... ... @@ -1,42 +1,26 @@
1 1  (% data-numbered-headings-start="2" style="--numbered-headings-start: 1;font-size: 0px;color: rgba(0, 0, 0, 0.0);margin-bottom: 0px; margin-top: 0px;" %)
2 2  = Installation and connection =
3 3  
4 -== Safety rules ==
5 -
6 -To perform the protection functions, the BMS must be able to disconnect the battery from the load and charger. To do this, **at least one contactor** able to break the load and charge circuits must be connected to the BMS.
7 -
8 -Before use, **configure the system**. Proper operation of the BMS is possible only if it is correctly configured.
9 -
10 -(% class="box errormessage" %)
11 -(((
12 -The BMS can be connected to batteries with life-threatening and health-hazardous voltage levels. When working with high-voltage batteries, observe electrical safety regulations, use safety glasses, protective clothing, insulated tools and appliances. To prevent the damage of device avoid electrostatic discharges while working with the battery.
13 -)))
14 -
15 -(% class="box errormessage" %)
16 -(((
17 -The system is not designed to operate with batteries whose total voltage exceeds 3000 V.
18 -)))
19 -
20 20  == Installation procedure ==
21 21  
22 -The mounting location of the BMS Main 2R device must be protected from mechanical particles (dust, dirt, large objects) and water. The installation location must provide easy access for subsequent connection to the device connectors.
6 +The mounting location of the BMS Main 3 / BMS Main 3X device must be protected from mechanical particles (dust, dirt, large objects) and water. The installation location must provide easy access for subsequent connection to the device connectors.
23 23  
24 24  Overall and mounting dimensions are shown in figure below.
25 25  
26 -[[image:1774349658793-888.0b.STEP.JPG||data-xwiki-image-style-alignment="center" height="522" width="450"]](% title="Click and drag to resize" %)​
10 +(% data-widget="image" contenteditable="false" tabindex="-1" %)[[image:1733311711953-224.png||data-xwiki-image-style-alignment="center" height="566" width="775"]](% title="Click and drag to resize" %)​
27 27  
28 28  |**Parameter**|**Value**
29 -|Overall dimensions (length × width × height), mm|120 × 120 × 16
30 -|Mounting dimensions (length × width), mm|114 × 114
13 +|Overall dimensions (length × width × height), mm|200 × 123 × 12
14 +|Mounting dimensions (length × width), mm|194 × 114
31 31  |Mounting holes|M3
32 32  
33 33  == Headers ==
34 34  
35 -The location and designation of connectors on the BMS Main 2R device are shown below.
19 +The location and designation of connectors on the BMS Main 3 / BMS Main 3X device are shown below.
36 36  
37 37  (% contenteditable="false" tabindex="-1" %)
38 38  (((
39 -[[image:1774455018488-627.png||data-xwiki-image-style-alignment="center"]]
23 +[[image:1732119505664-787.png||data-xwiki-image-style-alignment="center" height="417" width="684"]]
40 40  )))
41 41  
42 42  (% class="box warningmessage" %)
... ... @@ -45,23 +45,16 @@
45 45  All headers are shown from the device side!
46 46  )))
47 47  
48 -=== X1 – header for discrete inputs and outputs ===
32 +=== X1 – header to power the device ===
49 49  
50 -Receptacle Housing: Hirose ZE05-8DS-HU/R. Terminals: Hirose ZE05-2022SCF
51 -
52 52  (% class="wikigeneratedid" id="H" %)
53 -[[image:1732198937514-731.png||data-xwiki-image-style-alignment="center" height="85" width="272"]]
35 +(% data-widget="image" contenteditable="false" tabindex="-1" %)[[image:1732121673277-246.png||data-xwiki-image-style-alignment="center" height="85" width="200"]]
54 54  
55 55  |**Pin**|**Name**|**Description**
56 -|**1–8**|**GND**|Ground
57 -|**9**|**DO_1**|Discrete output 1 “open drain” (5V
58 -|**10**|**DO_2**|Discrete output 2 “open drain” (60 V, 1A)
59 -|**11**|**DO_3**|Discrete output 3 “open drain” (60 V, 1A)
60 -|**12**|**DO_4**|Discrete output 4 “open drain” (60 V, 1A)
61 -|**13**|**DI_4**|
62 -|**14**|**DI_3**|Power-on signal
63 -|**15**|**DI_2**|Power-on signal (battery charge requirement)
64 -|**16**|**DI_1**|Power line (9-32V)
38 +|**1–2, 5–6**|**GND**|Ground
39 +|**3**|**KEYRUN**|Power-on signal
40 +|**4**|**CHARGE_ON**|Power-on signal (battery charge requirement)
41 +|**7–8**|**VIN**|Power line (9-32V)
65 65  
