Wiki source code of 3.6 Battery protection
Hide last authors
author | version | line-number | content |
---|---|---|---|
![]() |
1.1 | 1 | The BMS Main 2.x board continuously monitors the state of the cells, BMS Logic boards, the external environment and, when detecting abnormalities, protects the battery and system components from damage. |
2 | |||
3 | == 3.6.1 Overcurrent protection == | ||
4 | |||
5 | To change the current protection of the battery, select the menu "Protections → Overcurrent protection": | ||
![]() |
2.2 | 6 | |
![]() |
2.3 | 7 | [[Overcurrent protection settings>>image:1732211959984-118.png||data-xwiki-image-style-alignment="center" height="266" width="386"]] |
8 | |||
9 | |||
10 | In this section: | ||
11 | |||
12 | * Enable – a flag to enable the protection; | ||
13 | * Maximum charging current, А; | ||
14 | * Tolerant charging current, А; | ||
15 | * Maximum discharging current, А; | ||
16 | * Tolerant discharging current, А; | ||
17 | * Delay before setting the error, second; | ||
18 | * Delay before clearing the error, second; | ||
19 | * Lock the error until the device is reset – a flag to block the error until the board is restarted. | ||
20 | |||
21 | As a result of operation of the current protection, the "Overcurrent" error is generated. | ||
22 | |||
23 | Error generation conditions: | ||
24 | |||
25 | * the current is positive (charging), and its modulo value is greater than the “Maximum charging current” value for the “Delay before setting the error” time; | ||
26 | * the current is negative (discharging), and its modulo value is greater than the “Maximum discharging current” value for the “Delay before setting the error” time. | ||
27 | |||
28 | Conditions for removing the error: | ||
29 | |||
30 | * the current is positive (charging) or zero, and its modulo value is less than the “Tolerant charging current” value for the “Delay before clearing the error” time; | ||
31 | * the current is negative (discharging), and its modulo value is less than the “Tolerant discharging current” value for the “Delay before clearing the error” time. | ||
32 | |||
33 | (% class="box infomessage" %) | ||
34 | ((( | ||
35 | If there is the "Overcurrent" error, the charging relay and discharging relay open. | ||
36 | ))) | ||
![]() |
3.2 | 37 | |
38 | == 3.6.2 Undervoltage protection == | ||
39 | |||
40 | The board implements battery protection from too low or too high voltage on the cells. | ||
41 | |||
42 | To change the battery protection parameters from low voltage on the cells, select the menu "Protections → Undervoltage protection": | ||
43 | |||
![]() |
3.3 | 44 | [[Undervoltage protection settings>>image:1732212212350-294.png||data-xwiki-image-style-alignment="center" height="207" width="359"]] |
45 | |||
46 | In this section: | ||
47 | |||
48 | * Enable – a flag to enable the protection; | ||
49 | * Minimum cell voltage, V; | ||
50 | * Tolerant cell voltage, V; | ||
51 | * Delay before setting the error, second; | ||
52 | * Delay before clearing the error, second; | ||
53 | * Lock the error until the device is reset. | ||
54 | |||
55 | As a result of the operation of battery protection from low voltage, the "Undervoltage" error is generated. | ||
56 | |||
57 | Error generation conditions: | ||
58 | |||
59 | * the minimum voltage among all cells of the battery is less than the “Minimum cell voltage” value for the “Delay before setting the error” time. | ||
60 | |||
61 | Conditions for removing the error: | ||
62 | |||
63 | * the minimum voltage among all cells of the battery is greater than the “Tolerant cell voltage” value for the “Delay before clearing the error” time. | ||
64 | |||
65 | (% class="box infomessage" %) | ||
66 | ((( | ||
67 | If there is the "Undervoltage" error, the discharging relay opens. | ||
68 | ))) | ||
69 | |||
![]() |
4.2 | 70 | 3.6.3 Overvoltage protection |
71 | |||
72 | To change the battery protection parameters from high voltage on the cells, select the menu "Protections → Overvoltage protection": | ||
73 | |||
74 | [[image:1732212357972-295.png]] | ||
75 | |||
![]() |
4.3 | 76 | In this section: |
77 | |||
78 | * Enable – a flag to enable the protection; | ||
79 | * Maximum cell voltage, V; | ||
80 | * Tolerant cell voltage, V; | ||
81 | * Delay before setting the error, second; | ||
82 | * Delay before clearing the error, second; | ||
83 | * Switch off the discharging relay on error – a flag to open the discharging relay when the "Overvoltage" error is generated; | ||
84 | * Lock the error until the device is reset. | ||
85 | |||
86 | As a result of the operation of the battery protection from high voltage, the "Overvoltage" error is generated. | ||
87 | |||
88 | Error generation conditions: | ||
89 | |||
90 | * the maximum voltage among all cells of the battery is greater than the “Maximum cell voltage” value for the “Delay before setting the error” time. | ||
91 | |||
92 | Conditions for removing the error: | ||
93 | |||
94 | * the maximum voltage among all cells of the battery is less than the “Tolerant cell voltage” value for the “Delay before clearing the error” time. | ||
95 | |||
96 | (% class="box infomessage" %) | ||
97 | ((( | ||
98 | If there is the "Overvoltage" error, the charging relay and discharging relay opens (if the “Switch off the discharging relay on error” flag is set). | ||
99 | ))) | ||
100 | |||
101 | 3.6.4 Low temperature protection | ||
102 | |||
![]() |
4.4 | 103 | 3.6.5 High temperature protection |
104 | |||
105 |