... ... @@ -6,9 +6,8 @@
6 6  
7 7  [[Overcurrent protection settings>>image:1732211959984-118.png||data-xwiki-image-style-alignment="center" height="266" width="386"]]
8 8  
9 + In this section:
9 9  
10 -In this section:
11 -
12 12  * Enable – a flag to enable the protection;
13 13  * Maximum charging current, А;
14 14  * Tolerant charging current, А;
... ... @@ -32,7 +32,7 @@
32 32  
33 33  (% class="box infomessage" %)
34 34  (((
35 -If there is the "Overcurrent" error, the charging relay and discharging relay open.
34 +If there is the "Overcurrent" error, the charging and discharging relay open.
36 36  )))
37 37  
38 38  == 3.6.2 Undervoltage protection ==
... ... @@ -128,7 +128,8 @@
128 128  
129 129  (% class="box infomessage" %)
130 130  (((
131 -If there is the "Low CH temperature" error, the charging relay opens. If there is the "Low DCH temperature" error, the discharging relay opens.
130 +If there is the "Low CH temperature" error, the charging relay opens.
131 +If there is the "Low DCH temperature" error, the discharging relay opens.
132 132  )))
133 133  
134 134  == 3.6.5 High temperature protection ==
... ... @@ -137,6 +137,7 @@
137 137  
138 138  To change the battery protection parameters from high temperature, select the menu "Protections → High temperature protection":
139 139  
140 +
140 140  In this section:
141 141  
142 142  * Enable – a flag to enable the protection;
... ... @@ -166,38 +166,467 @@
166 166  
167 167  == 3.6.6 Battery cover protection ==
168 168  
169 -== 3.6.7 High humidity protection ==
170 +To change the protection parameters from opening the battery cover, select the menu "Protections → Battery cover protection":
170 170  
172 +In this section:
173 +
174 +* Enable – a flag to enable the protection;
175 +* Delay before setting the error, second;
176 +* Delay before clearing the error, second;
177 +* Lock the error until the device is reset.
178 +
179 +As a result of the operation of the protection against opening the battery cover, the “Battery cover error” is generated.
180 +
181 +Error generation conditions:
182 +
183 +* there is a signal from the battery cover during the “Delay before setting the error” time.
184 +
185 +Conditions for removing the error:
186 +
187 +* no signal from the battery cover during the “Delay before clearing the error” time.
188 +
189 +(% class="box warningmessage" %)
190 +(((
191 +**If there is the "Battery cover error", the “Critical error” is generated and all relays open.**
192 +)))
193 +
194 +== 3.6.7 High humidity protection ==
195 +
196 +The board can protect the battery from high humidity and water.
197 +
198 +To change the protection parameters of the battery from high humidity, select the menu "Protections → High humidity protection":
199 +
200 +
201 +In this section:
202 +
203 +* Enable – a flag to enable the protection;
204 +* Maximum humidty, RH%;
205 +* Tolerant humidty, RH%;
206 +* Delay before setting the error, second;
207 +* Delay before clearing the error, second;
208 +* Lock the error until the device is reset.
209 +
210 +As a result of the operation of the battery protection from high humidity, the "High humidity" error is generated.
211 +
212 +Error generation conditions:
213 +
214 +* the measured humidity is greater than “Maximum humidity” during the “Delay before setting the error” time.
215 +
216 +Conditions for removing the error:
217 +
218 +* the measured humidity is less than the “Tolerant humidity” during the “Delay before clearing the error” time.
219 +
220 +(% class="box infomessage" %)
221 +(((
222 +If there is the "High humidity" error, no action is taken. The error is indicative.
223 +)))
224 +
171 171  == 3.6.8  Water protection ==
172 172  
227 +To change the protection parameters of the battery from water, select the menu "Protections → Water protection":
228 +
229 +
230 +In this section:
231 +
232 +* Enable – a flag to enable the protection;
233 +* Maximum (water) humidty, RH%;
234 +* Tolerant humidity, RH%;
235 +* Delay before setting the error, second;
236 +* Delay before clearing the error, second;
237 +* Lock the error until the device is reset.
238 +
239 +As a result of the operation of the battery protection from water, the "Water" error is generated.
240 +
241 +Error generation conditions:
242 +
243 +* the measured humidity is greater than the “Maximum (water) humidity” value during the “Delay before setting the error” time.
244 +
245 +Conditions for removing the error:
246 +
247 +* the measured humidity is less than the “Tolerant humidity” value during the “Delay before clearing the error” time.
