5 5  To change the current protection of the battery, select the menu "Protections → Overcurrent protection":
6 6  
7 -[[Overcurrent protection settings>>image:1732211959984-118.png||data-xwiki-image-style-alignment="center" height="266" width="386"]]
7 +[[image:1732211959984-118.png||data-xwiki-image-style-alignment="center" height="266" width="386"]]
8 8  
9 9   In this section:
10 10  
... ... @@ -31,16 +31,16 @@
31 31  
32 32  (% class="box infomessage" %)
33 33  (((
34 -If there is the "Overcurrent" error, the charging and discharging relay open.
34 +If there is the "Overcurrent" error, the **charging **and **discharging **relay open.
35 35  )))
36 36  
37 -== 3.6.2 Undervoltage protection ==
37 +== 3.6.2 Undervoltage protection ==
38 38  
39 39  The board implements battery protection from too low or too high voltage on the cells.
40 40  
41 41  To change the battery protection parameters from low voltage on the cells, select the menu "Protections → Undervoltage protection":
42 42  
43 -[[Undervoltage protection settings>>image:1732212212350-294.png||data-xwiki-image-style-alignment="center" height="207" width="359"]]
43 +[[image:1732212212350-294.png||data-xwiki-image-style-alignment="center" height="207" width="359"]]
44 44  
45 45   In this section:
46 46  
... ... @@ -63,14 +63,14 @@
63 63  
64 64  (% class="box infomessage" %)
65 65  (((
66 -If there is the "Undervoltage" error, the discharging relay opens.
66 +If there is the "Undervoltage" error, the **discharging **relay opens.
67 67  )))
68 68  
69 -3.6.3 Overvoltage protection
69 +== 3.6.3 Overvoltage protection ==
70 70  
71 71  To change the battery protection parameters from high voltage on the cells, select the menu "Protections → Overvoltage protection":
72 72  
73 -[[Overvoltage protection settings>>image:1732212357972-295.png||data-xwiki-image-style-alignment="center" height="218" width="338"]]
73 +[[image:1732212357972-295.png||data-xwiki-image-style-alignment="center" height="218" width="338"]]
74 74  
75 75  In this section:
76 76  
... ... @@ -94,7 +94,7 @@
94 94  
95 95  (% class="box infomessage" %)
96 96  (((
97 -If there is the "Overvoltage" error, the charging relay and discharging relay opens (if the “Switch off the discharging relay on error” flag is set).
97 +If there is the "Overvoltage" error, the **charging **relay and **discharging **relay opens (if the “Switch off the discharging relay on error” flag is set).
98 98  )))
99 99  
100 100  == 3.6.4 Low temperature protection ==
... ... @@ -103,7 +103,7 @@
103 103  
104 104  To change the battery protection parameters from low temperature, select the menu "Protections → Low temperature protection":
105 105  
106 -[[Low temperature protection settings>>image:1732213953083-955.png||data-xwiki-image-style-alignment="center" height="237" width="338"]]
106 +[[image:1732213953083-955.png||data-xwiki-image-style-alignment="center" height="237" width="338"]]
107 107  
108 108  In this section:
109 109  
... ... @@ -128,8 +128,8 @@
128 128  
129 129  (% class="box infomessage" %)
130 130  (((
131 -If there is the "Low CH temperature" error, the charging relay opens.
132 -If there is the "Low DCH temperature" error, the discharging relay opens.
131 +If there is the "Low CH temperature" error, the **charging **relay opens.
132 +If there is the "Low DCH temperature" error, the **discharging **relay opens.
133 133  )))
134 134  
135 135  == 3.6.5 High temperature protection ==
... ... @@ -138,7 +138,7 @@
138 138  
139 139  To change the battery protection parameters from high temperature, select the menu "Protections → High temperature protection":
140 140  
141 -[[image:1732213990755-759.png]]
141 +[[image:1732213990755-759.png||data-xwiki-image-style-alignment="center" height="258" width="370"]]
142 142  
143 143  In this section:
144 144  
... ... @@ -163,8 +163,8 @@
163 163  
164 164  (% class="box infomessage" %)
165 165  (((
166 -If there is the "High CH temperature" error, the charging relay opens.
167 -If there is the "High DCH temperature" error, the discharging relay opens.
166 +If there is the "High CH temperature" error, the **charging **relay opens.
167 +If there is the "High DCH temperature" error, the **discharging **relay opens.
