Changes for page 3.3 Control

Last modified by Admin on 2025/04/09 12:14

From version 10.3
edited by Admin
on 2024/12/24 16:20
Change comment: There is no comment for this version
To version 11.2
edited by Admin
on 2024/12/24 17:38
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -106,7 +106,7 @@
106 106  
107 107  Calculation of the resistance of cells is carried out in two ways. The first method is used when the battery passes from a relaxation state to a charge or discharge state, wherein the cell resistance value
108 108  
109 -{{formula fontSize="NORMAL" imageType="PNG"}}
109 +{{formula fontSize="SMALL" imageType="PNG"}}
110 110  R = \frac{U-U_{ocv}}{I_{stable}}
111 111  {{/formula}}
112 112  
... ... @@ -114,12 +114,17 @@
114 114  
115 115  The second method is used for a stepwise change in the current through the cell, while the value of the cell resistance:
116 116  
117 -R = (U,,2,,-U,,1,,) / (I,,stable2,,-I,,stable1,,) provided that | I,,stable2,,-I,,stable1,, | > 0.2 × Q,,max,,
117 +{{formula fontSize="SMALL"}}
118 +R = \frac{U_2-U_1}{I_{stable2}-I_{stable1}}
119 +{{/formula}}
118 118  
121 +provided that
119 119  
120 -(Q,,max,, is the maximum cell capacity),
123 +{{formula fontSize="SMALL"}}
124 +| I_{stable2}-I_{stable1} | > 0.2 × Qmax
125 +{{/formula}}
121 121  
122 -where U,,2,, is the voltage on the cell at the moment when the stabilized current I,,stable2,, is flowing through it; U,,1,, the voltage on the cell at the moment when the stabilized current I,,stable1,, flowing through it.
127 +where Q,,max,, the maximum cell capacity,U,,2,, — voltage on the cell at the moment when the stabilized current I,,stable2,, is flowing through it; U,,1,, the voltage on the cell at the moment when the stabilized current I,,stable1,, flowing through it.
123 123  
124 124  The stabilized current I,,stable,, = I, if during the stabilization time the instantaneous current I is in the range from 0.95 × I to 1.05 × I.
125 125  
... ... @@ -135,7 +135,7 @@
135 135  * Minimum SOC – minimum cell SOC value for resistance calculation;
136 136  * Maximum SOC – maximum cell SOC value for resistance calculation.
137 137  
138 -The calculated resistance is accepted by the system as valid (and therefore updated) if its value is in the range from Resistance/2 to “Maximum resistance factor” × Resistance, where "Resistance" is the nominal resistance of the cell (see [[Common settings>>doc:||anchor="HCommonsettings"]]). If the calculated resistance value is greater than the value (Maximum resistance factor × Resistance), the updated resistance value will be equal to the value (Maximum resistance factor × Resistance).
143 +The calculated resistance is accepted by the system as valid (and therefore updated) if its value is in the range from Resistance / 2 to “Maximum resistance factor” × Resistance, where "Resistance" is the nominal resistance of the cell (see [[Common settings>>doc:||anchor="HCommonsettings"]]). If the calculated resistance value is greater than the value (Maximum resistance factor × Resistance), the updated resistance value will be equal to the value (Maximum resistance factor × Resistance).
139 139  
140 140  === Low SOC (signal) ===
141 141  
... ... @@ -270,7 +270,6 @@
270 270  
271 271  I,,continuous,, = Maximum CONTINUOUS charge current × K,,cc,,
272 272  
273 -
274 274  === Discharge map (PEAK & CONTINUOUS) ===
275 275  
276 276  The BMS Main 3 has an alternative algorithm for the maximum allowed discharging current based on peak and continuous battery operating modes.
... ... @@ -298,6 +298,73 @@
298 298  
299 299  I,,continuous,, = Maximum CONTINUOUS discharge current × K,,dc,,
300 300  
305 +=== Main contactor ===
306 +
307 +The BMS Main 3 device controls the main contactor. The main contactor is usually placed in the common (minus) battery line for opening the charge and discharge circuits in case of sealing of the charging or discharging contactors.
308 +
309 +The Main contactor algorithm supports the following modes:
310 +
311 +* Always on;
312 +* Automatic;
313 +* On demand.
314 +
315 +In “Always on” mode main contactor closes if all the following is true:
316 +
317 +* Charging contactor is open;
318 +* Discharging contactor is open;
319 +* There are no errors from the list below:
320 +** Overcurrent;
321 +** Undervoltage;
322 +** Overvoltage;
323 +** High temperature (CH);
324 +** High temperature (DCH);
325 +** Unallowable charging;
326 +** Critical error.
