Changes for page 3.6 Battery protection
Last modified by Admin on 2025/04/09 12:25
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -73,33 +73,4 @@ 73 73 74 74 [[image:1732212357972-295.png]] 75 75 76 -In this section: 77 - 78 -* Enable – a flag to enable the protection; 79 -* Maximum cell voltage, V; 80 -* Tolerant cell voltage, V; 81 -* Delay before setting the error, second; 82 -* Delay before clearing the error, second; 83 -* Switch off the discharging relay on error – a flag to open the discharging relay when the "Overvoltage" error is generated; 84 -* Lock the error until the device is reset. 85 - 86 -As a result of the operation of the battery protection from high voltage, the "Overvoltage" error is generated. 87 - 88 -Error generation conditions: 89 - 90 -* the maximum voltage among all cells of the battery is greater than the “Maximum cell voltage” value for the “Delay before setting the error” time. 91 - 92 -Conditions for removing the error: 93 - 94 -* the maximum voltage among all cells of the battery is less than the “Tolerant cell voltage” value for the “Delay before clearing the error” time. 95 - 96 -(% class="box infomessage" %) 97 -((( 98 -If there is the "Overvoltage" error, the charging relay and discharging relay opens (if the “Switch off the discharging relay on error” flag is set). 99 -))) 100 - 101 -3.6.4 Low temperature protection 102 - 103 -3.6.5 High temperature protection 104 - 105 105