Changes for page 5.2 Modbus protocol
Last modified by Admin on 2026/04/24 10:30
Summary
-
Page properties (3 modified, 0 added, 0 removed)
Details
- Page properties
-
- Title
-
... ... @@ -1,1 +1,1 @@ 1 - 5.2 Modbus protocol1 +4.2 Modbus protocol - Parent
-
... ... @@ -1,1 +1,1 @@ 1 -drafts.BMS Main 2\.1. 5\. Communication protocols.WebHome1 +drafts.BMS Main 2\.1.4\. Communication protocols.WebHome - Content
-
... ... @@ -1,4 +1,4 @@ 1 -== 5.2.1 General information ==1 +== 4.2.1 General information == 2 2 3 3 The BMS Main 2.x device provides the information about the battery system using Modbus protocol. The BMS is a Modbus-server and it responds to the Modbus-client’s commands. 4 4 ... ... @@ -28,7 +28,7 @@ 28 28 29 29 Words are in the **little endian**. 30 30 31 -== 5.2.2 Input registers ==31 +== 4.2.2 Input registers == 32 32 33 33 (% style="width:651px" %) 34 34 |(% style="width:92px" %)**Register address**|(% style="width:94px" %)**Number of registers**|(% style="width:368px" %)**Content**|(% style="width:96px" %)**Type** ... ... @@ -480,7 +480,7 @@ 480 480 |(% style="width:92px" %)**0x2426**|(% style="width:94px" %)2|(% style="width:368px" %)Maximum charge current, A|(% style="width:96px" %)REAL32 481 481 |(% style="width:92px" %)**0x2428**|(% style="width:94px" %)2|(% style="width:368px" %)Maximum discharge current, A|(% style="width:96px" %)REAL32 482 482 483 -== 5.2.3 Holding registers ==483 +== 4.2.3 Holding registers == 484 484 485 485 (% style="width:653px" %) 486 486 |(% style="width:92px" %)**Register address**|(% style="width:94px" %)**Number of registers**|(% style="width:368px" %)**Content**|(% style="width:96px" %)**Type**