66 66  Power supply connection diagram:
67 67  
... ... @@ -69,8 +69,6 @@
69 69  
70 70  === X2 – header for contactors ===
71 71  
72 -Receptacle Housing: Hirose ZE05-12DS-HU/R. Terminals: Hirose ZE05-2022SCF
73 -
74 74  (% aria-label="1732121695049-411.png image widget" data-widget="image" contenteditable="false" role="region" tabindex="-1" %)[[image:1732121695049-411.png||data-xwiki-image-style-alignment="center" height="87" width="267"]](% title="Click and drag to resize" %)​
75 75  
76 76  |**Pin**|**Name**|**Description**
... ... @@ -88,8 +88,6 @@
88 88  
89 89  === (% title="Click and drag to resize" %)​(%%)X3 – header for discrete inputs and outputs ===
90 90  
91 -Receptacle Housing: Hirose ZE05-24DS-HU/R. Terminals: Hirose ZE05-2022SCF
92 -
93 93  (% aria-label="1732121811285-182.png image widget" data-widget="image" contenteditable="false" role="region" tabindex="-1" %)[[image:1732121811285-182.png||data-xwiki-image-style-alignment="center" height="94" width="531"]]
94 94  
95 95  |**Pin**|**Name**|**Description**
... ... @@ -119,8 +119,6 @@
119 119  
120 120  === X4 – header for HVIL ===
121 121  
122 -Receptacle Housing: Hirose ZE05-4S-HU/R. Terminals: Hirose ZE05-2022SCF
123 -
124 124  [[image:1732122015188-642.png||data-xwiki-image-style-alignment="center" height="64" width="150"]]
125 125  
126 126  |**Pin**|**Name**|**Description**
... ... @@ -129,7 +129,7 @@
129 129  |**3**|**HVIL_IN**|Input of the current measurement circuit in the current loop (higher potential, measuring shunt input)
130 130  |**4**|**HVIL_PWR**|Current loop power supply (max 5V, 25mA)
131 131  
132 - If the BMS Main 2R device generates current in a current loop, the current loop must be connected to the **HVIL_PWR** and **HVIL_IN** pins. If BMS Main 2R is a passive current loop meter, then the current loop must be connected to the **HVIL_IN** and **HVIL_OUT** pins.
103 + If the BMS Main 3 / BMS Main 3X device generates current in a current loop, the current loop must be connected to the **HVIL_PWR** and **HVIL_IN** pins. If BMS Main 3 / BMS Main 3X is a passive current loop meter, then the current loop must be connected to the **HVIL_IN** and **HVIL_OUT** pins.
133 133  
134 134  Connection diagram to the current loop:
135 135  
... ... @@ -137,8 +137,6 @@
137 137  
138 138  === X5 – header for current and temperature sensors ===
139 139  
140 -Receptacle Housing: Hirose ZE05-16DS-HU/R. Terminals: Hirose ZE05-2022SCF
141 -
142 142  [[image:1733311958053-469.png||data-xwiki-image-style-alignment="center" height="83" width="349"]]
143 143  
144 144  (% style="width:539px" %)
... ... @@ -170,8 +170,6 @@
170 170  
171 171  === X6 – header for CAN1 and RS-485-1 (external buses) ===
172 172  
173 -Receptacle Housing: Hirose ZE05-5S-HU/R. Terminals: Hirose ZE05-2022SCF
174 -
175 175  [[image:1733316218666-814.png||data-xwiki-image-style-alignment="center" height="55" width="162"]]
176 176  
177 177  |**Pin**|**Name**|**Description**
... ... @@ -191,8 +191,6 @@
191 191  
192 192  === X7 – header for CAN2 (internal bus) ===
193 193  
194 -Receptacle Housing: Hirose ZE05-4S-HU/R. Terminals: Hirose ZE05-2022SCF
195 -
196 196  [[image:1733316517741-698.png||data-xwiki-image-style-alignment="center" height="59" width="144"]]
197 197  
198 198  |**Pin**|**Name**|**Description**
... ... @@ -207,8 +207,6 @@
207 207  
208 208  === X8 – header for CAN3 ===
209 209  
210 -Receptacle Housing: Hirose ZE05-4S-HU/R. Terminals: Hirose ZE05-2022SCF
211 -
212 212  [[image:1733316517741-698.png||data-xwiki-image-style-alignment="center" height="59" width="144"]]
213 213  
214 214  |**Pin**|**Name**|**Description**
... ... @@ -230,8 +230,6 @@
230 230  
231 231  === X9 – header for BMS Logic (RS-485-2) ===
232 232  
233 -Receptacle Housing: Hirose ZE05-4S-HU/R. Terminals: Hirose ZE05-2022SCF
234 -
235 235  [[image:1733316517741-698.png||data-xwiki-image-style-alignment="center" height="59" width="144"]]
236 236  
237 237  |**Pin**|**Name**|**Description**
... ... @@ -253,12 +253,10 @@
253 253  
254 254  === X10 – miniUSB connector ===
255 255  
256 -The miniUSB connector is used to configure the parameters of the BMS Main 2R device.
217 +The miniUSB connector is used to configure the parameters of the BMS Main 3 / BMS Main 3X device.
