... ... @@ -70,7 +70,7 @@
70 70  
71 71  To change the battery protection parameters from high voltage on the cells, select the menu "Protections → Overvoltage protection":
72 72  
73 -[[image:1732212357972-295.png]]
73 +[[Overvoltage protection settings>>image:1732212357972-295.png||data-xwiki-image-style-alignment="center" height="218" width="338"]]
74 74  
75 75  In this section:
76 76  
... ... @@ -103,6 +103,7 @@
103 103  
104 104  To change the battery protection parameters from low temperature, select the menu "Protections → Low temperature protection":
105 105  
106 +[[Low temperature protection settings>>image:1732213953083-955.png||data-xwiki-image-style-alignment="center" height="237" width="338"]]
106 106  
107 107  In this section:
108 108  
... ... @@ -137,6 +137,7 @@
137 137  
138 138  To change the battery protection parameters from high temperature, select the menu "Protections → High temperature protection":
139 139  
141 +[[High temperature protection settings>>image:1732213990755-759.png||data-xwiki-image-style-alignment="center" height="258" width="370"]]
140 140  
141 141  In this section:
142 142  
... ... @@ -169,6 +169,8 @@
169 169  
170 170  To change the protection parameters from opening the battery cover, select the menu "Protections → Battery cover protection":
171 171  
174 +[[Battery cover protection settings>>image:1732214030014-281.png||data-xwiki-image-style-alignment="center" height="155" width="334"]]
175 +
172 172  In this section:
173 173  
174 174  * Enable – a flag to enable the protection;
... ... @@ -197,12 +197,13 @@
197 197  
198 198  To change the protection parameters of the battery from high humidity, select the menu "Protections → High humidity protection":
199 199  
204 +[[High humidity protection settings>>image:1732214076060-358.png||data-xwiki-image-style-alignment="center" height="185" width="321"]]
200 200  
201 201  In this section:
202 202  
203 203  * Enable – a flag to enable the protection;
204 -* Maximum humidty, RH%;
205 -* Tolerant humidty, RH%;
209 +* Maximum humidity, RH%;
210 +* Tolerant humidity, RH%;
206 206  * Delay before setting the error, second;
207 207  * Delay before clearing the error, second;
208 208  * Lock the error until the device is reset.
... ... @@ -226,6 +226,7 @@
226 226  
227 227  To change the protection parameters of the battery from water, select the menu "Protections → Water protection":
228 228  
234 +[[Water protection settings>>image:1732214111990-184.png||data-xwiki-image-style-alignment="center" height="199" width="340"]]
229 229  
230 230  In this section:
231 231  
... ... @@ -257,6 +257,7 @@
257 257  
258 258  To change the test parameters of the current sensor connection circuits, select the menu "Protections → Current sensor error":
259 259  
266 +[[Current sensor error settings>>image:1732214146724-132.png||data-xwiki-image-style-alignment="center" height="438" width="365"]]
260 260  
261 261  In this section:
262 262  
... ... @@ -290,6 +290,7 @@
290 290  
291 291  To change the protection parameters from short circuit, select the menu "Protections → Short circuit protection":
292 292  
300 +[[Short circuit protection se>>image:1732214207026-822.png||data-xwiki-image-style-alignment="center" height="528" width="371"]]
293 293  
294 294  In this section:
295 295  
... ... @@ -764,7 +764,7 @@
764 764  
765 765  == 3.6.29 Heater (AUX) control ==
766 766  
767 -To change the parameters of the heater control algorithm, select the menu "Protections → Heater (AUX) control":
775 +To change the parameters of the auxiliary heater control algorithm, select the menu "Protections → Heater (AUX) control":
768 768  
769 769  
770 770  In this section:
... ... @@ -787,8 +787,81 @@
787 787  
788 788  * the minimum temperature among all cells of the battery is greater than the “Tolerant cell temperature” value during the “Delay before clearing the signal” time.
789 789  
790 -If there is the "Heater" signal, the heater relay closes and/or a signal is output to the corresponded digital output.
798 +(% class="box infomessage" %)
799 +(((
800 +If there is the "Heater (AUX)" signal, the auxiliary heater relay closes and/or a signal is output to the corresponded digital output.
801 +)))
791 791  
792 792  == 3.6.30 Cooler control ==
793 793  
805 +To change the parameters of the cooler control algorithm, select the menu "Protections → Cooler control":
806 +
807 +
808 +In this section:
809 +
810 +* Enable – a flag to enable cooler control;
811 +* Maximum cell temperature, °C;
812 +* Tolerant cell temperature, °C;
813 +* Delay before setting the signal, second;
814 +* Delay before clearing the signal, second;
815 +* Lock the signal until the device is reset;
816 +* Switch off the cooler relay on errors (Undervoltage, Overcurrent, Low temperature, Short circuit or Critical error).
817 +
818 +As a result of operating the cooling algorithm, the "Cooler" signal is generated.
819 +
820 +Conditions of signal generation:
821 +
822 +* the maximum temperature among all cells of the battery is greater than the “Maximum cell temperature” value during the “Delay before setting the signal” time.
823 +
824 +Conditions for clearing the signal:
825 +
826 +* the maximum temperature among all cells of the battery is less than the “Tolerant cell temperature” value during the “Delay before clearing the signal” time.
827 +
828 +(% class="box infomessage" %)
829 +(((
830 +If there is the "Cooler" signal, the cooler relay closes and/or a signal is output to the corresponded digital output.
831 +)))
832 +
794 794  == 3.6.31 Fault simulation ==
834 +
835 +The board provides the ability to manually generate error flags bypassing the protection algorithms. This functionality is intended for commissioning.
836 +
837 +To simulate battery and BMS errors, select the menu "Protections → Fault simulation":
838 +
839 +
840 +In this section:
841 +
842 +* Overcurrent;
843 +* Undervoltage;
844 +* Overvoltage;
845 +* Low CH temperature;
846 +* Low DCH temperature;
847 +* High CH temperature;
848 +* High DCH temperature;
849 +* Battery cover error;
850 +* High humidity;
851 +* Water;
852 +* Current sensor error;
853 +* Short circuit;
854 +* Contactor high temperature;
855 +* Unallowable charging;
856 +* Stuck contactor;
857 +* CH contactor feedback error;
858 +* DCH contactor feedback error;
859 +* PCH contactor feedback error;
860 +* CH/DCH contactor feedback error;
861 +* Main contactor feedback error;
862 +* CH contactor cycles error;
863 +* DCH contactor cycles error;
864 +* Logic high temperature;
865 +* Logic offline;
866 +* Cell count error;
867 +* Logic count error;
868 +* Insulation error;
869 +* Critical error;
870 +* Low SOC;
871 +* High charging current;
872 +* Heater;
873 +* Cooler.
874 +
875 +To simulate errors, set the necessary flags and click on the "Save" button.
1732213953083-955.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +22.0 KB
Content
1732213990755-759.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +22.7 KB
Content
1732214030014-281.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +12.6 KB
Content
1732214076060-358.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +16.1 KB
Content
1732214111990-184.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +16.1 KB
Content
1732214146724-132.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +27.8 KB
Content
1732214183037-761.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +32.7 KB
Content
1732214207026-822.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.admin
Size
... ... @@ -1,0 +1,1 @@
1 +32.8 KB
Content