... ... @@ -1,1 +1,1 @@ 1 -Battery management systems.BMS Main 2\.1.5\. Communication protocols.WebHome 1 +Battery management systems.BMS Main 2\.1 (End-of-Life).5\. Communication protocols.WebHome - Content
-
... ... @@ -680,3 +680,39 @@ 680 680 681 681 2-65535 – use the physical input "Fuse 3". 682 682 )))|(% style="width:96px" %)U16 683 +|(% style="width:92px" %)**0x5112**|(% style="width:94px" %)1|(% style="width:368px" %)((( 684 +Software control of the "Circuit breaker status" signal. Allowable values: 685 + 686 +0 – clear the signal; 687 + 688 +1 – set the signal; 689 + 690 +2-65535 – use the physical input "Circuit breaker status". 691 +)))|(% style="width:96px" %)U16 692 +|(% style="width:92px" %)**0x5113**|(% style="width:94px" %)1|(% style="width:368px" %)((( 693 +Software control of the "Balancing request" signal. Allowable values: 694 + 695 +0 – clear the signal; 696 + 697 +1 – set the signal; 698 + 699 +2-65535 – use the physical input "Balancing request". 700 +)))|(% style="width:96px" %)U16 701 +|(% style="width:92px" %)**0x5114**|(% style="width:94px" %)1|(% style="width:368px" %)((( 702 +Software control of the "Close Main contactor" signal. Allowable values: 703 + 704 +0 – clear the signal; 705 + 706 +1 – set the signal; 707 + 708 +2-65535 – use the physical input "Close Main contactor". 709 +)))|(% style="width:96px" %)U16 710 +|(% style="width:92px" %)**0x5115**|(% style="width:94px" %)1|(% style="width:368px" %)((( 711 +Software control of the "Close External 1" signal. Allowable values: 712 + 713 +0 – clear the signal; 714 + 715 +1 – set the signal; 716 + 717 +2-65535 – use the physical input "Close External 1". 718 +)))|(% style="width:96px" %)U16