248 +
249 +(% class="box warningmessage" %)
250 +(((
251 +**If there is the “Water” error, the “Critical error” is generated and all relays open.**
252 +)))
253 +
173 173  == 3.6.9 Current sensor error ==
174 174  
256 +The board is implemented to check the current sensor connection circuits. The circuits are checked for breakage and short-circuit to the +5 V supply line.
257 +
258 +To change the test parameters of the current sensor connection circuits, select the menu "Protections → Current sensor error":
259 +
260 +
261 +In this section:
262 +
263 +* Enable – a flag to enable the protection;
264 +* Maximum voltage, V;
265 +* Minimum voltage, V;
266 +* Hysteresis voltage – a hysteresis value to clear the error, V;
267 +* Delay before setting the error, second;
268 +* Delay before clearing the error, second;
269 +* Lock the error until the device is reset.
270 +
271 +If there is an open or short circuit connection of a current sensor, the "Current sensor error" is generated.
272 +
273 +Error generation conditions:
274 +
275 +* the voltage in the signal line or zero level line of the current sensor is greater than the “Maximum voltage” value during the “Delay before setting the error” time;
276 +* the voltage in the signal line or zero level line of the current sensor is less than the “Minimum voltage” value during the “Delay before setting the error” time.
277 +
278 +Conditions for removing the error:
279 +
280 +* the voltage in the signal line or zero level line of the current sensor is in range from (Minimum voltage + Hysteresis voltage) to (Maximum voltage - Hysteresis voltage) during the “Delay before clearing the error” time.
281 +
282 +(% class="box warningmessage" %)
283 +(((
284 +**If there is the “Current sensor error”, the “Critical error” is generated and all relays open.**
285 +)))
286 +
175 175  == 3.6.10 Short circuit protection ==
176 176  
289 +The BMS implements a protection of power circuits (contactors, power cables) against overheating caused by the flow of high current for a long time.
290 +
291 +To change the protection parameters from short circuit, select the menu "Protections → Short circuit protection":
292 +
293 +
294 +In this section:
295 +
296 +* Level 1, 2, 3 – three protection levels. The following parameters are configured at each level:
297 +** Enable – a flag to enable the protection;
298 +** Maximum current, A;
299 +** Delay before setting the error, second;
300 +* Delay before clearing the error, second;
301 +* Switch off the charging relay on error – a flag to open the charging relay when the "Short circuit" error occurs;
302 +* Switch off the discharging relay on error – a flag to open the discharging relay when the "Short circuit" error occurs;
303 +* Lock the error until the device is reset.
304 +
305 +If there is a short circuit, the "Short circuit" error is generated.
306 +
307 +Error generation conditions:
308 +
309 +* at any of the three protection levels, the current modulo is greater than the “Maximum current” value during the “Delay before setting the error” time.
310 +
311 +Conditions for removing the error:
312 +
313 +* the current modulo is lower than the “Maximum current” values for all three protection levels during the “Delay before setting the error” time.
314 +
315 +(% class="box infomessage" %)
316 +(((
317 +If there is the "Short circuit" error, the charging relay opens (the “Switch off the charging relay on error” flag is set) and the discharging relay opens (the “Switch off the discharging relay on error flag” is set).
318 +)))
319 +
177 177  == 3.6.11 Contactor high temperature protection ==
178 178  
322 +The BMS protects power contactors from overheating. To measure the temperature of the contactor, a thermistor is used, connected to the P13 connector of the board. Configuring of the analog input for temperature measurement is described in section Input signals.
323 +
324 +To change the overheating protection parameters of power contactors, select the menu "Protections → Contactor high temperature protection":
325 +
326 +
327 +In this section:
328 +
329 +* Enable – a flag to enable the protection;
330 +* Maximum temperature, °C;
331 +* Tolerant temperature, °C;
332 +* Delay before setting the error, second;
333 +* Delay before clearing the error, second;
334 +* Switch off the charging relay on error – a flag to open the charging relay when the "Contactor high temperature" error occurs;
335 +* Switch off the discharging relay on error – a flag to open the discharging relay when the "Contactor high temperature" error occurs;
336 +* Lock the error until the device is reset.
337 +
338 +If there is a contactor overheat, the "Contactor high temperature" error is generated.
339 +
340 +Error generation conditions:
341 +
342 +* the contactor temperature is greater than the “Maximum temperature” value during the “Delay before setting the error” time.
343 +
344 +Conditions for removing the error:
345 +
346 +* the contactor temperature is lower than the “Tolerant temperature” value during the “Delay before clearing the error” time.
