... ... @@ -1,6 +1,24 @@
1 1  (% data-numbered-headings-start="2" style="--numbered-headings-start: 1;font-size: 0px;color: rgba(0, 0, 0, 0.0);margin-bottom: 0px; margin-top: 0px;" %)
2 2  = Installation and connection =
3 3  
4 +== Safety rules ==
5 +
6 +To perform the protection functions, the BMS must be able to disconnect the battery from the load and charger. To do this, at least one contactor able to break the load and charge circuits must be connected to the BMS.
7 +
8 +Before use, configure the system. Proper operation of the BMS is possible only if it is correctly configured.
9 +
10 +It is not recommended to use the system in batteries formed by several series of cells connected in parallel. To increase capacity, it is recommended to connect several cells in parallel groups, and then connect the groups in series.
11 +
12 +(% class="box warningmessage" %)
13 +(((
14 +The BMS can be connected to batteries with life-threatening and health-hazardous voltage levels. When working with high-voltage batteries, observe electrical safety regulations, use safety glasses, protective clothing, insulated tools and appliances. To prevent the damage of device avoid electrostatic discharges while working with the battery.
15 +)))
16 +
17 +(% class="box errormessage" %)
18 +(((
19 +**The system is not designed to operate with batteries whose total voltage exceeds 3000 V.**
20 +)))
21 +
4 4  == Installation procedure ==
5 5  
6 6  The mounting location of the BMS Main 3 / BMS Main 3X device must be protected from mechanical particles (dust, dirt, large objects) and water. The installation location must provide easy access for subsequent connection to the device connectors.
... ... @@ -368,18 +368,6 @@
368 368  
369 369  == Connection procedure ==
370 370  
371 -The BMS can connect to batteries with voltage levels dangerous to life and health. When working with high voltage batteries, follow electrical safety rules, use safety glasses, protective clothing, insulated tools and devices.
372 -
373 -(% class="box errormessage" %)
374 -(((
375 -**The system is not designed to operate with batteries with total voltage more than 3000V.**
376 -)))
377 -
378 -(% class="box warningmessage" %)
379 -(((
380 -Before connection, configure the device (see [[Settings>>doc:Battery management systems.BMS Main 3.3\. Configuration.WebHome]]). Correct operation of the BMS system is only possible with correct configuration.
381 -)))
382 -
383 383  All operations to connect the device must be carried out with the supply voltage removed.