Changes for page 5.2 Modbus protocol

Last modified by Admin on 2026/04/24 10:30

From version 7.2
edited by Admin
on 2024/12/11 11:21
Change comment: Update document after refactoring.
To version 8.3
edited by Admin
on 2025/02/04 10:04
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -268,7 +268,7 @@
268 268  
269 269  bits 4-15 — not used.
270 270  )))|(% style="width:96px" %)U16
271 -|(% style="width:92px" %)**0x200E**|(% style="width:94px" %)2|(% style="width:368px" %)(((
271 +|(% style="width:92px" %)**0x200E-0x200F**|(% style="width:94px" %)2|(% style="width:368px" %)(((
272 272  Errors 2 (bitfield):
273 273  
274 274  bit 0 – "Low CH temperature", temperature is too low for charging;
... ... @@ -299,7 +299,11 @@
299 299  
300 300  bit 13 – “General error”;
301 301  
302 -bits 14-31 — reserved.
302 +bit 14-16 — reserved (set to 0);
303 +
304 +bit 17 — “Precharge error”;
305 +
306 +bits 19-31 — not used.
303 303  )))|(% style="width:96px" %)U32
304 304  |(% style="width:92px" %)**0x2010**|(% style="width:94px" %)1|(% style="width:368px" %)Address or the BMS Logic device whose parameters are in registers 0x2011-0x20C9|(% style="width:96px" %)U16
305 305  |(% style="width:92px" %)**0x2011**|(% style="width:94px" %)1|(% style="width:368px" %)(((
... ... @@ -353,13 +353,19 @@
353 353  |(% style="width:92px" %)**0x20F4**|(% style="width:94px" %)1|(% style="width:368px" %)(((
354 354  Discrete input signals 2 (bitfield):
355 355  
356 -bit 0 “Fuse 2”;
360 +bit 0 “Fuse 2”;
357 357  
358 -bit 1 “Fuse 3”;
362 +bit 1 “Fuse 3”;
359 359  
360 -bit 2 “Circuit breaker status”;
364 +bit 2 “Circuit breaker status”;
361 361  
362 -bits 3-15 – reserved.
366 +bit 3 — signal "Balancing request";
367 +
368 +bit 4 — signal "Close Main contactor";
369 +
370 +bit 5 — signal "Close External 1";
371 +
372 +bits 6-15 — not used.
363 363  )))|(% style="width:96px" %)U16
364 364  |(% style="width:92px" %)**0x2100-0x2101**|(% style="width:94px" %)2|(% style="width:368px" %)Battery state of charge (SOC), %|(% style="width:96px" %)REAL32
365 365  |(% style="width:92px" %)**0x2102**|(% style="width:94px" %)1|(% style="width:368px" %)Number of BMS Logic devices|(% style="width:96px" %)U16