347 +
348 +(% class="box infomessage" %)
349 +(((
350 +If there is the "Contactor high temperature" error, the charging relay opens (the “Switch off the charging relay on error” flag is set) and the discharging relay opens (the “Switch off the discharging relay on error flag” is set).
351 +)))
352 +
179 179  == 3.6.12 Unallowable charging protection ==
180 180  
355 +The BMS can detect that the battery is charging through the discharging circuit and protectively open the discharging relay to prevent unallowable battery operation.
356 +
357 +To change the parameters of the unallowable charging protection, select the menu "Protections → Unallowable charging protection":
358 +
359 +
360 +In this section:
361 +
362 +* Enable – a flag to enable the protection;
363 +* Delay before setting the error, second;
364 +* Delay before clearing the error, second;
365 +* Lock the error until the device is reset.
366 +
367 +If there is charging the battery through the discharging circuit detected, the "Unallowable charging" error is generated.
368 +
369 +Error generation conditions:
370 +
371 +* the charging relay is open and the battery current is not zero during the “Delay before setting the error” time.
372 +
373 +Conditions for removing the error:
374 +
375 +* the battery current is zero during the “Delay before clearing the error” time.
376 +
377 +(% class="box infomessage" %)
378 +(((
379 +If there is the "Unallowable charging" error, the discharging relay opens.
380 +)))
381 +
181 181  == 3.6.13 Stuck contactor protection ==
182 182  
384 +The BMS Main 2.x protects contactors against sticking.
385 +
386 +To change the protection parameters against sticking, select the menu "Protections → Stuck contactor protection":
387 +
388 +
389 +In this section:
390 +
391 +* Enable – a flag to enable the protection;
392 +* Delay before setting the error, second;
393 +* Delay before clearing the error, second;
394 +* Lock the error until the device is reset;
395 +
396 +If there is a stuck contactor, the “Stuck contactor” error is generated.
397 +
398 +Error generation conditions:
399 +
400 +* charging and discharging contactors are open, but the “Charging current present” or “Discharging current present” signal is set.
401 +
183 183  == 3.6.14 Contactor feedback check ==
184 184  
404 +The BMS Main 2.x can receive feedback signals from contactors and detect discrepancy between the control value and the feedback signal. To enable specific contactor protection, one of the discrete input must be set as corresponding contactor feedback signal (see section Input and output signals).
405 +
406 +To change the contactor feedback check parameters, select the menu "Protections → Contactor feedback check":
407 +
408 +
409 +In this section:
410 +
411 +* Enable – a flag to enable the protection;
412 +* Delay before setting the error, second;
413 +* Delay before clearing the error, second;
414 +* Lock the error until the device is reset;
415 +
416 +If there is a discrepancy at any contactor, the corresponding contactor feedback error is generated. Error generation conditions:
417 +
418 +* discrete output of charging, precharge, discharging, charging/discharging or main contactor not matches its feedback value.
419 +
185 185  == 3.6.15 Charging contactor cycles protection ==
186 186  
422 +The BMS protects the charging contactor against frequent switching.
423 +
424 +To change the protection parameters against high frequency switching of the charging contactor, select the menu "Protections → Charging contactor cycles protection":
425 +
426 +
427 +In this section:
428 +
429 +* Enable – a flag to enable the protection;
430 +* Cycles threshold – a number of cycles in a given period, upon which the “CH contactor cycles error” is generated;
431 +* Period – a time in which the BMS counts switchings of the charging contactor, second;
432 +* Delay before setting the error, second;
433 +* Delay before clearing the error, second;
434 +* Lock the error until the device is reset;
435 +* Cycles – a number of the charging contactor switchings made during battery operation.
436 +
437 +If there is the high switching frequency of the charging contactor, the “CH contactor cycles error” is generated.
438 +
439 +Error generation conditions:
440 +
441 +* the number of switchings of the charging contactor for the “Period” time is greater than or equal to the “Cycles threshold” value. The error is generated with the “Delay before setting the error” delay.
442 +
443 +Conditions for removing the error:
444 +
445 +* the “Delay before clearing the error” time has passed since the error was generated.
446 +
447 +(% class="box infomessage" %)
448 +(((
449 +If there is the "CH contactor cycles error" error, the charging relay opens.
450 +)))
451 +
187 187  == 3.6.16 Discharging contactor cycles protection ==
188 188  
454 +The BMS protects the discharging contactor against frequent switching.