327 +
328 +In “Always on” mode main contactor opens if all the following is true:
329 +
330 +* Charging contactor is open;
331 +* Discharging contactor is open;
332 +* There is an error from the list below:
333 +** Overcurrent;
334 +** Undervoltage;
335 +** Overvoltage;
336 +** High temperature (CH);
337 +** High temperature (DCH);
338 +** Unallowable charging;
339 +** Critical error.
340 +
341 +In “Automatic” mode, the main contactor closes by internal charging and discharging algorithms at the same time with Precharging, Charging and Discharging contactors.
342 +
343 +In “On demand” mode, the main contactor closes by external the “Close Main contactor” request.
344 +
345 +To change the parameters of the main contactor, select the "Control → Main contactor" section:
346 +
347 +[[image:1733322872744-536.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="105" width="800"]]
348 +
349 +In this section:
350 +
351 +* Enable – a flag to enable the main contactor control;
352 +* Algorithm – main contactor control algorithm:
353 +** Always on – contactor is always closed;
354 +** Automatic – contactor closes by internal charge and discharge algorithms;
355 +** On demand – contactor is closed by an external request;
356 +* Time to keep the contactor closed before closing the others – a time for other contactors to be open after the main contactor is closed;
357 +* Delay before opening the contactor – a time which is used to detect conditions for opening the contactor, s;
358 +* Keep the contactor open until the device is restarted – a flag for keeping the main contactor open until the system is reset.
359 +
360 +=== Charging status ===
361 +
362 +TBA
363 +
364 +=== Discharging status ===
365 +
366 +TBA
367 +
368 +=== Precharge ===
369 +
370 +TBA
371 +
301 301  === Charge ===
302 302  
303 303  There are two contactors that serve charging the battery: a charging contactor and an allow charging contactor. With the help of the allow charging contactor, the BMS commands the charger to start or stop charging.
... ... @@ -486,61 +486,6 @@
486 486  * Maximum voltage – maximum battery voltage, V;
487 487  * Switch off the discharging (AUX) contactor on errors – the auxiliary (AUX) discharging contactor opens if the following errors occur: Undervoltage, Overcurrent, High temperature (DCH), Short circuit, Critical error.
488 488  
489 -=== Main contactor ===
490 -
491 -The BMS Main 3 device controls the main contactor. The main contactor is usually placed in the common (minus) battery line for opening the charge and discharge circuits in case of sealing of the charging or discharging contactors.
492 -
493 -The Main contactor algorithm supports the following modes:
494 -
495 -* Always on;
496 -* Automatic;
497 -* On demand.
498 -
499 -In “Always on” mode main contactor closes if all the following is true:
500 -
501 -* Charging contactor is open;
502 -* Discharging contactor is open;
503 -* There are no errors from the list below:
504 -** Overcurrent;
505 -** Undervoltage;
506 -** Overvoltage;
507 -** High temperature (CH);
508 -** High temperature (DCH);
509 -** Unallowable charging;
510 -** Critical error.
511 -
512 -In “Always on” mode main contactor opens if all the following is true:
513 -
514 -* Charging contactor is open;
515 -* Discharging contactor is open;
516 -* There is an error from the list below:
517 -** Overcurrent;
518 -** Undervoltage;
519 -** Overvoltage;
520 -** High temperature (CH);
521 -** High temperature (DCH);
522 -** Unallowable charging;
523 -** Critical error.
524 -
525 -In “Automatic” mode, the main contactor closes by internal charging and discharging algorithms at the same time with Precharging, Charging and Discharging contactors.
526 -
527 -In “On demand” mode, the main contactor closes by external the “Close Main contactor” request.
528 -
529 -To change the parameters of the main contactor, select the "Control → Main contactor" section:
530 -
531 -[[image:1733322872744-536.png||data-xwiki-image-style-alignment="center" data-xwiki-image-style-border="true" height="105" width="800"]]
532 -
533 -In this section:
534 -
535 -* Enable – a flag to enable the main contactor control;
536 -* Algorithm – main contactor control algorithm:
537 -** Always on – contactor is always closed;
538 -** Automatic – contactor closes by internal charge and discharge algorithms;
539 -** On demand – contactor is closed by an external request;
540 -* Time to keep the contactor closed before closing the others – a time for other contactors to be open after the main contactor is closed;
541 -* Delay before opening the contactor – a time which is used to detect conditions for opening the contactor, s;
542 -* Keep the contactor open until the device is restarted – a flag for keeping the main contactor open until the system is reset.
543 -
544 544  === Cell balancing ===
545 545  
546 546  Balancing makes the voltage of all cells equal to the minimum cell voltage.