... ... @@ -497,12 +497,44 @@
497 497  
498 498  If there are no temperature sensors connected to a BMS Logic board or any temperature sensor is shorted, the "No temp. sensors" error and "Temp. sensor is shorted" error are generated respectively. These errors generated and removed with the “Delay before setting the error” and “Delay before clearing the error” delays.
499 499  
500 +(% class="box warningmessage" %)
501 +(((
500 500  **If there is the “No temp. sensors” or “Temp. sensor is shorted” error, the “Critical error” is generated and all relays open.**
503 +)))
501 501  
502 502  == 3.6.18 Logic high temperature protection ==
503 503  
507 +To change the overheating protection parameters of BMS Logic boards, select the menu "Protections → Logic high temperature protection":
508 +
509 +
510 +In this section:
511 +
512 +* Enable – a flag to enable the protection;
513 +* Maximum Logic temperature, °C;
514 +* Tolerant Logic temperature, °C;
515 +* Lock the error until the device is reset.
516 +
517 +As a result of the operation of the protection from high temperatures of BMS Logic boards, the "Logic high temperature" is generated.
518 +
519 +Error generation conditions:
520 +
521 +* a BMS Logic board temperature is higher than the “Maximum Logic temperature” value.
522 +
523 +Conditions for removing the error:
524 +
525 +* a BMS Logic board temperature is less than the “Tolerant Logic temperature” value.
526 +
527 +(% class="box infomessage" %)
528 +(((
529 +**Cell balancing is prohibited for overheated boards.**
530 +)))
531 +
504 504  == 3.6.19 Logic offline protection ==
505 505  
534 +To change the protection parameters from loss of communication with BMS Logic boards, select the menu "Protections → Logic offline protection":
535 +
536 +
537 +
506 506  == 3.6.20 Cell count protection ==
507 507  
508 508  == 3.6.21 Logic count protection ==