Admin 1.1 1 The BMS Main 2.x board continuously monitors the state of the cells, BMS Logic boards, the external environment and, when detecting abnormalities, protects the battery and system components from damage.
2
3 == 3.6.1 Overcurrent protection ==
4
5 To change the current protection of the battery, select the menu "Protections → Overcurrent protection":
Admin 2.2 6
Admin 2.3 7 [[Overcurrent protection settings>>image:1732211959984-118.png||data-xwiki-image-style-alignment="center" height="266" width="386"]]
8
Admin 4.13 9 In this section:
Admin 2.3 10
11 * Enable – a flag to enable the protection;
12 * Maximum charging current, А;
13 * Tolerant charging current, А;
14 * Maximum discharging current, А;
15 * Tolerant discharging current, А;
16 * Delay before setting the error, second;
17 * Delay before clearing the error, second;
18 * Lock the error until the device is reset – a flag to block the error until the board is restarted.
19
20 As a result of operation of the current protection, the "Overcurrent" error is generated.
21
22 Error generation conditions:
23
24 * the current is positive (charging), and its modulo value is greater than the “Maximum charging current” value for the “Delay before setting the error” time;
25 * the current is negative (discharging), and its modulo value is greater than the “Maximum discharging current” value for the “Delay before setting the error” time.
26
27 Conditions for removing the error:
28
29 * the current is positive (charging) or zero, and its modulo value is less than the “Tolerant charging current” value for the “Delay before clearing the error” time;
30 * the current is negative (discharging), and its modulo value is less than the “Tolerant discharging current” value for the “Delay before clearing the error” time.
31
32 (% class="box infomessage" %)
33 (((
Admin 4.13 34 If there is the "Overcurrent" error, the charging and discharging relay open.
Admin 2.3 35 )))
Admin 3.2 36
37 == 3.6.2 Undervoltage protection ==
38
39 The board implements battery protection from too low or too high voltage on the cells.
40
41 To change the battery protection parameters from low voltage on the cells, select the menu "Protections → Undervoltage protection":
42
Admin 3.3 43 [[Undervoltage protection settings>>image:1732212212350-294.png||data-xwiki-image-style-alignment="center" height="207" width="359"]]
44
45 In this section:
46
47 * Enable – a flag to enable the protection;
48 * Minimum cell voltage, V;
49 * Tolerant cell voltage, V;
50 * Delay before setting the error, second;
51 * Delay before clearing the error, second;
52 * Lock the error until the device is reset.
53
54 As a result of the operation of battery protection from low voltage, the "Undervoltage" error is generated.
55
56 Error generation conditions:
57
58 * the minimum voltage among all cells of the battery is less than the “Minimum cell voltage” value for the “Delay before setting the error” time.
59
60 Conditions for removing the error:
61
62 * the minimum voltage among all cells of the battery is greater than the “Tolerant cell voltage” value for the “Delay before clearing the error” time.
63
64 (% class="box infomessage" %)
65 (((
66 If there is the "Undervoltage" error, the discharging relay opens.
67 )))
68
Admin 4.2 69 3.6.3 Overvoltage protection
70
71 To change the battery protection parameters from high voltage on the cells, select the menu "Protections → Overvoltage protection":
72
Admin 6.2 73 [[Overvoltage protection settings>>image:1732212357972-295.png||data-xwiki-image-style-alignment="center" height="218" width="338"]]
Admin 4.2 74
Admin 4.3 75 In this section:
76
77 * Enable – a flag to enable the protection;
78 * Maximum cell voltage, V;
79 * Tolerant cell voltage, V;
80 * Delay before setting the error, second;
81 * Delay before clearing the error, second;
82 * Switch off the discharging relay on error – a flag to open the discharging relay when the "Overvoltage" error is generated;
83 * Lock the error until the device is reset.
84
85 As a result of the operation of the battery protection from high voltage, the "Overvoltage" error is generated.
86
87 Error generation conditions:
88
89 * the maximum voltage among all cells of the battery is greater than the “Maximum cell voltage” value for the “Delay before setting the error” time.
90
91 Conditions for removing the error:
92
93 * the maximum voltage among all cells of the battery is less than the “Tolerant cell voltage” value for the “Delay before clearing the error” time.
94
95 (% class="box infomessage" %)
96 (((
97 If there is the "Overvoltage" error, the charging relay and discharging relay opens (if the “Switch off the discharging relay on error” flag is set).
