Wiki source code of 3.6 Battery protection
Hide last authors
author | version | line-number | content |
---|---|---|---|
![]() |
1.1 | 1 | The BMS Main 2.x board continuously monitors the state of the cells, BMS Logic boards, the external environment and, when detecting abnormalities, protects the battery and system components from damage. |
2 | |||
3 | == 3.6.1 Overcurrent protection == | ||
4 | |||
5 | To change the current protection of the battery, select the menu "Protections → Overcurrent protection": | ||
![]() |
2.2 | 6 | |
![]() |
2.3 | 7 | [[Overcurrent protection settings>>image:1732211959984-118.png||data-xwiki-image-style-alignment="center" height="266" width="386"]] |
8 | |||
![]() |
4.13 | 9 | In this section: |
![]() |
2.3 | 10 | |
11 | * Enable – a flag to enable the protection; | ||
12 | * Maximum charging current, А; | ||
13 | * Tolerant charging current, А; | ||
14 | * Maximum discharging current, А; | ||
15 | * Tolerant discharging current, А; | ||
16 | * Delay before setting the error, second; | ||
17 | * Delay before clearing the error, second; | ||
18 | * Lock the error until the device is reset – a flag to block the error until the board is restarted. | ||
19 | |||
20 | As a result of operation of the current protection, the "Overcurrent" error is generated. | ||
21 | |||
22 | Error generation conditions: | ||
23 | |||
24 | * the current is positive (charging), and its modulo value is greater than the “Maximum charging current” value for the “Delay before setting the error” time; | ||
25 | * the current is negative (discharging), and its modulo value is greater than the “Maximum discharging current” value for the “Delay before setting the error” time. | ||
26 | |||
27 | Conditions for removing the error: | ||
28 | |||
29 | * the current is positive (charging) or zero, and its modulo value is less than the “Tolerant charging current” value for the “Delay before clearing the error” time; | ||
30 | * the current is negative (discharging), and its modulo value is less than the “Tolerant discharging current” value for the “Delay before clearing the error” time. | ||
31 | |||
32 | (% class="box infomessage" %) | ||
33 | ((( | ||
![]() |
4.13 | 34 | If there is the "Overcurrent" error, the charging and discharging relay open. |
![]() |
2.3 | 35 | ))) |
![]() |
3.2 | 36 | |
37 | == 3.6.2 Undervoltage protection == | ||
38 | |||
39 | The board implements battery protection from too low or too high voltage on the cells. | ||
40 | |||
41 | To change the battery protection parameters from low voltage on the cells, select the menu "Protections → Undervoltage protection": | ||
42 | |||
![]() |
3.3 | 43 | [[Undervoltage protection settings>>image:1732212212350-294.png||data-xwiki-image-style-alignment="center" height="207" width="359"]] |
44 | |||
45 | In this section: | ||
46 | |||
47 | * Enable – a flag to enable the protection; | ||
48 | * Minimum cell voltage, V; | ||
49 | * Tolerant cell voltage, V; | ||
50 | * Delay before setting the error, second; | ||
51 | * Delay before clearing the error, second; | ||
52 | * Lock the error until the device is reset. | ||
53 | |||
54 | As a result of the operation of battery protection from low voltage, the "Undervoltage" error is generated. | ||
55 | |||
56 | Error generation conditions: | ||
57 | |||
58 | * the minimum voltage among all cells of the battery is less than the “Minimum cell voltage” value for the “Delay before setting the error” time. | ||
59 | |||
60 | Conditions for removing the error: | ||
61 | |||
62 | * the minimum voltage among all cells of the battery is greater than the “Tolerant cell voltage” value for the “Delay before clearing the error” time. | ||
63 | |||
64 | (% class="box infomessage" %) | ||
65 | ((( | ||
66 | If there is the "Undervoltage" error, the discharging relay opens. | ||
67 | ))) | ||
68 | |||
![]() |
4.2 | 69 | 3.6.3 Overvoltage protection |
70 | |||
71 | To change the battery protection parameters from high voltage on the cells, select the menu "Protections → Overvoltage protection": | ||
72 | |||
73 | [[image:1732212357972-295.png]] | ||
74 | |||
![]() |
4.3 | 75 | In this section: |
76 | |||
77 | * Enable – a flag to enable the protection; | ||
