... ... @@ -6,9 +6,8 @@
6 6  
7 7  [[Overcurrent protection settings>>image:1732211959984-118.png||data-xwiki-image-style-alignment="center" height="266" width="386"]]
8 8  
9 + In this section:
9 9  
10 -In this section:
11 -
12 12  * Enable – a flag to enable the protection;
13 13  * Maximum charging current, А;
14 14  * Tolerant charging current, А;
... ... @@ -32,7 +32,7 @@
32 32  
33 33  (% class="box infomessage" %)
34 34  (((
35 -If there is the "Overcurrent" error, the charging relay and discharging relay open.
34 +If there is the "Overcurrent" error, the charging and discharging relay open.
36 36  )))
37 37  
38 38  == 3.6.2 Undervoltage protection ==
... ... @@ -192,12 +192,96 @@
192 192  **If there is the "Battery cover error", the “Critical error” is generated and all relays open.**
193 193  )))
194 194  
195 -== 3.6.7 High humidity protection ==
194 +== 3.6.7 High humidity protection ==
196 196  
196 +The board can protect the battery from high humidity and water.
197 +
198 +To change the protection parameters of the battery from high humidity, select the menu "Protections → High humidity protection":
199 +
200 +
201 +In this section:
202 +
203 +* Enable – a flag to enable the protection;
204 +* Maximum humidty, RH%;
205 +* Tolerant humidty, RH%;
206 +* Delay before setting the error, second;
207 +* Delay before clearing the error, second;
208 +* Lock the error until the device is reset.
209 +
210 +As a result of the operation of the battery protection from high humidity, the "High humidity" error is generated.
211 +
212 +Error generation conditions:
213 +
214 +* the measured humidity is greater than “Maximum humidity” during the “Delay before setting the error” time.
215 +
216 +Conditions for removing the error:
217 +
218 +* the measured humidity is less than the “Tolerant humidity” during the “Delay before clearing the error” time.
219 +
220 +(% class="box infomessage" %)
221 +(((
222 +If there is the "High humidity" error, no action is taken. The error is indicative.
223 +)))
224 +
197 197  == 3.6.8  Water protection ==
198 198  
227 +To change the protection parameters of the battery from water, select the menu "Protections → Water protection":
228 +
229 +
230 +In this section:
231 +
232 +* Enable – a flag to enable the protection;
233 +* Maximum (water) humidty, RH%;
234 +* Tolerant humidity, RH%;
235 +* Delay before setting the error, second;
236 +* Delay before clearing the error, second;
237 +* Lock the error until the device is reset.
238 +
239 +As a result of the operation of the battery protection from water, the "Water" error is generated.
240 +
241 +Error generation conditions:
242 +
243 +* the measured humidity is greater than the “Maximum (water) humidity” value during the “Delay before setting the error” time.
244 +
245 +Conditions for removing the error:
246 +
247 +* the measured humidity is less than the “Tolerant humidity” value during the “Delay before clearing the error” time.
248 +
249 +(% class="box warningmessage" %)
250 +(((
251 +**If there is the “Water” error, the “Critical error” is generated and all relays open.**
252 +)))
253 +
199 199  == 3.6.9 Current sensor error ==
200 200  
256 +The board is implemented to check the current sensor connection circuits. The circuits are checked for breakage and short-circuit to the +5 V supply line.
257 +
258 +To change the test parameters of the current sensor connection circuits, select the menu "Protections → Current sensor error":
259 +
260 +
261 +In this section:
262 +
263 +* Enable – a flag to enable the protection;
264 +* Maximum voltage, V;
265 +* Minimum voltage, V;
266 +* Hysteresis voltage – a hysteresis value to clear the error, V;
267 +* Delay before setting the error, second;
268 +* Delay before clearing the error, second;
269 +* Lock the error until the device is reset.
270 +
271 +If there is an open or short circuit connection of a current sensor, the "Current sensor error" is generated.
272 +
273 +Error generation conditions:
274 +
275 +* the voltage in the signal line or zero level line of the current sensor is greater than the “Maximum voltage” value during the “Delay before setting the error” time;
276 +* the voltage in the signal line or zero level line of the current sensor is less than the “Minimum voltage” value during the “Delay before setting the error” time.
277 +
278 +Conditions for removing the error:
279 +
280 +* the voltage in the signal line or zero level line of the current sensor is in range from (Minimum voltage + Hysteresis voltage) to (Maximum voltage - Hysteresis voltage) during the “Delay before clearing the error” time.
281 +
282 +**If there is the “Current sensor error”, the “Critical error” is generated and all relays open.**
283 +
201 201  == 3.6.10 Short circuit protection ==