168 168  )))
169 169  
170 170  == 3.6.6 Battery cover protection ==
... ... @@ -171,6 +171,8 @@
171 171  
172 172  To change the protection parameters from opening the battery cover, select the menu "Protections → Battery cover protection":
173 173  
174 +[[image:1732214030014-281.png||data-xwiki-image-style-alignment="center" height="155" width="334"]]
175 +
174 174  In this section:
175 175  
176 176  * Enable – a flag to enable the protection;
... ... @@ -190,7 +190,7 @@
190 190  
191 191  (% class="box warningmessage" %)
192 192  (((
193 -**If there is the "Battery cover error", the “Critical error” is generated and all relays open.**
195 +If there is the "Battery cover error", the **“Critical error” **is generated and **all relays open.**
194 194  )))
195 195  
196 196  == 3.6.7 High humidity protection ==
... ... @@ -199,12 +199,13 @@
199 199  
200 200  To change the protection parameters of the battery from high humidity, select the menu "Protections → High humidity protection":
201 201  
204 +[[image:1732214076060-358.png||data-xwiki-image-style-alignment="center" height="185" width="321"]]
202 202  
203 203  In this section:
204 204  
205 205  * Enable – a flag to enable the protection;
206 -* Maximum humidty, RH%;
207 -* Tolerant humidty, RH%;
209 +* Maximum humidity, RH%;
210 +* Tolerant humidity, RH%;
208 208  * Delay before setting the error, second;
209 209  * Delay before clearing the error, second;
210 210  * Lock the error until the device is reset.
... ... @@ -228,6 +228,7 @@
228 228  
229 229  To change the protection parameters of the battery from water, select the menu "Protections → Water protection":
230 230  
234 +[[image:1732214111990-184.png||data-xwiki-image-style-alignment="center" height="199" width="340"]]
231 231  
232 232  In this section:
233 233  
... ... @@ -250,7 +250,7 @@
250 250  
251 251  (% class="box warningmessage" %)
252 252  (((
253 -**If there is the “Water” error, the “Critical error” is generated and all relays open.**
257 +If there is the “Water” error,** **the **“Critical error”** is generated and **all relays open.**
254 254  )))
255 255  
256 256  == 3.6.9 Current sensor error ==
... ... @@ -259,6 +259,7 @@
259 259  
260 260  To change the test parameters of the current sensor connection circuits, select the menu "Protections → Current sensor error":
261 261  
266 +[[image:1732214146724-132.png||data-xwiki-image-style-alignment="center" height="438" width="365"]]
262 262  
263 263  In this section:
264 264  
... ... @@ -283,7 +283,7 @@
283 283  
284 284  (% class="box warningmessage" %)
285 285  (((
286 -**If there is the “Current sensor error”, the “Critical error” is generated and all relays open.**
291 +If there is the “Current sensor error”, the **“Critical error” **is generated and **all relays open.**
287 287  )))
288 288  
289 289  == 3.6.10 Short circuit protection ==
... ... @@ -292,6 +292,7 @@
292 292  
293 293  To change the protection parameters from short circuit, select the menu "Protections → Short circuit protection":
294 294  
300 +[[image:1732214207026-822.png||data-xwiki-image-style-alignment="center" height="528" width="371"]]
295 295  
296 296  In this section:
297 297  
... ... @@ -316,7 +316,7 @@
316 316  
317 317  (% class="box infomessage" %)
318 318  (((
319 -If there is the "Short circuit" error, the charging relay opens (the “Switch off the charging relay on error” flag is set) and the discharging relay opens (the “Switch off the discharging relay on error flag” is set).
325 +If there is the "Short circuit" error, the **charging **relay opens (the “Switch off the charging relay on error” flag is set) and the **discharging **relay opens (the “Switch off the discharging relay on error flag” is set).
320 320  )))
321 321  
322 322  == 3.6.11 Contactor high temperature protection ==
... ... @@ -325,6 +325,7 @@
325 325  
326 326  To change the overheating protection parameters of power contactors, select the menu "Protections → Contactor high temperature protection":
327 327  
334 +[[image:1732214237851-405.png||data-xwiki-image-style-alignment="center" height="234" width="336"]]
328 328  
329 329  In this section:
330 330  
... ... @@ -349,7 +349,7 @@
349 349  
350 350  (% class="box infomessage" %)
351 351  (((
352 -If there is the "Contactor high temperature" error, the charging relay opens (the “Switch off the charging relay on error” flag is set) and the discharging relay opens (the “Switch off the discharging relay on error flag” is set).
