... ... @@ -706,162 +706,17 @@
706 706  
707 707  * the battery SOC is greater than the “Tolerant SOC” during the “Delay before clearing the signal” time.
708 708  
709 -The "Low SOC signal" is //indicative //and can be linked to any discrete output of the board.
709 +(% class="box infomessage" %)
710 +(((
711 +The "Low SOC signal" is indicative and can be linked to any discrete output of the board.
712 +)))
710 710  
711 711  == 3.6.27 High charging current signal ==
712 712  
713 -To change the parameters of the generation high-current signal, select the menu "Protections → High charging current signal":
714 -
715 -
716 -In this section:
717 -
718 -* Enable – a flag to enable signal generation;
719 -* Maximum charging current, А;
720 -* Tolerant charging current, А;
721 -* Delay before setting the signal, second;
722 -* Delay before clearing the signal, second;
723 -* Lock the signal until the device is reset.
724 -
725 -Signal generation conditions:
726 -
727 -* the measured current is greater than the “Maximum charging current” value during the “Delay before setting the signal” time.
728 -
729 -Conditions for clearing the signal:
730 -
731 -* the measured current is less than the “Tolerant charging current” value during the “Delay before clearing the signal” time.
732 -
733 -The "High charging current" signal is //indicative //and can be linked to any discrete output of the board.
734 -
735 735  == 3.6.28 Heater control ==
736 736  
737 -To change the parameters of the heater control algorithm, select the menu "Protections → Heater control":
738 -
739 -
740 -In this section:
741 -
742 -* Enable – a flag to enable heater control;
743 -* Minimum cell temperature, °C;
744 -* Tolerant cell temperature, °C;
745 -* Delay before setting the signal, second;
746 -* Delay before clearing the signal, second;
747 -* Lock the signal until the device is reset;
748 -* Switch off the heater relay on errors (Undervoltage, Overcurrent, High temperature, Short circuit or Critical error).
749 -
750 -As a result of operating the heating algorithm, the “Heater” signal is generated.
751 -
752 -Conditions of signal generation:
753 -
754 -* The minimum temperature among all cells of the battery is less than the “Minimum cell temperature” value during the “Delay before setting the signal” time.
755 -
756 -Conditions for clearing the signal:
757 -
758 -* the minimum temperature among all cells of the battery is greater than the “Tolerant cell temperature” value during the “Delay before clearing the signal” time.
759 -
760 -(% class="box infomessage" %)
761 -(((
762 -If there is the "Heater" signal, the heater relay closes and/or a signal is output to the corresponded digital output.
763 -)))
764 -
765 765  == 3.6.29 Heater (AUX) control ==
766 766  
767 -To change the parameters of the auxiliary heater control algorithm, select the menu "Protections → Heater (AUX) control":
768 -
769 -
770 -In this section:
771 -
772 -* Enable – a flag to enable heater control;
773 -* Minimum cell temperature, °C;
774 -* Tolerant cell temperature, °C;
775 -* Delay before setting the signal, second;
776 -* Delay before clearing the signal, second;
777 -* Lock the signal until the device is reset;
778 -* Switch off the heater relay on errors (Undervoltage, Overcurrent, High temperature, Short circuit or Critical error).
779 -
780 -As a result of operating the heating algorithm, the “Heater (AUX)” signal is generated.
781 -
782 -Conditions of signal generation:
783 -
784 -* The minimum temperature among all cells of the battery is less than the “Minimum cell temperature” value during the “Delay before setting the signal” time.
785 -
786 -Conditions for clearing the signal:
787 -
788 -* the minimum temperature among all cells of the battery is greater than the “Tolerant cell temperature” value during the “Delay before clearing the signal” time.
789 -
790 -(% class="box infomessage" %)
791 -(((
792 -If there is the "Heater (AUX)" signal, the auxiliary heater relay closes and/or a signal is output to the corresponded digital output.
793 -)))
794 -
795 795  == 3.6.30 Cooler control ==
796 796  
797 -To change the parameters of the cooler control algorithm, select the menu "Protections → Cooler control":
798 -
799 -
800 -In this section:
801 -
802 -* Enable – a flag to enable cooler control;
803 -* Maximum cell temperature, °C;
804 -* Tolerant cell temperature, °C;
805 -* Delay before setting the signal, second;
806 -* Delay before clearing the signal, second;
807 -* Lock the signal until the device is reset;
808 -* Switch off the cooler relay on errors (Undervoltage, Overcurrent, Low temperature, Short circuit or Critical error).
809 -
810 -As a result of operating the cooling algorithm, the "Cooler" signal is generated.
811 -
812 -Conditions of signal generation:
813 -
814 -* the maximum temperature among all cells of the battery is greater than the “Maximum cell temperature” value during the “Delay before setting the signal” time.
815 -
816 -Conditions for clearing the signal:
817 -
818 -* the maximum temperature among all cells of the battery is less than the “Tolerant cell temperature” value during the “Delay before clearing the signal” time.
819 -
820 -(% class="box infomessage" %)
821 -(((
822 -If there is the "Cooler" signal, the cooler relay closes and/or a signal is output to the corresponded digital output.
823 -)))
824 -
825 825  == 3.6.31 Fault simulation ==
826 -
827 -The board provides the ability to manually generate error flags bypassing the protection algorithms. This functionality is intended for commissioning.
828 -
829 -To simulate battery and BMS errors, select the menu "Protections → Fault simulation":
830 -
831 -
832 -In this section:
833 -
834 -* Overcurrent;
835 -* Undervoltage;
836 -* Overvoltage;
837 -* Low CH temperature;
838 -* Low DCH temperature;
839 -* High CH temperature;
840 -* High DCH temperature;
841 -* Battery cover error;
842 -* High humidity;
843 -* Water;
844 -* Current sensor error;
845 -* Short circuit;
846 -* Contactor high temperature;
847 -* Unallowable charging;
848 -* Stuck contactor;
849 -* CH contactor feedback error;
850 -* DCH contactor feedback error;
851 -* PCH contactor feedback error;
852 -* CH/DCH contactor feedback error;
853 -* Main contactor feedback error;
854 -* CH contactor cycles error;
855 -* DCH contactor cycles error;
856 -* Logic high temperature;
857 -* Logic offline;
858 -* Cell count error;
859 -* Logic count error;
860 -* Insulation error;
861 -* Critical error;
862 -* Low SOC;
863 -* High charging current;
864 -* Heater;
865 -* Cooler.
866 -
867 -To simulate errors, set the necessary flags and click on the "Save" button.
1732213953083-955.png