... ... @@ -1,1 +1,1 @@ 1 - drafts.BMS Main 2\.1.5\. Communication protocols.WebHome1 +Battery management systems.BMS Main 2\.1.5\. Communication protocols.WebHome - Content
-
... ... @@ -240,7 +240,11 @@ 240 240 241 241 bit 25 – “Power up”; 242 242 243 -bits 26-31 – reserved. 243 +bit 26 — signal “External 1”; 244 + 245 +bit 27 — signal “Heater (AUX)”; 246 + 247 +bits 28-31 — not used. 244 244 )))|(% style="width:96px" %)U32 245 245 |(% style="width:92px" %)**0x200B**|(% style="width:94px" %)1|(% style="width:368px" %)((( 246 246 Discrete output signals (bitfield): ... ... @@ -268,7 +268,7 @@ 268 268 269 269 bits 4-15 — not used. 270 270 )))|(% style="width:96px" %)U16 271 -|(% style="width:92px" %)**0x200E**|(% style="width:94px" %)2|(% style="width:368px" %)((( 275 +|(% style="width:92px" %)**0x200E-0x200F**|(% style="width:94px" %)2|(% style="width:368px" %)((( 272 272 Errors 2 (bitfield): 273 273 274 274 bit 0 – "Low CH temperature", temperature is too low for charging; ... ... @@ -299,7 +299,11 @@ 299 299 300 300 bit 13 – “General error”; 301 301 302 -bits 14-31 — reserved. 306 +bit 14-16 — reserved (set to 0); 307 + 308 +bit 17 — “Precharge error”; 309 + 310 +bits 18-31 — not used. 303 303 )))|(% style="width:96px" %)U32 304 304 |(% style="width:92px" %)**0x2010**|(% style="width:94px" %)1|(% style="width:368px" %)Address or the BMS Logic device whose parameters are in registers 0x2011-0x20C9|(% style="width:96px" %)U16 305 305 |(% style="width:92px" %)**0x2011**|(% style="width:94px" %)1|(% style="width:368px" %)((( ... ... @@ -353,13 +353,19 @@ 353 353 |(% style="width:92px" %)**0x20F4**|(% style="width:94px" %)1|(% style="width:368px" %)((( 354 354 Discrete input signals 2 (bitfield): 355 355 356 -bit 0 –“Fuse 2”;364 +bit 0 — “Fuse 2”; 357 357 358 -bit 1 –“Fuse 3”;366 +bit 1 — “Fuse 3”; 359 359 360 -bit 2 –“Circuit breaker status”;368 +bit 2 — “Circuit breaker status”; 361 361 362 -bits 3-15 – reserved. 370 +bit 3 — signal "Balancing request"; 371 + 372 +bit 4 — signal "Close Main contactor"; 373 + 374 +bit 5 — signal "Close External 1"; 375 + 376 +bits 6-15 — not used. 363 363 )))|(% style="width:96px" %)U16 364 364 |(% style="width:92px" %)**0x2100-0x2101**|(% style="width:94px" %)2|(% style="width:368px" %)Battery state of charge (SOC), %|(% style="width:96px" %)REAL32 365 365 |(% style="width:92px" %)**0x2102**|(% style="width:94px" %)1|(% style="width:368px" %)Number of BMS Logic devices|(% style="width:96px" %)U16