359 +If there is the "Contactor high temperature" error, the **charging **relay opens (the “Switch off the charging relay on error” flag is set) and the **discharging **relay opens (the “Switch off the discharging relay on error flag” is set).
353 353  )))
354 354  
355 355  == 3.6.12 Unallowable charging protection ==
... ... @@ -358,6 +358,7 @@
358 358  
359 359  To change the parameters of the unallowable charging protection, select the menu "Protections → Unallowable charging protection":
360 360  
368 +[[image:1732214272022-547.png||data-xwiki-image-style-alignment="center" height="145" width="312"]]
361 361  
362 362  In this section:
363 363  
... ... @@ -378,7 +378,7 @@
378 378  
379 379  (% class="box infomessage" %)
380 380  (((
381 -If there is the "Unallowable charging" error, the discharging relay opens.
389 +If there is the "Unallowable charging" error, the **discharging **relay opens.
382 382  )))
383 383  
384 384  == 3.6.13 Stuck contactor protection ==
... ... @@ -387,6 +387,7 @@
387 387  
388 388  To change the protection parameters against sticking, select the menu "Protections → Stuck contactor protection":
389 389  
398 +[[image:1732214367207-318.png||data-xwiki-image-style-alignment="center" height="152" width="331"]]
390 390  
391 391  In this section:
392 392  
... ... @@ -401,6 +401,11 @@
401 401  
402 402  * charging and discharging contactors are open, but the “Charging current present” or “Discharging current present” signal is set.
403 403  
413 +(% class="box warningmessage" %)
414 +(((
415 +If there is the “Stuck contactor error”, the **“Critical error” **is generated and **all relays open.**
416 +)))
417 +
404 404  == 3.6.14 Contactor feedback check ==
405 405  
406 406  The BMS Main 2.x can receive feedback signals from contactors and detect discrepancy between the control value and the feedback signal. To enable specific contactor protection, one of the discrete input must be set as corresponding contactor feedback signal (see section Input and output signals).
... ... @@ -407,6 +407,7 @@
407 407  
408 408  To change the contactor feedback check parameters, select the menu "Protections → Contactor feedback check":
409 409  
424 +[[image:1732214400721-274.png||data-xwiki-image-style-alignment="center" height="150" width="323"]]
410 410  
411 411  In this section:
412 412  
... ... @@ -419,6 +419,11 @@
419 419  
420 420  * discrete output of charging, precharge, discharging, charging/discharging or main contactor not matches its feedback value.
421 421  
437 +(% class="box warningmessage" %)
438 +(((
439 +If there is the contactor feedback error, the **“Critical error” **is generated and **all relays open.**
440 +)))
441 +
422 422  == 3.6.15 Charging contactor cycles protection ==
423 423  
424 424  The BMS protects the charging contactor against frequent switching.
... ... @@ -425,6 +425,7 @@
425 425  
426 426  To change the protection parameters against high frequency switching of the charging contactor, select the menu "Protections → Charging contactor cycles protection":
427 427  
448 +[[image:1732214432750-543.png||data-xwiki-image-style-alignment="center" height="260" width="336"]]
428 428  
429 429  In this section:
430 430  
... ... @@ -448,7 +448,7 @@
448 448  
449 449  (% class="box infomessage" %)
450 450  (((
451 -If there is the "CH contactor cycles error" error, the charging relay opens.
472 +If there is the "CH contactor cycles error" error, the **charging **relay opens.
452 452  )))
453 453  
454 454  == 3.6.16 Discharging contactor cycles protection ==
... ... @@ -457,6 +457,7 @@
457 457  
458 458  To change the protection parameters against high frequency switching of the discharging contactor, select the menu "Protections → Discharging contactor cycles protection":
459 459  
481 +[[image:1732214468462-541.png||data-xwiki-image-style-alignment="center" height="269" width="346"]]
460 460  
461 461  In this section:
462 462  
... ... @@ -480,7 +480,7 @@
480 480  
481 481  (% class="box infomessage" %)
482 482  (((
483 -If there is the "DCH contactor cycles error" error, the discharging relay opens.
505 +If there is the "DCH contactor cycles error" error, the **discharging **relay opens.