98 )))
99
Admin 4.10 100 == 3.6.4 Low temperature protection ==
Admin 4.3 101
Admin 4.11 102 The board implements battery protection from too low temperature.
Admin 4.4 103
Admin 4.11 104 To change the battery protection parameters from low temperature, select the menu "Protections → Low temperature protection":
105
Admin 6.2 106 [[Low temperature protection settings>>image:1732213953083-955.png||data-xwiki-image-style-alignment="center" height="237" width="338"]]
Admin 4.11 107
108 In this section:
109
110 * Enable – a flag to enable the protection;
111 * Minimum charging temperature, °C;
112 * Tolerant charging temperature, °C;
113 * Minimum discharging temperature, °C;
114 * Tolerant discharging temperature, °C;
115 * Delay before setting the error, second;
116 * Delay before clearing the error, second;
117 * Lock the error until the device is reset.
118
119 As a result of the operation of the battery protection from low temperature, the "Low CH temperature" or “Low DCH temperature” error is generated.
120
121 Error generation conditions:
122
123 * the minimum temperature among all cells of the battery is less than the “Minimum charging (discharging) temperature” value for the “Delay before setting the error” time.
124
125 Conditions for removing the error:
126
127 * the minimum temperature among all cells of the battery is greater than the “Tolerant charging (discharging) temperature” value for the “Delay before clearing the error” time.
128
129 (% class="box infomessage" %)
130 (((
Admin 4.12 131 If there is the "Low CH temperature" error, the charging relay opens.
132 If there is the "Low DCH temperature" error, the discharging relay opens.
Admin 4.11 133 )))
134
Admin 4.10 135 == 3.6.5 High temperature protection ==
Admin 4.5 136
Admin 4.11 137 The board implements battery protection from too high temperature.
138
139 To change the battery protection parameters from high temperature, select the menu "Protections → High temperature protection":
140
Admin 7.2 141 [[High temperature protection settings>>image:1732213990755-759.png||data-xwiki-image-style-alignment="center" height="258" width="370"]]
Admin 4.12 142
Admin 4.11 143 In this section:
144
145 * Enable – a flag to enable the protection;
146 * Maximum charging temperature, °C;
147 * Tolerant charging temperature, °C;
148 * Maximum discharging temperature, °C;
149 * Tolerant discharging temperature, °C;
150 * Delay before setting the error, second;
151 * Delay before clearing the error, second;
152 * Lock the error until the device is reset.
153
154 As a result of the operation of the battery protection from high temperature, the "High CH temperature" or “High DCH temperature” error is generated.
155
156 Error generation conditions:
157
158 * the maximum temperature among all cells of the battery is greater than the “Maximum charging (discharging) temperature” value for the “Delay before setting the error” time.
159
160 Conditions for removing the error:
161
162 * the maximum temperature among all cells of the battery is less than the “Tolerant charging (discharging) temperature” value for the “Delay before clearing the error” time.
163
164 (% class="box infomessage" %)
165 (((
166 If there is the "High CH temperature" error, the charging relay opens.
167 If there is the "High DCH temperature" error, the discharging relay opens.
168 )))
169
Admin 4.10 170 == 3.6.6 Battery cover protection ==
Admin 4.5 171
Admin 4.12 172 To change the protection parameters from opening the battery cover, select the menu "Protections → Battery cover protection":
173
Admin 7.2 174 [[Battery cover protection settings>>image:1732214030014-281.png||data-xwiki-image-style-alignment="center" height="155" width="334"]]
175
Admin 4.12 176 In this section:
177
178 * Enable – a flag to enable the protection;
179 * Delay before setting the error, second;
180 * Delay before clearing the error, second;
181 * Lock the error until the device is reset.
182
183 As a result of the operation of the protection against opening the battery cover, the “Battery cover error” is generated.
184
185 Error generation conditions:
186
187 * there is a signal from the battery cover during the “Delay before setting the error” time.
188
189 Conditions for removing the error:
190
191 * no signal from the battery cover during the “Delay before clearing the error” time.
192
193 (% class="box warningmessage" %)
194 (((
195 **If there is the "Battery cover error", the “Critical error” is generated and all relays open.**
196 )))
197
Admin 4.13 198 == 3.6.7 High humidity protection ==
Admin 4.10 199
Admin 4.13 200 The board can protect the battery from high humidity and water.