78 | * Maximum cell voltage, V; | ||
79 | * Tolerant cell voltage, V; | ||
80 | * Delay before setting the error, second; | ||
81 | * Delay before clearing the error, second; | ||
82 | * Switch off the discharging relay on error – a flag to open the discharging relay when the "Overvoltage" error is generated; | ||
83 | * Lock the error until the device is reset. | ||
84 | |||
85 | As a result of the operation of the battery protection from high voltage, the "Overvoltage" error is generated. | ||
86 | |||
87 | Error generation conditions: | ||
88 | |||
89 | * the maximum voltage among all cells of the battery is greater than the “Maximum cell voltage” value for the “Delay before setting the error” time. | ||
90 | |||
91 | Conditions for removing the error: | ||
92 | |||
93 | * the maximum voltage among all cells of the battery is less than the “Tolerant cell voltage” value for the “Delay before clearing the error” time. | ||
94 | |||
95 | (% class="box infomessage" %) | ||
96 | ((( | ||
97 | If there is the "Overvoltage" error, the charging relay and discharging relay opens (if the “Switch off the discharging relay on error” flag is set). | ||
98 | ))) | ||
99 | |||
![]() |
4.10 | 100 | == 3.6.4 Low temperature protection == |
![]() |
4.3 | 101 | |
![]() |
4.11 | 102 | The board implements battery protection from too low temperature. |
![]() |
4.4 | 103 | |
![]() |
4.11 | 104 | To change the battery protection parameters from low temperature, select the menu "Protections → Low temperature protection": |
105 | |||
106 | |||
107 | In this section: | ||
108 | |||
109 | * Enable – a flag to enable the protection; | ||
110 | * Minimum charging temperature, °C; | ||
111 | * Tolerant charging temperature, °C; | ||
112 | * Minimum discharging temperature, °C; | ||
113 | * Tolerant discharging temperature, °C; | ||
114 | * Delay before setting the error, second; | ||
115 | * Delay before clearing the error, second; | ||
116 | * Lock the error until the device is reset. | ||
117 | |||
118 | As a result of the operation of the battery protection from low temperature, the "Low CH temperature" or “Low DCH temperature” error is generated. | ||
119 | |||
120 | Error generation conditions: | ||
121 | |||
122 | * the minimum temperature among all cells of the battery is less than the “Minimum charging (discharging) temperature” value for the “Delay before setting the error” time. | ||
123 | |||
124 | Conditions for removing the error: | ||
125 | |||
126 | * the minimum temperature among all cells of the battery is greater than the “Tolerant charging (discharging) temperature” value for the “Delay before clearing the error” time. | ||
127 | |||
128 | (% class="box infomessage" %) | ||
129 | ((( | ||
![]() |
4.12 | 130 | If there is the "Low CH temperature" error, the charging relay opens. |
131 | If there is the "Low DCH temperature" error, the discharging relay opens. | ||
![]() |
4.11 | 132 | ))) |
133 | |||
![]() |
4.10 | 134 | == 3.6.5 High temperature protection == |
![]() |
4.5 | 135 | |
![]() |
4.11 | 136 | The board implements battery protection from too high temperature. |
137 | |||
138 | To change the battery protection parameters from high temperature, select the menu "Protections → High temperature protection": | ||
139 | |||
![]() |
4.12 | 140 | |
![]() |
4.11 | 141 | In this section: |
142 | |||
143 | * Enable – a flag to enable the protection; | ||
144 | * Maximum charging temperature, °C; | ||
145 | * Tolerant charging temperature, °C; | ||
146 | * Maximum discharging temperature, °C; | ||
147 | * Tolerant discharging temperature, °C; | ||
148 | * Delay before setting the error, second; | ||
149 | * Delay before clearing the error, second; | ||
150 | * Lock the error until the device is reset. | ||
151 | |||
152 | As a result of the operation of the battery protection from high temperature, the "High CH temperature" or “High DCH temperature” error is generated. | ||
153 | |||
154 | Error generation conditions: | ||
155 | |||
156 | * the maximum temperature among all cells of the battery is greater than the “Maximum charging (discharging) temperature” value for the “Delay before setting the error” time. | ||
157 | |||
158 | Conditions for removing the error: | ||