484 484  )))
485 485  
486 486  == 3.6.17 Temperature sensor error ==
... ... @@ -489,6 +489,7 @@
489 489  
490 490  To change the protection parameters of the temperature sensors circuits, select the menu "Protections → Temperature sensor error":
491 491  
514 +[[image:1732214501360-654.png||data-xwiki-image-style-alignment="center" height="154" width="334"]]
492 492  
493 493  In this section:
494 494  
... ... @@ -501,7 +501,7 @@
501 501  
502 502  (% class="box warningmessage" %)
503 503  (((
504 -**If there is the “No temp. sensors” or “Temp. sensor is shorted” error, the “Critical error” is generated and all relays open.**
527 +If there is the “No temp. sensors” or “Temp. sensor is shorted” error, the **“Critical error” **is generated and **all relays open.**
505 505  )))
506 506  
507 507  == 3.6.18 Logic high temperature protection ==
... ... @@ -508,6 +508,7 @@
508 508  
509 509  To change the overheating protection parameters of BMS Logic boards, select the menu "Protections → Logic high temperature protection":
510 510  
534 +[[image:1732214545352-111.png||data-xwiki-image-style-alignment="center" height="156" width="309"]]
511 511  
512 512  In this section:
513 513  
... ... @@ -528,7 +528,7 @@
528 528  
529 529  (% class="box infomessage" %)
530 530  (((
531 -**Cell balancing is prohibited for overheated boards.**
555 +Cell balancing is prohibited for overheated boards.
532 532  )))
533 533  
534 534  == 3.6.19 Logic offline protection ==
... ... @@ -535,6 +535,7 @@
535 535  
536 536  To change the protection parameters from loss of communication with BMS Logic boards, select the menu "Protections → Logic offline protection":
537 537  
562 +[[image:1732214579147-515.png||data-xwiki-image-style-alignment="center" height="107" width="204"]]
538 538  
539 539  In this section:
540 540  
... ... @@ -553,7 +553,7 @@
553 553  
554 554  (% class="box warningmessage" %)
555 555  (((
556 -**If there is the "Logic offline" error, the “Critical error” is generated and all relays open.**
581 +If there is the "Logic offline" error, the **“Critical error”** is generated and **all relays open.**
557 557  )))
558 558  
559 559  == 3.6.20 Cell count protection ==
... ... @@ -560,6 +560,7 @@
560 560  
561 561  To change the protection parameters from the mismatch of the number of cells to the set value, select the menu "Protections → Cell count protection":
562 562  
588 +[[image:1732214641606-453.png||data-xwiki-image-style-alignment="center" height="178" width="341"]]
563 563  
564 564  In this section:
565 565  
... ... @@ -581,7 +581,7 @@
581 581  
582 582  (% class="box warningmessage" %)
583 583  (((
584 -**If there is the "Cell count error", the “Critical error” is generated and all relays open.**
610 +If there is the "Cell count error",** **the **“Critical error”** is generated and **all relays open.**
585 585  )))
586 586  
587 587  == 3.6.21 Logic count protection ==
... ... @@ -588,6 +588,7 @@
588 588  
589 589  To change the protection parameters from the mismatch of the number of BMS Logic boards to the set value, select the menu "Protections → Logic count protection":
590 590  
617 +[[image:1732214675358-202.png||data-xwiki-image-style-alignment="center" height="163" width="230"]]
591 591  
592 592  In this section:
593 593  
... ... @@ -608,7 +608,7 @@
608 608  
609 609  (% class="box warningmessage" %)
610 610  (((
611 -**If there is the "Logic count error", the “Critical error” is generated and all relays open.**
638 +If there is the "Logic count error", the **“Critical error” **is generated and **all relays open.**
612 612  )))
613 613  
614 614  == 3.6.22 WDT protection ==
... ... @@ -617,6 +617,7 @@
617 617  
618 618  To change the parameters of the watchdog protection, select the menu "Protections → WDT protection":
619 619  
647 +[[image:1732214703914-144.png||data-xwiki-image-style-alignment="center" height="127" width="323"]]
620 620  
621 621  In this section:
622 622  
... ... @@ -630,7 +630,7 @@
630 630  
631 631  (% class="box warningmessage" %)
632 632  (((
633 -**If there is the "WDT reset" error, the “Critical error” is generated and all relays open.**
661 +If there is the "WDT reset" error, the **“Critical error”** is generated and** all relays open.**
634 634  )))
635 635  
636 636  == 3.6.23 Insulation monitoring ==
... ... @@ -639,6 +639,7 @@
639 639  
640 640  To change the insulation monitoring parameters, select the menu "Protections → Insulation monitoring":
641 641  
670 +[[image:1732214731490-961.png||data-xwiki-image-style-alignment="center" height="162" width="315"]]
642 642  
643 643  In this section:
644 644  
... ... @@ -649,10 +649,16 @@
649 649  
650 650  Error is set if corresponding discrete input is set up and it received logical zero.