201
202 To change the protection parameters of the battery from high humidity, select the menu "Protections → High humidity protection":
203
Admin 10.2 204 [[High humidity protection settings>>image:1732214076060-358.png||data-xwiki-image-style-alignment="center" height="185" width="321"]]
Admin 4.14 205
Admin 4.13 206 In this section:
207
208 * Enable – a flag to enable the protection;
Admin 10.2 209 * Maximum humidity, RH%;
210 * Tolerant humidity, RH%;
Admin 4.13 211 * Delay before setting the error, second;
212 * Delay before clearing the error, second;
213 * Lock the error until the device is reset.
214
215 As a result of the operation of the battery protection from high humidity, the "High humidity" error is generated.
216
217 Error generation conditions:
218
219 * the measured humidity is greater than “Maximum humidity” during the “Delay before setting the error” time.
220
221 Conditions for removing the error:
222
223 * the measured humidity is less than the “Tolerant humidity” during the “Delay before clearing the error” time.
224
Admin 4.14 225 (% class="box infomessage" %)
226 (((
Admin 4.13 227 If there is the "High humidity" error, no action is taken. The error is indicative.
Admin 4.14 228 )))
Admin 4.13 229
Admin 4.10 230 == 3.6.8  Water protection ==
231
Admin 4.14 232 To change the protection parameters of the battery from water, select the menu "Protections → Water protection":
233
Admin 10.2 234 [[Water protection settings>>image:1732214111990-184.png||data-xwiki-image-style-alignment="center" height="199" width="340"]]
Admin 4.14 235
236 In this section:
237
238 * Enable – a flag to enable the protection;
239 * Maximum (water) humidty, RH%;
240 * Tolerant humidity, RH%;
241 * Delay before setting the error, second;
242 * Delay before clearing the error, second;
243 * Lock the error until the device is reset.
244
245 As a result of the operation of the battery protection from water, the "Water" error is generated.
246
247 Error generation conditions:
248
249 * the measured humidity is greater than the “Maximum (water) humidity” value during the “Delay before setting the error” time.
250
251 Conditions for removing the error:
252
253 * the measured humidity is less than the “Tolerant humidity” value during the “Delay before clearing the error” time.
254
255 (% class="box warningmessage" %)
256 (((
257 **If there is the “Water” error, the “Critical error” is generated and all relays open.**
258 )))
259
Admin 4.10 260 == 3.6.9 Current sensor error ==
261
Admin 4.14 262 The board is implemented to check the current sensor connection circuits. The circuits are checked for breakage and short-circuit to the +5 V supply line.
263
264 To change the test parameters of the current sensor connection circuits, select the menu "Protections → Current sensor error":
265
Admin 12.2 266 [[Current sensor error settings>>image:1732214146724-132.png||data-xwiki-image-style-alignment="center" height="438" width="365"]]
Admin 4.14 267
268 In this section:
269
270 * Enable – a flag to enable the protection;
271 * Maximum voltage, V;
272 * Minimum voltage, V;
273 * Hysteresis voltage – a hysteresis value to clear the error, V;
274 * Delay before setting the error, second;
275 * Delay before clearing the error, second;
276 * Lock the error until the device is reset.
277
278 If there is an open or short circuit connection of a current sensor, the "Current sensor error" is generated.
279
280 Error generation conditions:
281
282 * the voltage in the signal line or zero level line of the current sensor is greater than the “Maximum voltage” value during the “Delay before setting the error” time;
283 * the voltage in the signal line or zero level line of the current sensor is less than the “Minimum voltage” value during the “Delay before setting the error” time.
284
285 Conditions for removing the error:
286
287 * the voltage in the signal line or zero level line of the current sensor is in range from (Minimum voltage + Hysteresis voltage) to (Maximum voltage - Hysteresis voltage) during the “Delay before clearing the error” time.
288
Admin 4.15 289 (% class="box warningmessage" %)
290 (((
Admin 4.14 291 **If there is the “Current sensor error”, the “Critical error” is generated and all relays open.**
Admin 4.15 292 )))
Admin 4.14 293
Admin 4.10 294 == 3.6.10 Short circuit protection ==
295
Admin 4.15 296 The BMS implements a protection of power circuits (contactors, power cables) against overheating caused by the flow of high current for a long time.
297
298 To change the protection parameters from short circuit, select the menu "Protections → Short circuit protection":
299
Admin 13.2 300 [[Short circuit protection settings>>image:1732214207026-822.png||data-xwiki-image-style-alignment="center" height="528" width="371"]]
Admin 4.15 301
302 In this section:
303
304 * Level 1, 2, 3 – three protection levels. The following parameters are configured at each level:
305 ** Enable – a flag to enable the protection;
306 ** Maximum current, A;
307 ** Delay before setting the error, second;
308 * Delay before clearing the error, second;
309 * Switch off the charging relay on error – a flag to open the charging relay when the "Short circuit" error occurs;
310 * Switch off the discharging relay on error – a flag to open the discharging relay when the "Short circuit" error occurs;
311 * Lock the error until the device is reset.