257 257  
258 258  === X11 – header for high-voltage bus before contactors (plus) ===
259 259  
260 -Receptacle Housing: Molex 436450200. Terminals: Molex 43030
261 -
262 262  [[image:1733316780753-798.png||data-xwiki-image-style-alignment="center" height="60" width="91"]]
263 263  
264 264  |**Pin**|**Name**|**Description**
... ... @@ -272,8 +272,6 @@
272 272  
273 273  === X12 – header for high-voltage bus before contactors (minus) ===
274 274  
275 -Receptacle Housing: Molex 436450200. Terminals: Molex 43030
276 -
277 277  [[image:1733316843397-336.png||data-xwiki-image-style-alignment="center" height="53" width="79"]]
278 278  
279 279  |**Pin**|**Name**|**Description**
... ... @@ -287,8 +287,6 @@
287 287  
288 288  === X13 – header for high-voltage bus after contactors (plus) ===
289 289  
290 -Receptacle Housing: Molex 436450200. Terminals: Molex 43030
291 -
292 292  [[image:1733316780753-798.png||data-xwiki-image-style-alignment="center" height="60" width="91"]]
293 293  
294 294  |**Pin**|**Name**|**Description**
... ... @@ -302,8 +302,6 @@
302 302  
303 303  === X14 – header for high-voltage bus after contactors (minus) ===
304 304  
305 -Receptacle Housing: Molex 436450200. Terminals: Molex 43030
306 -
307 307  [[image:1733316843397-336.png||data-xwiki-image-style-alignment="center" height="53" width="79"]]
308 308  
309 309  |**Pin**|**Name**|**Description**
... ... @@ -345,7 +345,7 @@
345 345  
346 346  === J5, J6 – jumpers for emergency opening of contactors when removing discrete input signals DIN7, DIN8 ===
347 347  
348 -The BMS Main 2R device implements a circuit for hardware opening of power contactors when the discrete input signal DIN7 and/or DIN8 (voltage level 9-32V) is removed. To enable this function, jumper J5 and/or J6 must be installed.
301 +The BMS Main 3 / BMS Main 3X device implements a circuit for hardware opening of power contactors when the discrete input signal DIN7 and/or DIN8 (voltage level 9-32V) is removed. To enable this function, jumper J5 and/or J6 must be installed.
349 349  
350 350  == Indicators ==
351 351  
... ... @@ -389,6 +389,18 @@
389 389  
390 390  == Connection procedure ==
391 391  
345 +The BMS can connect to batteries with voltage levels dangerous to life and health. When working with high voltage batteries, follow electrical safety rules, use safety glasses, protective clothing, insulated tools and devices.
346 +
347 +(% class="box errormessage" %)
348 +(((
349 +**The system is not designed to operate with batteries with total voltage more than 3000V.**
350 +)))
351 +
352 +(% class="box warningmessage" %)
353 +(((
354 +Before connection, configure the device (see [[Settings>>doc:Battery management systems.BMS Main 3.3\. Configuration.WebHome]]). Correct operation of the BMS system is only possible with correct configuration.
355 +)))
356 +
392 392  All operations to connect the device must be carried out with the supply voltage removed.
393 393  
394 394  * Connect the power contactors to header X2.
... ... @@ -399,5 +399,5 @@
399 399  * Connect the high-voltage network integrity circuit (if necessary) to header X4.
400 400  * Connect external devices (if necessary) to header X6.
401 401  * Connect other devices (BMS Indication, BMS Display, if necessary) to header X7.
402 -* If the BMS Main 2R is the last device on the RS-485-1, CAN1, or CAN2 bus, install jumpers J1-J3.
367 +* If the BMS Main 3 / BMS Main 3X is the last device on the RS-485-1, CAN1, or CAN2 bus, install jumpers J1-J3.
403 403  * Connect an external power supply to header X1. The device will start when there is a 9-32V power supply and one of the KEYRUN or CHARGE_ON signals with a voltage of more than 8.5V is supplied.
1731517180930-597.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.admin
Size
... ... @@ -1,1 +1,0 @@
1 -5.5 KB
Content
1731517188900-976.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.admin
Size
... ... @@ -1,1 +1,0 @@
1 -3.1 KB
Content
1731517195672-298.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.admin
Size
... ... @@ -1,1 +1,0 @@
1 -3.2 KB
Content
1732198827034-560.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.admin
Size
... ... @@ -1,1 +1,0 @@
1 -1.2 KB
Content
1732198890482-787.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.admin
Size
... ... @@ -1,1 +1,0 @@
1 -2.0 KB
Content
1732198896526-660.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.admin
Size
... ... @@ -1,1 +1,0 @@
1 -1.7 KB
Content
1732198937514-731.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.admin
Size
... ... @@ -1,1 +1,0 @@
1 -6.6 KB
Content
1741620022836-867.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.admin
Size
... ... @@ -1,1 +1,0 @@
1 -9.7 KB
Content
1774349658793-888.0b.STEP.JPG
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.admin
Size
... ... @@ -1,1 +1,0 @@
1 -42.2 KB
Content
1774453953377-602.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.admin
Size
... ... @@ -1,1 +1,0 @@
1 -7.8 KB
Content
1774455018488-627.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.admin
Size
... ... @@ -1,1 +1,0 @@
1 -35.6 KB