651 651  
681 +(% class="box warningmessage" %)
682 +(((
683 +If there is the "Insulation monitoring" error, the **“Critical error”** is generated and** all relays open.**
684 +)))
685 +
652 652  == 3.6.24 Critical error parameters ==
653 653  
654 654  To change the critical error parameters, select the menu "Protections → Critical error parameters":
655 655  
690 +[[image:1732214761141-983.png||data-xwiki-image-style-alignment="center" height="158" width="348"]]
656 656  
657 657  In this section:
658 658  
... ... @@ -672,10 +672,13 @@
672 672  * “No temp. sensors”;
673 673  * “Temp. sensor is shorted”;
674 674  * “Current sensor error”;
710 +* "Stuck contactor";
711 +* "Contactor feedback";
675 675  * “Shunt offline”;
676 676  * “Shunt error”;
677 677  * “Settings error”;
678 -* “WDT reset”.
715 +* “WDT reset”
716 +* "Insulation monitoring".
679 679  
680 680  The “Critical error” is cleared if there are no errors from the list above during the “Delay before clearing the error” time.
681 681  
... ... @@ -686,10 +686,32 @@
686 686  
687 687  == 3.6.25 General error parameters ==
688 688  
727 +To change the general error parameters, select the menu "Protections → General error parameters":
728 +
729 +[[image:1732214987517-111.png||data-xwiki-image-style-alignment="center" height="535" width="349"]]
730 +
731 +In this section:
732 +
733 +* Enable – a flag to enable the protection;
734 +* Delay before setting the error, second;
735 +* Delay before clearing the error, second;
736 +* Lock the error until the device is reset;
737 +* Errors – a section to select errors that should trigger General error.
738 +
739 +The critical error flag is generated if at least one of the selected errors is generated during the “Delay before setting the error” time.
740 +
741 +The “General error” is cleared if there are no errors from selected list during the “Delay before clearing the error” time.
742 +
743 +(% class="box infomessage" %)
744 +(((
745 +The "General error" is //indicative //and can be linked to any discrete output of the board.
746 +)))
747 +
689 689  == 3.6.26 Low SOC signal ==
690 690  
691 691  To change the parameters of the generation a signal about low battery level, select the menu "Protections → Low SOC signal":
692 692  
752 +[[image:1732215174961-645.png||data-xwiki-image-style-alignment="center" height="186" width="325"]]
693 693  
694 694  In this section:
695 695  
... ... @@ -708,12 +708,16 @@
708 708  
709 709  * the battery SOC is greater than the “Tolerant SOC” during the “Delay before clearing the signal” time.
710 710  
771 +(% class="box infomessage" %)
772 +(((
711 711  The "Low SOC signal" is //indicative //and can be linked to any discrete output of the board.
774 +)))
712 712  
713 713  == 3.6.27 High charging current signal ==
714 714  
715 715  To change the parameters of the generation high-current signal, select the menu "Protections → High charging current signal":
716 716  
780 +[[image:1732215211714-445.png||data-xwiki-image-style-alignment="center" height="181" width="322"]]
717 717  
718 718  In this section:
719 719  
... ... @@ -732,12 +732,16 @@
732 732  
733 733  * the measured current is less than the “Tolerant charging current” value during the “Delay before clearing the signal” time.
734 734  
799 +(% class="box infomessage" %)
800 +(((
735 735  The "High charging current" signal is //indicative //and can be linked to any discrete output of the board.
802 +)))
736 736  
737 737  == 3.6.28 Heater control ==
738 738  
739 739  To change the parameters of the heater control algorithm, select the menu "Protections → Heater control":
740 740  
808 +[[image:1732215252650-791.png||data-xwiki-image-style-alignment="center" height="233" width="370"]]
741 741  
742 742  In this section:
743 743  
... ... @@ -761,7 +761,7 @@
761 761  
762 762  (% class="box infomessage" %)
763 763  (((
764 -If there is the "Heater" signal, the heater relay closes and/or a signal is output to the corresponded digital output.
832 +If there is the "Heater" signal, the **heater **relay closes and/or a signal is output to the corresponded digital output.