312
313 If there is a short circuit, the "Short circuit" error is generated.
314
315 Error generation conditions:
316
317 * at any of the three protection levels, the current modulo is greater than the “Maximum current” value during the “Delay before setting the error” time.
318
319 Conditions for removing the error:
320
321 * the current modulo is lower than the “Maximum current” values for all three protection levels during the “Delay before setting the error” time.
322
323 (% class="box infomessage" %)
324 (((
325 If there is the "Short circuit" error, the charging relay opens (the “Switch off the charging relay on error” flag is set) and the discharging relay opens (the “Switch off the discharging relay on error flag” is set).
326 )))
327
Admin 4.10 328 == 3.6.11 Contactor high temperature protection ==
329
Admin 4.15 330 The BMS protects power contactors from overheating. To measure the temperature of the contactor, a thermistor is used, connected to the P13 connector of the board. Configuring of the analog input for temperature measurement is described in section Input signals.
331
332 To change the overheating protection parameters of power contactors, select the menu "Protections → Contactor high temperature protection":
333
Admin 14.2 334 [[Contactor high temperature protection settings>>image:1732214237851-405.png||data-xwiki-image-style-alignment="center" height="234" width="336"]]
Admin 4.15 335
336 In this section:
337
338 * Enable – a flag to enable the protection;
339 * Maximum temperature, °C;
340 * Tolerant temperature, °C;
341 * Delay before setting the error, second;
342 * Delay before clearing the error, second;
343 * Switch off the charging relay on error – a flag to open the charging relay when the "Contactor high temperature" error occurs;
344 * Switch off the discharging relay on error – a flag to open the discharging relay when the "Contactor high temperature" error occurs;
345 * Lock the error until the device is reset.
346
347 If there is a contactor overheat, the "Contactor high temperature" error is generated.
348
349 Error generation conditions:
350
351 * the contactor temperature is greater than the “Maximum temperature” value during the “Delay before setting the error” time.
352
353 Conditions for removing the error:
354
355 * the contactor temperature is lower than the “Tolerant temperature” value during the “Delay before clearing the error” time.
356
357 (% class="box infomessage" %)
358 (((
359 If there is the "Contactor high temperature" error, the charging relay opens (the “Switch off the charging relay on error” flag is set) and the discharging relay opens (the “Switch off the discharging relay on error flag” is set).
360 )))
361
Admin 4.10 362 == 3.6.12 Unallowable charging protection ==
363
Admin 4.16 364 The BMS can detect that the battery is charging through the discharging circuit and protectively open the discharging relay to prevent unallowable battery operation.
365
366 To change the parameters of the unallowable charging protection, select the menu "Protections → Unallowable charging protection":
367
Admin 14.2 368 [[Unallowable charging protection settings>>image:1732214272022-547.png||data-xwiki-image-style-alignment="center" height="145" width="312"]]
Admin 4.16 369
370 In this section:
371
372 * Enable – a flag to enable the protection;
373 * Delay before setting the error, second;
374 * Delay before clearing the error, second;
375 * Lock the error until the device is reset.
376
377 If there is charging the battery through the discharging circuit detected, the "Unallowable charging" error is generated.
378
379 Error generation conditions:
380
381 * the charging relay is open and the battery current is not zero during the “Delay before setting the error” time.
382
383 Conditions for removing the error:
384
385 * the battery current is zero during the “Delay before clearing the error” time.
386
387 (% class="box infomessage" %)
388 (((
389 If there is the "Unallowable charging" error, the discharging relay opens.
390 )))
391
Admin 4.10 392 == 3.6.13 Stuck contactor protection ==
393
Admin 4.16 394 The BMS Main 2.x protects contactors against sticking.
395
396 To change the protection parameters against sticking, select the menu "Protections → Stuck contactor protection":
397
398
399 In this section:
400
401 * Enable – a flag to enable the protection;
402 * Delay before setting the error, second;
403 * Delay before clearing the error, second;
404 * Lock the error until the device is reset;
405
406 If there is a stuck contactor, the “Stuck contactor” error is generated.
407
408 Error generation conditions:
409
410 * charging and discharging contactors are open, but the “Charging current present” or “Discharging current present” signal is set.
