... ... @@ -757,69 +757,10 @@
757 757  
758 758  * the minimum temperature among all cells of the battery is greater than the “Tolerant cell temperature” value during the “Delay before clearing the signal” time.
759 759  
760 -(% class="box infomessage" %)
761 -(((
762 762  If there is the "Heater" signal, the heater relay closes and/or a signal is output to the corresponded digital output.
763 -)))
764 764  
765 765  == 3.6.29 Heater (AUX) control ==
766 766  
767 -To change the parameters of the auxiliary heater control algorithm, select the menu "Protections → Heater (AUX) control":
768 -
769 -
770 -In this section:
771 -
772 -* Enable – a flag to enable heater control;
773 -* Minimum cell temperature, °C;
774 -* Tolerant cell temperature, °C;
775 -* Delay before setting the signal, second;
776 -* Delay before clearing the signal, second;
777 -* Lock the signal until the device is reset;
778 -* Switch off the heater relay on errors (Undervoltage, Overcurrent, High temperature, Short circuit or Critical error).
779 -
780 -As a result of operating the heating algorithm, the “Heater (AUX)” signal is generated.
781 -
782 -Conditions of signal generation:
783 -
784 -* The minimum temperature among all cells of the battery is less than the “Minimum cell temperature” value during the “Delay before setting the signal” time.
785 -
786 -Conditions for clearing the signal:
787 -
788 -* the minimum temperature among all cells of the battery is greater than the “Tolerant cell temperature” value during the “Delay before clearing the signal” time.
789 -
790 -(% class="box infomessage" %)
791 -(((
792 -If there is the "Heater (AUX)" signal, the auxiliary heater relay closes and/or a signal is output to the corresponded digital output.
793 -)))
794 -
795 795  == 3.6.30 Cooler control ==
796 796  
797 -To change the parameters of the cooler control algorithm, select the menu "Protections → Cooler control":
798 -
799 -
800 -In this section:
801 -
802 -* Enable – a flag to enable cooler control;
803 -* Maximum cell temperature, °C;
804 -* Tolerant cell temperature, °C;
805 -* Delay before setting the signal, second;
806 -* Delay before clearing the signal, second;
807 -* Lock the signal until the device is reset;
808 -* Switch off the cooler relay on errors (Undervoltage, Overcurrent, Low temperature, Short circuit or Critical error).
809 -
810 -As a result of operating the cooling algorithm, the "Cooler" signal is generated.
811 -
812 -Conditions of signal generation:
813 -
814 -* the maximum temperature among all cells of the battery is greater than the “Maximum cell temperature” value during the “Delay before setting the signal” time.
815 -
816 -Conditions for clearing the signal:
817 -
818 -* the maximum temperature among all cells of the battery is less than the “Tolerant cell temperature” value during the “Delay before clearing the signal” time.
819 -
820 -(% class="box infomessage" %)
821 -(((
822 -If there is the "Cooler" signal, the cooler relay closes and/or a signal is output to the corresponded digital output.
823 -)))
824 -
825 825  == 3.6.31 Fault simulation ==