159 | |||
160 | * the maximum temperature among all cells of the battery is less than the “Tolerant charging (discharging) temperature” value for the “Delay before clearing the error” time. | ||
161 | |||
162 | (% class="box infomessage" %) | ||
163 | ((( | ||
164 | If there is the "High CH temperature" error, the charging relay opens. | ||
165 | If there is the "High DCH temperature" error, the discharging relay opens. | ||
166 | ))) | ||
167 | |||
![]() |
4.10 | 168 | == 3.6.6 Battery cover protection == |
![]() |
4.5 | 169 | |
![]() |
4.12 | 170 | To change the protection parameters from opening the battery cover, select the menu "Protections → Battery cover protection": |
171 | |||
172 | In this section: | ||
173 | |||
174 | * Enable – a flag to enable the protection; | ||
175 | * Delay before setting the error, second; | ||
176 | * Delay before clearing the error, second; | ||
177 | * Lock the error until the device is reset. | ||
178 | |||
179 | As a result of the operation of the protection against opening the battery cover, the “Battery cover error” is generated. | ||
180 | |||
181 | Error generation conditions: | ||
182 | |||
183 | * there is a signal from the battery cover during the “Delay before setting the error” time. | ||
184 | |||
185 | Conditions for removing the error: | ||
186 | |||
187 | * no signal from the battery cover during the “Delay before clearing the error” time. | ||
188 | |||
189 | (% class="box warningmessage" %) | ||
190 | ((( | ||
191 | **If there is the "Battery cover error", the “Critical error” is generated and all relays open.** | ||
192 | ))) | ||
193 | |||
![]() |
4.13 | 194 | == 3.6.7 High humidity protection == |
![]() |
4.10 | 195 | |
![]() |
4.13 | 196 | The board can protect the battery from high humidity and water. |
197 | |||
198 | To change the protection parameters of the battery from high humidity, select the menu "Protections → High humidity protection": | ||
199 | |||
200 | In this section: | ||
201 | |||
202 | * Enable – a flag to enable the protection; | ||
203 | * Maximum humidty, RH%; | ||
204 | * Tolerant humidty, RH%; | ||
205 | * Delay before setting the error, second; | ||
206 | * Delay before clearing the error, second; | ||
207 | * Lock the error until the device is reset. | ||
208 | |||
209 | As a result of the operation of the battery protection from high humidity, the "High humidity" error is generated. | ||
210 | |||
211 | Error generation conditions: | ||
212 | |||
213 | * the measured humidity is greater than “Maximum humidity” during the “Delay before setting the error” time. | ||
214 | |||
215 | Conditions for removing the error: | ||
216 | |||
217 | * the measured humidity is less than the “Tolerant humidity” during the “Delay before clearing the error” time. | ||
218 | |||
219 | If there is the "High humidity" error, no action is taken. The error is indicative. | ||
220 | |||
221 | |||
![]() |
4.10 | 222 | == 3.6.8 Water protection == |
223 | |||
224 | == 3.6.9 Current sensor error == | ||
225 | |||
226 | == 3.6.10 Short circuit protection == | ||
227 | |||
228 | == 3.6.11 Contactor high temperature protection == | ||
229 | |||
230 | == 3.6.12 Unallowable charging protection == | ||
231 | |||
232 | == 3.6.13 Stuck contactor protection == | ||
233 | |||
234 | == 3.6.14 Contactor feedback check == | ||
235 | |||
236 | == 3.6.15 Charging contactor cycles protection == | ||
237 | |||
238 | == 3.6.16 Discharging contactor cycles protection == | ||
239 | |||
240 | == 3.6.17 Temperature sensor error == | ||
241 | |||
242 | == 3.6.18 Logic high temperature protection == | ||
243 | |||
244 | == 3.6.19 Logic offline protection == | ||
245 | |||
246 | == 3.6.20 Cell count protection == | ||
247 | |||
248 | == 3.6.21 Logic count protection == | ||
249 | |||
250 | == 3.6.22 WDT protection == | ||
251 | |||
252 | == 3.6.23 Insulation monitoring == | ||
253 | |||
254 | == 3.6.24 Critical error parameters == | ||
255 | |||
256 | == 3.6.25 General error parameters == | ||
257 | |||
258 | == 3.6.26 Low SOC signal == | ||
259 | |||
260 | == 3.6.27 High charging current signal == | ||
261 | |||
262 | == 3.6.28 Heater control == | ||
263 | |||
264 | == 3.6.29 Heater (AUX) control == | ||
265 | |||