cell voltage is above this value, it will start discharging through balancing resistor;
647 +* Maximum allowable temperature of BMS Logic devices, ºC;
588 588  * Command to discharge all cells – a flag to force the balancing of all cells.
589 589  
590 590  === Series balancing ===
... ... @@ -662,7 +662,10 @@
662 662  
663 663  * the minimum temperature among all cells of the battery is greater than the “Tolerant cell temperature” value during the “Delay before stopping the heater” time.
664 664  
665 -If there is the "Heater" signal, the heater contactor closes and/or a signal is output to the corresponding digital output.
725 +(% class="box infomessage" %)
726 +(((
727 +If there is the "Heater" signal, the heater contactor closes and/or a signal is set to the corresponding digital output.
728 +)))
666 666  
667 667  === Cooler ===
668 668  
... ... @@ -689,7 +689,10 @@
689 689  
690 690  * the maximum temperature among all cells of the battery is less than the “Tolerant cell temperature” value during the “Delay before stopping the cooler” time.
691 691  
692 -If there is the "Cooler" signal, the cooler contactor closes and/or a signal is output to the corresponding digital output.
755 +(% class="box infomessage" %)
756 +(((
757 +If there is the "Cooler" signal, the cooler contactor closes and/or a signal is set to the corresponding digital output.
758 +)))
693 693  
694 694  === High voltage ===
695 695  
... ... @@ -707,7 +707,10 @@
707 707  
708 708  The BMS Main 3 implements a self-diagnostics of high-voltage measurement lines. If measurement line breaks or high-voltage polarity is wrong, “High voltage fault” is generated.
709 709  
710 -**If there is the “High voltage fault”, the “Critical error” is generated and all contactors open.**
776 +(% class="box warningmessage" %)
777 +(((
778 +If there is the “High voltage fault”, **the “Critical error” is generated.**
779 +)))
711 711  
712 712  === Cell analysis ===
713 713  
1735063563460-549.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +59.6 KB
Content
1735064038329-836.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +62.0 KB
Content
1735064362593-844.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +35.8 KB
Content
1735064399985-526.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +36.1 KB
Content
1735064434321-430.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +27.5 KB
Content
1735064454708-345.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +27.7 KB
Content
1735064488658-863.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +24.9 KB
Content
1735064583408-498.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +23.4 KB
Content
1735064935499-941.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +25.7 KB
Content
1735064980481-209.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +24.2 KB
Content
1735065073836-743.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +38.8 KB
Content
1735065666891-686.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +29.0 KB
Content
1735065702806-422.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +27.2 KB
Content
1735066190419-838.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +37.2 KB
Content
1735122153011-166.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +54.3 KB
Content