... ... @@ -197,6 +197,7 @@
197 197  
198 198  To change the protection parameters of the battery from high humidity, select the menu "Protections → High humidity protection":
199 199  
200 +
200 200  In this section:
201 201  
202 202  * Enable – a flag to enable the protection;
... ... @@ -216,13 +216,70 @@
216 216  
217 217  * the measured humidity is less than the “Tolerant humidity” during the “Delay before clearing the error” time.
218 218  
220 +(% class="box infomessage" %)
221 +(((
219 219  If there is the "High humidity" error, no action is taken. The error is indicative.
223 +)))
220 220  
221 -
222 222  == 3.6.8  Water protection ==
223 223  
227 +To change the protection parameters of the battery from water, select the menu "Protections → Water protection":
228 +
229 +
230 +In this section:
231 +
232 +* Enable – a flag to enable the protection;
233 +* Maximum (water) humidty, RH%;
234 +* Tolerant humidity, RH%;
235 +* Delay before setting the error, second;
236 +* Delay before clearing the error, second;
237 +* Lock the error until the device is reset.
238 +
239 +As a result of the operation of the battery protection from water, the "Water" error is generated.
240 +
241 +Error generation conditions:
242 +
243 +* the measured humidity is greater than the “Maximum (water) humidity” value during the “Delay before setting the error” time.
244 +
245 +Conditions for removing the error:
246 +
247 +* the measured humidity is less than the “Tolerant humidity” value during the “Delay before clearing the error” time.
248 +
249 +(% class="box warningmessage" %)
250 +(((
251 +**If there is the “Water” error, the “Critical error” is generated and all relays open.**
252 +)))
253 +
224 224  == 3.6.9 Current sensor error ==
225 225  
256 +The board is implemented to check the current sensor connection circuits. The circuits are checked for breakage and short-circuit to the +5 V supply line.
257 +
258 +To change the test parameters of the current sensor connection circuits, select the menu "Protections → Current sensor error":
259 +
260 +
261 +In this section:
262 +
263 +* Enable – a flag to enable the protection;
264 +* Maximum voltage, V;
265 +* Minimum voltage, V;
266 +* Hysteresis voltage – a hysteresis value to clear the error, V;
267 +* Delay before setting the error, second;
268 +* Delay before clearing the error, second;
269 +* Lock the error until the device is reset.
270 +
271 +If there is an open or short circuit connection of a current sensor, the "Current sensor error" is generated.
272 +
273 +Error generation conditions:
274 +
275 +* the voltage in the signal line or zero level line of the current sensor is greater than the “Maximum voltage” value during the “Delay before setting the error” time;
276 +* the voltage in the signal line or zero level line of the current sensor is less than the “Minimum voltage” value during the “Delay before setting the error” time.
277 +
278 +Conditions for removing the error:
279 +
280 +* the voltage in the signal line or zero level line of the current sensor is in range from (Minimum voltage + Hysteresis voltage) to (Maximum voltage - Hysteresis voltage) during the “Delay before clearing the error” time.
281 +
282 +**If there is the “Current sensor error”, the “Critical error” is generated and all relays open.**
283 +
226 226  == 3.6.10 Short circuit protection ==
227 227  
228 228  == 3.6.11 Contactor high temperature protection ==