765 765  )))
766 766  
767 767  == 3.6.29 Heater (AUX) control ==
... ... @@ -768,6 +768,7 @@
768 768  
769 769  To change the parameters of the auxiliary heater control algorithm, select the menu "Protections → Heater (AUX) control":
770 770  
839 +[[image:1732215282135-420.png||data-xwiki-image-style-alignment="center" height="228" width="361"]]
771 771  
772 772  In this section:
773 773  
... ... @@ -791,7 +791,7 @@
791 791  
792 792  (% class="box infomessage" %)
793 793  (((
794 -If there is the "Heater (AUX)" signal, the auxiliary heater relay closes and/or a signal is output to the corresponded digital output.
863 +If there is the "Heater (AUX)" signal, the **auxiliary heater **relay closes and/or a signal is output to the corresponded digital output.
795 795  )))
796 796  
797 797  == 3.6.30 Cooler control ==
... ... @@ -798,6 +798,7 @@
798 798  
799 799  To change the parameters of the cooler control algorithm, select the menu "Protections → Cooler control":
800 800  
870 +[[image:1732215313977-499.png||data-xwiki-image-style-alignment="center" height="219" width="348"]]
801 801  
802 802  In this section:
803 803  
... ... @@ -821,7 +821,7 @@
821 821  
822 822  (% class="box infomessage" %)
823 823  (((
824 -If there is the "Cooler" signal, the cooler relay closes and/or a signal is output to the corresponded digital output.
894 +If there is the "Cooler" signal, the **cooler **relay closes and/or a signal is output to the corresponded digital output.
825 825  )))
826 826  
827 827  == 3.6.31 Fault simulation ==
... ... @@ -830,40 +830,6 @@
830 830  
831 831  To simulate battery and BMS errors, select the menu "Protections → Fault simulation":
832 832  
903 +[[image:1732215359330-850.png||data-xwiki-image-style-alignment="center" height="732" width="204"]]
833 833  
834 -In this section:
835 -
836 -* Overcurrent;
837 -* Undervoltage;
838 -* Overvoltage;
839 -* Low CH temperature;
840 -* Low DCH temperature;
841 -* High CH temperature;
842 -* High DCH temperature;
843 -* Battery cover error;
844 -* High humidity;
845 -* Water;
846 -* Current sensor error;
847 -* Short circuit;
848 -* Contactor high temperature;
849 -* Unallowable charging;
850 -* Stuck contactor;
851 -* CH contactor feedback error;
852 -* DCH contactor feedback error;
853 -* PCH contactor feedback error;
854 -* CH/DCH contactor feedback error;
855 -* Main contactor feedback error;
856 -* CH contactor cycles error;
857 -* DCH contactor cycles error;
858 -* Logic high temperature;
859 -* Logic offline;
860 -* Cell count error;
861 -* Logic count error;
862 -* Insulation error;
863 -* Critical error;
864 -* Low SOC;
865 -* High charging current;
866 -* Heater;
867 -* Cooler.
868 -
869 869  To simulate errors, set the necessary flags and click on the "Save" button.
1732214030014-281.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +12.6 KB
Content
1732214076060-358.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +16.1 KB
Content
1732214111990-184.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +16.1 KB
Content
1732214146724-132.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +27.8 KB
Content
1732214183037-761.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +32.7 KB
Content
1732214207026-822.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +32.8 KB
Content
1732214237851-405.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +22.6 KB
Content
1732214272022-547.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +13.7 KB
Content
1732214367207-318.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +13.2 KB
Content
1732214400721-274.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +13.9 KB
Content
1732214432750-543.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +20.1 KB
Content
1732214468462-541.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +20.3 KB
Content
1732214501360-654.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +13.1 KB
Content
1732214545352-111.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +13.2 KB
Content
1732214579147-515.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +7.5 KB
Content
1732214641606-453.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +12.8 KB
Content
1732214675358-202.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +9.1 KB
Content
1732214703914-144.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +9.6 KB
Content
1732214731490-961.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +13.7 KB
Content
1732214761141-983.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +13.1 KB
Content
1732214987517-111.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +37.3 KB
Content
1732215174961-645.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +16.1 KB
Content
1732215211714-445.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +17.4 KB
Content
1732215252650-791.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +17.9 KB
Content
1732215282135-420.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +19.3 KB
Content
1732215313977-499.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +17.8 KB
Content
1732215359330-850.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +31.8 KB
Content