... ... @@ -73,4 +73,60 @@
73 73  
74 74  [[image:1732212357972-295.png]]
75 75  
76 -
76 +In this section:
77 +
78 +* Enable – a flag to enable the protection;
79 +* Maximum cell voltage, V;
80 +* Tolerant cell voltage, V;
81 +* Delay before setting the error, second;
82 +* Delay before clearing the error, second;
83 +* Switch off the discharging relay on error – a flag to open the discharging relay when the "Overvoltage" error is generated;
84 +* Lock the error until the device is reset.
85 +
86 +As a result of the operation of the battery protection from high voltage, the "Overvoltage" error is generated.
87 +
88 +Error generation conditions:
89 +
90 +* the maximum voltage among all cells of the battery is greater than the “Maximum cell voltage” value for the “Delay before setting the error” time.
91 +
92 +Conditions for removing the error:
93 +
94 +* the maximum voltage among all cells of the battery is less than the “Tolerant cell voltage” value for the “Delay before clearing the error” time.
95 +
96 +(% class="box infomessage" %)
97 +(((
98 +If there is the "Overvoltage" error, the charging relay and discharging relay opens (if the “Switch off the discharging relay on error” flag is set).
99 +)))
100 +
101 +3.6.4 Low temperature protection
102 +
103 +3.6.5 High temperature protection
104 +
105 +3.6.6 Battery cover protection
106 +
107 +3.6.7 High humidity protection
108 +
109 +3.6.8  Water protection
110 +3.6.9 Current sensor error
111 +3.6.10 Short circuit protection
112 +3.6.11 Contactor high temperature protection
113 +3.6.12 Unallowable charging protection
114 +3.6.13 Stuck contactor protection
115 +3.6.14 Contactor feedback check
116 +3.6.15 Charging contactor cycles protection
117 +3.6.16 Discharging contactor cycles protection
118 +3.6.17 Temperature sensor error
119 +3.6.18 Logic high temperature protection
120 +3.6.19 Logic offline protection
121 +3.6.20 Cell count protection
122 +3.6.21 Logic count protection
123 +3.6. WDT protection
124 +Insulation monitoring
125 +Critical error parameters
126 +General error parameters
127 +Low SOC signal
128 +High charging current signal
129 +Heater control
130 +Heater (AUX) control
131 +Cooler control
132 +Fault simulation