411
Admin 4.10 412 == 3.6.14 Contactor feedback check ==
413
Admin 4.16 414 The BMS Main 2.x can receive feedback signals from contactors and detect discrepancy between the control value and the feedback signal. To enable specific contactor protection, one of the discrete input must be set as corresponding contactor feedback signal (see section Input and output signals).
415
416 To change the contactor feedback check parameters, select the menu "Protections → Contactor feedback check":
417
Admin 4.17 418
419 In this section:
420
421 * Enable – a flag to enable the protection;
422 * Delay before setting the error, second;
423 * Delay before clearing the error, second;
424 * Lock the error until the device is reset;
425
426 If there is a discrepancy at any contactor, the corresponding contactor feedback error is generated. Error generation conditions:
427
428 * discrete output of charging, precharge, discharging, charging/discharging or main contactor not matches its feedback value.
429
Admin 4.10 430 == 3.6.15 Charging contactor cycles protection ==
431
Admin 4.18 432 The BMS protects the charging contactor against frequent switching.
Admin 4.17 433
Admin 4.18 434 To change the protection parameters against high frequency switching of the charging contactor, select the menu "Protections → Charging contactor cycles protection":
435
436
437 In this section:
438
439 * Enable – a flag to enable the protection;
440 * Cycles threshold – a number of cycles in a given period, upon which the “CH contactor cycles error” is generated;
441 * Period – a time in which the BMS counts switchings of the charging contactor, second;
442 * Delay before setting the error, second;
443 * Delay before clearing the error, second;
444 * Lock the error until the device is reset;
445 * Cycles – a number of the charging contactor switchings made during battery operation.
446
447 If there is the high switching frequency of the charging contactor, the “CH contactor cycles error” is generated.
448
449 Error generation conditions:
450
451 * the number of switchings of the charging contactor for the “Period” time is greater than or equal to the “Cycles threshold” value. The error is generated with the “Delay before setting the error” delay.
452
453 Conditions for removing the error:
454
455 * the “Delay before clearing the error” time has passed since the error was generated.
456
457 (% class="box infomessage" %)
458 (((
459 If there is the "CH contactor cycles error" error, the charging relay opens.
460 )))
461
Admin 4.10 462 == 3.6.16 Discharging contactor cycles protection ==
463
Admin 4.18 464 The BMS protects the discharging contactor against frequent switching.
465
466 To change the protection parameters against high frequency switching of the discharging contactor, select the menu "Protections → Discharging contactor cycles protection":
467
468
469 In this section:
470
471 * Enable – a flag to enable the protection;
472 * Cycles threshold – a number of cycles in a given period, upon which the “DCH contactor cycles error” is generated;
473 * Period – a time in which the BMS counts switchings of the charging contactor, second;
474 * Delay before setting the error, second;
475 * Delay before clearing the error, second;
476 * Lock the error until the device is reset;
477 * Cycles – a number of the charging contactor switchings made during battery operation.
478
479 If there is the high switching frequency of the discharging contactor, the “DCH contactor cycles error” is generated.
480
481 Error generation conditions:
482
483 * the number of switchings of the discharging contactor for the “Period” time is greater than or equal to the “Cycles threshold” value. The error is generated with the “Delay before setting the error” delay.
484
485 Conditions for removing the error:
486
487 * the “Delay before clearing the error” time has passed since the error was generated.
488
489 (% class="box infomessage" %)
490 (((
491 If there is the "DCH contactor cycles error" error, the discharging relay opens.
492 )))
493
Admin 4.10 494 == 3.6.17 Temperature sensor error ==
495
Admin 4.18 496 The board is implemented to check the temperature sensors connection circuits. The circuits are checked for breakage and short-circuit.
497
498 To change the protection parameters of the temperature sensors circuits, select the menu "Protections → Temperature sensor error":
499
500
501 In this section:
502
503 * Enable – a flag to enable the protection;
504 * Delay before setting the error, second;
505 * Delay before clearing the error, second;
506 * Lock the error until the device is reset.
507
508 If there are no temperature sensors connected to a BMS Logic board or any temperature sensor is shorted, the "No temp. sensors" error and "Temp. sensor is shorted" error are generated respectively. These errors generated and removed with the “Delay before setting the error” and “Delay before clearing the error” delays.
509
Admin 4.19 510 (% class="box warningmessage" %)
511 (((
Admin 4.18 512 **If there is the “No temp. sensors” or “Temp. sensor is shorted” error, the “Critical error” is generated and all relays open.**
Admin 4.19 513 )))
Admin 4.18 514
Admin 4.10 515 == 3.6.18 Logic high temperature protection ==
516
Admin 4.19 517 To change the overheating protection parameters of BMS Logic boards, select the menu "Protections → Logic high temperature protection":
518
519
520 In this section:
521
522 * Enable – a flag to enable the protection;
523 * Maximum Logic temperature, °C;
524 * Tolerant Logic temperature, °C;
525 * Lock the error until the device is reset.
526
527 As a result of the operation of the protection from high temperatures of BMS Logic boards, the "Logic high temperature" is generated.
528
529 Error generation conditions:
530
531 * a BMS Logic board temperature is higher than the “Maximum Logic temperature” value.
532
533 Conditions for removing the error:
534
535 * a BMS Logic board temperature is less than the “Tolerant Logic temperature” value.
536
537 (% class="box infomessage" %)
538 (((
539 **Cell balancing is prohibited for overheated boards.**
540 )))
541
Admin 4.10 542 == 3.6.19 Logic offline protection ==
543
Admin 4.19 544 To change the protection parameters from loss of communication with BMS Logic boards, select the menu "Protections → Logic offline protection":
545
546
Admin 4.20 547 In this section:
Admin 4.19 548
Admin 4.20 549 * Enable – a flag to enable the protection;
550 * Lock the error until the device is reset.
551
552 As a result of the protection from loss of communication with BMS Logic boards, the "Logic offline" error is generated.
553
554 Error generation conditions:
555
556 * at least one of the connected BMS Logic boards does not respond to the commands of the BMS Main 2.x board for 10 seconds.
557
558 Conditions for removing the error:
559
560 * all connected BMS Logic boards respond to the commands of the BMS Main 2.x board.
561
562 (% class="box warningmessage" %)
563 (((
564 **If there is the "Logic offline" error, the “Critical error” is generated and all relays open.**
565 )))
566
Admin 4.10 567 == 3.6.20 Cell count protection ==
568
Admin 4.20 569 To change the protection parameters from the mismatch of the number of cells to the set value, select the menu "Protections → Cell count protection":
570
571
572 In this section:
573
574 * Enable – a flag to enable the protection;
575 * Cell count – a number of cells connected to the BMS;
576 * Delay before setting the error, second;
577 * Delay before clearing the error, second;
578 * Lock the error until the device is reset.
579
580 As a result of the operation of the protection from the mismatch of the number of cells, the "Cell count error" is generated.
581
582 Error generation conditions:
583
584 * the number of cells connected to the BMS is **not equal** to the “Cell count” value during the “Delay before setting the error” time.
585
586 Conditions for removing the error:
587
588 * the number of cells connected to the BMS is **equal** to the “Cell count” value during the “Delay before clearing the error” time.
589
590 (% class="box warningmessage" %)
591 (((
592 **If there is the "Cell count error", the “Critical error” is generated and all relays open.**
593 )))
594
Admin 4.10 595 == 3.6.21 Logic count protection ==
596
Admin 4.20 597 To change the protection parameters from the mismatch of the number of BMS Logic boards to the set value, select the menu "Protections → Logic count protection":
598
599
600 In this section:
601
602 * Enable – a flag to enable the protection;
603 * Logic count – a number of BMS Logic boards connected to the BMS Main 2.x;
604 * Fast scan – a flag to scan BMS Logic boards fast (boards with addresses from 1 to “Logic count” are scanned; this mode reduces BMS system startup time);
605 * Lock the error until the device is reset.
606
607 As a result of the operation of the protection from the mismatch of the number of BMS Logic boards, the "Logic count error" is generated.
608
609 Error generation conditions:
610
611 * the number of BMS Logic boards connected to the BMS Main 2.x is **not equal** to the “Logic count” value.
612
613 Conditions for removing the error:
614
615 * the number of BMS Logic boards connected to the BMS Main is **equal** to the “Logic count” value.
616
617 (% class="box warningmessage" %)
618 (((
619 **If there is the "Logic count error", the “Critical error” is generated and all relays open.**
620 )))
621
Admin 4.10 622 == 3.6.22 WDT protection ==
623
Admin 4.20 624 If the BMS firmware hangs, the watchdog timer resets the board. The BMS can detect that the board was reset and generates the “WDT reset” error.
625
626 To change the parameters of the watchdog protection, select the menu "Protections → WDT protection":
627
628
Admin 4.21 629 In this section:
630
631 * Enable – a flag to enable the protection;
632 * Delay before clearing the error, second;
633 * Lock the error until the device is reset.
