Changes for page 2. Installation and connection
Last modified by Admin on 2026/04/02 13:49
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -169,8 +169,23 @@ 169 169 |**5**|**CAN_EXT_L**|CAN L line for communication with external equipment 170 170 |**6**|**GND**|Ground 171 171 172 -=== J1 –jumper forswitchingRS-485bus terminalresistor===172 +=== X14 – header for high-voltage bus after contactors (minus) === 173 173 174 +Receptacle Housing: Molex 436450200. Terminals: Molex 43030 175 + 176 +[[image:1733316843397-336.png||data-xwiki-image-style-alignment="center" height="53" width="79"]] 177 + 178 +|**Pin**|**Name**|**Description** 179 +|**1**|**IN2-**|Minus of the high-voltage bus (after contactors) 180 +|**2**|**IN2-**|Minus of the high-voltage bus (after contactors) 181 + 182 +(% class="box warningmessage" %) 183 +((( 184 +The connected voltage must not exceed 1000V. 185 +))) 186 + 187 +=== J1 – jumper for switching RS-485-1 bus terminal resistor === 188 + 174 174 [[image:1733316982359-759.png||data-xwiki-image-style-alignment="center" height="77" width="148"]] 175 175 176 176 To connect a terminal resistor between the **RS485_1_A** and **RS485_1_B** lines, install a jumper. The jumper is installed according to the table: