... ... @@ -70,7 +70,7 @@
70 70  
71 71  To change the battery protection parameters from high voltage on the cells, select the menu "Protections → Overvoltage protection":
72 72  
73 -[[Overvoltage protection settings>>image:1732212357972-295.png||data-xwiki-image-style-alignment="center" height="218" width="338"]]
73 +[[image:1732212357972-295.png]]
74 74  
75 75  In this section:
76 76  
... ... @@ -103,7 +103,6 @@
103 103  
104 104  To change the battery protection parameters from low temperature, select the menu "Protections → Low temperature protection":
105 105  
106 -[[Low temperature protection settings>>image:1732213953083-955.png||data-xwiki-image-style-alignment="center" height="237" width="338"]]
107 107  
108 108  In this section:
109 109  
... ... @@ -138,7 +138,6 @@
138 138  
139 139  To change the battery protection parameters from high temperature, select the menu "Protections → High temperature protection":
140 140  
141 -[[High temperature protection settings>>image:1732213990755-759.png||data-xwiki-image-style-alignment="center" height="258" width="370"]]
142 142  
143 143  In this section:
144 144  
... ... @@ -171,8 +171,6 @@
171 171  
172 172  To change the protection parameters from opening the battery cover, select the menu "Protections → Battery cover protection":
173 173  
174 -[[Battery cover protection settings>>image:1732214030014-281.png||data-xwiki-image-style-alignment="center" height="155" width="334"]]
175 -
176 176  In this section:
177 177  
178 178  * Enable – a flag to enable the protection;
... ... @@ -620,252 +620,20 @@
620 620  To change the parameters of the watchdog protection, select the menu "Protections → WDT protection":
621 621  
622 622  
623 -In this section:
624 -
625 -* Enable – a flag to enable the protection;
626 -* Delay before clearing the error, second;
627 -* Lock the error until the device is reset.
628 -
629 -Conditions for removing the error:
630 -
631 -* the “Delay before clearing the error” time has passed from the board startup.
632 -
633 -(% class="box warningmessage" %)
634 -(((
635 -**If there is the "WDT reset" error, the “Critical error” is generated and all relays open.**
636 -)))
637 -
638 638  == 3.6.23 Insulation monitoring ==
639 639  
640 -BMS Main 2.x can detect a signal from an external insulation monitoring device (such as Bender IR155) to monitor the insulation quality.
641 -
642 -To change the insulation monitoring parameters, select the menu "Protections → Insulation monitoring":
643 -
644 -
645 -In this section:
646 -
647 -* Enable – a flag to enable the protection;
648 -* Delay before setting the error, second;
649 -* Delay before clearing the error, second;
650 -* Lock the error until the device is reset.
651 -
652 -Error is set if corresponding discrete input is set up and it received logical zero.
653 -
654 654  == 3.6.24 Critical error parameters ==
655 655  
656 -To change the critical error parameters, select the menu "Protections → Critical error parameters":
657 -
658 -
659 -In this section:
660 -
661 -* Enable – a flag to enable the protection;
662 -* Delay before setting the error, second;
663 -* Delay before clearing the error, second;
664 -* Lock the error until the device is reset.
665 -
666 -The critical error flag is generated if at least one of the following errors is generated during the “Delay before setting the error” time:
667 -
668 -* “Battery cover error”;
669 -* “Water”;
670 -* “Logic offline”;
671 -* “Cell count error”;
672 -* “Logic count error”;
673 -* “ADC error”;
674 -* “No temp. sensors”;
675 -* “Temp. sensor is shorted”;
676 -* “Current sensor error”;
677 -* “Shunt offline”;
678 -* “Shunt error”;
679 -* “Settings error”;
680 -* “WDT reset”.
681 -
682 -The “Critical error” is cleared if there are no errors from the list above during the “Delay before clearing the error” time.
683 -
684 -(% class="box warningmessage" %)
685 -(((
686 -**If there is the “Critical error”, all relays open.**
687 -)))
688 -
689 689  == 3.6.25 General error parameters ==
690 690  
691 691  == 3.6.26 Low SOC signal ==
692 692  
693 -To change the parameters of the generation a signal about low battery level, select the menu "Protections → Low SOC signal":
694 -
695 -
696 -In this section:
697 -
698 -* Enable – a flag to enable signal generation;
699 -* Minimum SOC, %;
700 -* Tolerant SOC, %;
701 -* Delay before setting the signal, second;
702 -* Delay before clearing the signal, second;
703 -* Lock the signal until the device is reset.
704 -
705 -Signal generation conditions:
706 -
707 -* the battery SOC is less than the “Minimum SOC” value during the “Delay before setting the signal” time.
708 -
709 -Conditions for clearing the signal:
710 -
711 -* the battery SOC is greater than the “Tolerant SOC” during the “Delay before clearing the signal” time.
712 -
713 -The "Low SOC signal" is //indicative //and can be linked to any discrete output of the board.
714 -
715 715  == 3.6.27 High charging current signal ==
716 716  
717 -To change the parameters of the generation high-current signal, select the menu "Protections → High charging current signal":
718 -
719 -
720 -In this section:
721 -
722 -* Enable – a flag to enable signal generation;
723 -* Maximum charging current, А;
724 -* Tolerant charging current, А;
725 -* Delay before setting the signal, second;
726 -* Delay before clearing the signal, second;
727 -* Lock the signal until the device is reset.
728 -
729 -Signal generation conditions:
730 -
731 -* the measured current is greater than the “Maximum charging current” value during the “Delay before setting the signal” time.
732 -
733 -Conditions for clearing the signal:
734 -
735 -* the measured current is less than the “Tolerant charging current” value during the “Delay before clearing the signal” time.
736 -
737 -The "High charging current" signal is //indicative //and can be linked to any discrete output of the board.
738 -
739 739  == 3.6.28 Heater control ==
740 740  
741 -To change the parameters of the heater control algorithm, select the menu "Protections → Heater control":
742 -
743 -
744 -In this section:
745 -
746 -* Enable – a flag to enable heater control;
747 -* Minimum cell temperature, °C;
748 -* Tolerant cell temperature, °C;
749 -* Delay before setting the signal, second;
750 -* Delay before clearing the signal, second;
751 -* Lock the signal until the device is reset;
752 -* Switch off the heater relay on errors (Undervoltage, Overcurrent, High temperature, Short circuit or Critical error).
753 -
754 -As a result of operating the heating algorithm, the “Heater” signal is generated.
755 -
756 -Conditions of signal generation:
757 -
758 -* The minimum temperature among all cells of the battery is less than the “Minimum cell temperature” value during the “Delay before setting the signal” time.
759 -
760 -Conditions for clearing the signal:
761 -
762 -* the minimum temperature among all cells of the battery is greater than the “Tolerant cell temperature” value during the “Delay before clearing the signal” time.
763 -
764 -(% class="box infomessage" %)
765 -(((
766 -If there is the "Heater" signal, the heater relay closes and/or a signal is output to the corresponded digital output.
767 -)))
768 -
769 769  == 3.6.29 Heater (AUX) control ==
770 770  
771 -To change the parameters of the auxiliary heater control algorithm, select the menu "Protections → Heater (AUX) control":
772 -
773 -
774 -In this section:
775 -
776 -* Enable – a flag to enable heater control;
777 -* Minimum cell temperature, °C;
778 -* Tolerant cell temperature, °C;
779 -* Delay before setting the signal, second;
780 -* Delay before clearing the signal, second;
781 -* Lock the signal until the device is reset;
782 -* Switch off the heater relay on errors (Undervoltage, Overcurrent, High temperature, Short circuit or Critical error).
783 -
784 -As a result of operating the heating algorithm, the “Heater (AUX)” signal is generated.
785 -
786 -Conditions of signal generation:
787 -
788 -* The minimum temperature among all cells of the battery is less than the “Minimum cell temperature” value during the “Delay before setting the signal” time.
789 -
790 -Conditions for clearing the signal:
791 -
792 -* the minimum temperature among all cells of the battery is greater than the “Tolerant cell temperature” value during the “Delay before clearing the signal” time.
793 -
794 -(% class="box infomessage" %)
795 -(((
796 -If there is the "Heater (AUX)" signal, the auxiliary heater relay closes and/or a signal is output to the corresponded digital output.
797 -)))
798 -
799 799  == 3.6.30 Cooler control ==
800 800  
801 -To change the parameters of the cooler control algorithm, select the menu "Protections → Cooler control":
802 -
803 -
804 -In this section:
805 -
806 -* Enable – a flag to enable cooler control;
807 -* Maximum cell temperature, °C;
808 -* Tolerant cell temperature, °C;
809 -* Delay before setting the signal, second;
810 -* Delay before clearing the signal, second;
811 -* Lock the signal until the device is reset;
812 -* Switch off the cooler relay on errors (Undervoltage, Overcurrent, Low temperature, Short circuit or Critical error).
813 -
814 -As a result of operating the cooling algorithm, the "Cooler" signal is generated.
815 -
816 -Conditions of signal generation:
817 -
818 -* the maximum temperature among all cells of the battery is greater than the “Maximum cell temperature” value during the “Delay before setting the signal” time.
819 -
820 -Conditions for clearing the signal:
821 -
822 -* the maximum temperature among all cells of the battery is less than the “Tolerant cell temperature” value during the “Delay before clearing the signal” time.
823 -
824 -(% class="box infomessage" %)
825 -(((
826 -If there is the "Cooler" signal, the cooler relay closes and/or a signal is output to the corresponded digital output.
827 -)))
828 -
829 829  == 3.6.31 Fault simulation ==
830 -
831 -The board provides the ability to manually generate error flags bypassing the protection algorithms. This functionality is intended for commissioning.
832 -
833 -To simulate battery and BMS errors, select the menu "Protections → Fault simulation":
834 -
835 -
836 -In this section:
837 -
838 -* Overcurrent;
839 -* Undervoltage;
840 -* Overvoltage;
841 -* Low CH temperature;
842 -* Low DCH temperature;
843 -* High CH temperature;
844 -* High DCH temperature;
845 -* Battery cover error;
846 -* High humidity;
847 -* Water;
848 -* Current sensor error;
849 -* Short circuit;
850 -* Contactor high temperature;
851 -* Unallowable charging;
852 -* Stuck contactor;
853 -* CH contactor feedback error;
854 -* DCH contactor feedback error;
855 -* PCH contactor feedback error;
856 -* CH/DCH contactor feedback error;
857 -* Main contactor feedback error;
858 -* CH contactor cycles error;
859 -* DCH contactor cycles error;
860 -* Logic high temperature;
861 -* Logic offline;
862 -* Cell count error;
863 -* Logic count error;
864 -* Insulation error;
865 -* Critical error;
866 -* Low SOC;
867 -* High charging current;
868 -* Heater;
869 -* Cooler.
870 -
871 -To simulate errors, set the necessary flags and click on the "Save" button.
1732213953083-955.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.admin
Size
... ... @@ -1,1 +1,0 @@
1 -22.0 KB
Content
1732213990755-759.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.admin
Size
... ... @@ -1,1 +1,0 @@
1 -22.7 KB
Content
1732214030014-281.png
Author
... ... @@ -1,1 +1,0 @@
1 -XWiki.admin
Size
... ... @@ -1,1 +1,0 @@
1 -12.6 KB
Content