634
635 Conditions for removing the error:
636
637 * the “Delay before clearing the error” time has passed from the board startup.
638
Admin 4.22 639 (% class="box warningmessage" %)
640 (((
Admin 4.21 641 **If there is the "WDT reset" error, the “Critical error” is generated and all relays open.**
Admin 4.22 642 )))
Admin 4.21 643
Admin 4.10 644 == 3.6.23 Insulation monitoring ==
645
Admin 4.22 646 BMS Main 2.x can detect a signal from an external insulation monitoring device (such as Bender IR155) to monitor the insulation quality.
647
648 To change the insulation monitoring parameters, select the menu "Protections → Insulation monitoring":
649
650
651 In this section:
652
653 * Enable – a flag to enable the protection;
654 * Delay before setting the error, second;
655 * Delay before clearing the error, second;
656 * Lock the error until the device is reset.
657
658 Error is set if corresponding discrete input is set up and it received logical zero.
659
Admin 4.10 660 == 3.6.24 Critical error parameters ==
661
Admin 4.22 662 To change the critical error parameters, select the menu "Protections → Critical error parameters":
663
664
665 In this section:
666
667 * Enable – a flag to enable the protection;
668 * Delay before setting the error, second;
669 * Delay before clearing the error, second;
670 * Lock the error until the device is reset.
671
672 The critical error flag is generated if at least one of the following errors is generated during the “Delay before setting the error” time:
673
674 * “Battery cover error”;
675 * “Water”;
676 * “Logic offline”;
677 * “Cell count error”;
678 * “Logic count error”;
679 * “ADC error”;
680 * “No temp. sensors”;
681 * “Temp. sensor is shorted”;
682 * “Current sensor error”;
683 * “Shunt offline”;
684 * “Shunt error”;
685 * “Settings error”;
686 * “WDT reset”.
687
688 The “Critical error” is cleared if there are no errors from the list above during the “Delay before clearing the error” time.
689
690 (% class="box warningmessage" %)
691 (((
692 **If there is the “Critical error”, all relays open.**
693 )))
694
Admin 4.10 695 == 3.6.25 General error parameters ==
696
697 == 3.6.26 Low SOC signal ==
698
Admin 4.22 699 To change the parameters of the generation a signal about low battery level, select the menu "Protections → Low SOC signal":
700
701
702 In this section:
703
704 * Enable – a flag to enable signal generation;
705 * Minimum SOC, %;
706 * Tolerant SOC, %;
707 * Delay before setting the signal, second;
708 * Delay before clearing the signal, second;
709 * Lock the signal until the device is reset.
710
711 Signal generation conditions:
712
713 * the battery SOC is less than the “Minimum SOC” value during the “Delay before setting the signal” time.
714
715 Conditions for clearing the signal:
716
717 * the battery SOC is greater than the “Tolerant SOC” during the “Delay before clearing the signal” time.
718
Admin 4.23 719 The "Low SOC signal" is //indicative //and can be linked to any discrete output of the board.
Admin 4.22 720
Admin 4.10 721 == 3.6.27 High charging current signal ==
722
Admin 4.23 723 To change the parameters of the generation high-current signal, select the menu "Protections → High charging current signal":
724
725
726 In this section:
727
728 * Enable – a flag to enable signal generation;
729 * Maximum charging current, А;
730 * Tolerant charging current, А;
731 * Delay before setting the signal, second;
732 * Delay before clearing the signal, second;
733 * Lock the signal until the device is reset.
734
735 Signal generation conditions:
736
737 * the measured current is greater than the “Maximum charging current” value during the “Delay before setting the signal” time.
738
739 Conditions for clearing the signal:
740
741 * the measured current is less than the “Tolerant charging current” value during the “Delay before clearing the signal” time.
742
743 The "High charging current" signal is //indicative //and can be linked to any discrete output of the board.
744
Admin 4.10 745 == 3.6.28 Heater control ==
746
Admin 4.23 747 To change the parameters of the heater control algorithm, select the menu "Protections → Heater control":
748
749
750 In this section:
751
752 * Enable – a flag to enable heater control;
753 * Minimum cell temperature, °C;
754 * Tolerant cell temperature, °C;
755 * Delay before setting the signal, second;
756 * Delay before clearing the signal, second;
757 * Lock the signal until the device is reset;
758 * Switch off the heater relay on errors (Undervoltage, Overcurrent, High temperature, Short circuit or Critical error).
759
760 As a result of operating the heating algorithm, the “Heater” signal is generated.
761
762 Conditions of signal generation:
763
764 * The minimum temperature among all cells of the battery is less than the “Minimum cell temperature” value during the “Delay before setting the signal” time.
765
766 Conditions for clearing the signal:
767
768 * the minimum temperature among all cells of the battery is greater than the “Tolerant cell temperature” value during the “Delay before clearing the signal” time.
769
Admin 4.24 770 (% class="box infomessage" %)
771 (((
Admin 4.23 772 If there is the "Heater" signal, the heater relay closes and/or a signal is output to the corresponded digital output.
Admin 4.24 773 )))
Admin 4.23 774
Admin 4.10 775 == 3.6.29 Heater (AUX) control ==
776
Admin 4.25 777 To change the parameters of the auxiliary heater control algorithm, select the menu "Protections → Heater (AUX) control":
Admin 4.24 778
779
780 In this section:
781
782 * Enable – a flag to enable heater control;
783 * Minimum cell temperature, °C;
784 * Tolerant cell temperature, °C;
785 * Delay before setting the signal, second;
786 * Delay before clearing the signal, second;
787 * Lock the signal until the device is reset;
788 * Switch off the heater relay on errors (Undervoltage, Overcurrent, High temperature, Short circuit or Critical error).
789
790 As a result of operating the heating algorithm, the “Heater (AUX)” signal is generated.
791
792 Conditions of signal generation:
793
794 * The minimum temperature among all cells of the battery is less than the “Minimum cell temperature” value during the “Delay before setting the signal” time.
795
796 Conditions for clearing the signal:
797
798 * the minimum temperature among all cells of the battery is greater than the “Tolerant cell temperature” value during the “Delay before clearing the signal” time.
799
Admin 4.25 800 (% class="box infomessage" %)
801 (((
802 If there is the "Heater (AUX)" signal, the auxiliary heater relay closes and/or a signal is output to the corresponded digital output.
803 )))
Admin 4.24 804
Admin 4.10 805 == 3.6.30 Cooler control ==
806
Admin 4.25 807 To change the parameters of the cooler control algorithm, select the menu "Protections → Cooler control":
808
809
810 In this section:
811
812 * Enable – a flag to enable cooler control;
813 * Maximum cell temperature, °C;
814 * Tolerant cell temperature, °C;
815 * Delay before setting the signal, second;
816 * Delay before clearing the signal, second;
817 * Lock the signal until the device is reset;
818 * Switch off the cooler relay on errors (Undervoltage, Overcurrent, Low temperature, Short circuit or Critical error).
819
820 As a result of operating the cooling algorithm, the "Cooler" signal is generated.
821
822 Conditions of signal generation:
823
824 * the maximum temperature among all cells of the battery is greater than the “Maximum cell temperature” value during the “Delay before setting the signal” time.
825
826 Conditions for clearing the signal:
827
828 * the maximum temperature among all cells of the battery is less than the “Tolerant cell temperature” value during the “Delay before clearing the signal” time.
829
830 (% class="box infomessage" %)
831 (((
832 If there is the "Cooler" signal, the cooler relay closes and/or a signal is output to the corresponded digital output.
833 )))
834
Admin 4.10 835 == 3.6.31 Fault simulation ==
Admin 4.26 836
837 The board provides the ability to manually generate error flags bypassing the protection algorithms. This functionality is intended for commissioning.
838
839 To simulate battery and BMS errors, select the menu "Protections → Fault simulation":
840
841
842 In this section:
843
844 * Overcurrent;
845 * Undervoltage;
846 * Overvoltage;
847 * Low CH temperature;
848 * Low DCH temperature;
849 * High CH temperature;
850 * High DCH temperature;
851 * Battery cover error;
852 * High humidity;
853 * Water;
854 * Current sensor error;
855 * Short circuit;
856 * Contactor high temperature;
857 * Unallowable charging;
858 * Stuck contactor;
859 * CH contactor feedback error;
860 * DCH contactor feedback error;
861 * PCH contactor feedback error;
862 * CH/DCH contactor feedback error;
863 * Main contactor feedback error;
864 * CH contactor cycles error;
865 * DCH contactor cycles error;
866 * Logic high temperature;
867 * Logic offline;
868 * Cell count error;
869 * Logic count error;
870 * Insulation error;
871 * Critical error;
872 * Low SOC;
873 * High charging current;
874 * Heater;