455 +
456 +To change the protection parameters against high frequency switching of the discharging contactor, select the menu "Protections → Discharging contactor cycles protection":
457 +
458 +
459 +In this section:
460 +
461 +* Enable – a flag to enable the protection;
462 +* Cycles threshold – a number of cycles in a given period, upon which the “DCH contactor cycles error” is generated;
463 +* Period – a time in which the BMS counts switchings of the charging contactor, second;
464 +* Delay before setting the error, second;
465 +* Delay before clearing the error, second;
466 +* Lock the error until the device is reset;
467 +* Cycles – a number of the charging contactor switchings made during battery operation.
468 +
469 +If there is the high switching frequency of the discharging contactor, the “DCH contactor cycles error” is generated.
470 +
471 +Error generation conditions:
472 +
473 +* the number of switchings of the discharging contactor for the “Period” time is greater than or equal to the “Cycles threshold” value. The error is generated with the “Delay before setting the error” delay.
474 +
475 +Conditions for removing the error:
476 +
477 +* the “Delay before clearing the error” time has passed since the error was generated.
478 +
479 +(% class="box infomessage" %)
480 +(((
481 +If there is the "DCH contactor cycles error" error, the discharging relay opens.
482 +)))
483 +
189 189  == 3.6.17 Temperature sensor error ==
190 190  
486 +The board is implemented to check the temperature sensors connection circuits. The circuits are checked for breakage and short-circuit.
487 +
488 +To change the protection parameters of the temperature sensors circuits, select the menu "Protections → Temperature sensor error":
489 +
490 +
491 +In this section:
492 +
493 +* Enable – a flag to enable the protection;
494 +* Delay before setting the error, second;
495 +* Delay before clearing the error, second;
496 +* Lock the error until the device is reset.
497 +
498 +If there are no temperature sensors connected to a BMS Logic board or any temperature sensor is shorted, the "No temp. sensors" error and "Temp. sensor is shorted" error are generated respectively. These errors generated and removed with the “Delay before setting the error” and “Delay before clearing the error” delays.
499 +
500 +(% class="box warningmessage" %)
501 +(((
502 +**If there is the “No temp. sensors” or “Temp. sensor is shorted” error, the “Critical error” is generated and all relays open.**
503 +)))
504 +
191 191  == 3.6.18 Logic high temperature protection ==
192 192  
507 +To change the overheating protection parameters of BMS Logic boards, select the menu "Protections → Logic high temperature protection":
508 +
509 +
510 +In this section:
511 +
512 +* Enable – a flag to enable the protection;
513 +* Maximum Logic temperature, °C;
514 +* Tolerant Logic temperature, °C;
515 +* Lock the error until the device is reset.
516 +
517 +As a result of the operation of the protection from high temperatures of BMS Logic boards, the "Logic high temperature" is generated.
518 +
519 +Error generation conditions:
520 +
521 +* a BMS Logic board temperature is higher than the “Maximum Logic temperature” value.
522 +
523 +Conditions for removing the error:
524 +
525 +* a BMS Logic board temperature is less than the “Tolerant Logic temperature” value.
526 +
527 +(% class="box infomessage" %)
528 +(((
529 +**Cell balancing is prohibited for overheated boards.**
530 +)))
531 +
193 193  == 3.6.19 Logic offline protection ==
194 194  
534 +To change the protection parameters from loss of communication with BMS Logic boards, select the menu "Protections → Logic offline protection":
535 +
536 +
537 +In this section:
538 +
539 +* Enable – a flag to enable the protection;
540 +* Lock the error until the device is reset.
541 +
542 +As a result of the protection from loss of communication with BMS Logic boards, the "Logic offline" error is generated.
543 +
544 +Error generation conditions:
545 +
546 +* at least one of the connected BMS Logic boards does not respond to the commands of the BMS Main 2.x board for 10 seconds.
547 +
548 +Conditions for removing the error:
549 +
550 +* all connected BMS Logic boards respond to the commands of the BMS Main 2.x board.
551 +
552 +(% class="box warningmessage" %)
553 +(((
554 +**If there is the "Logic offline" error, the “Critical error” is generated and all relays open.**
555 +)))
556 +
195 195  == 3.6.20 Cell count protection ==
196 196  
559 +To change the protection parameters from the mismatch of the number of cells to the set value, select the menu "Protections → Cell count protection":
560 +
561 +
562 +In this section:
563 +
564 +* Enable – a flag to enable the protection;
565 +* Cell count – a number of cells connected to the BMS;
566 +* Delay before setting the error, second;
567 +* Delay before clearing the error, second;
568 +* Lock the error until the device is reset.
569 +
570 +As a result of the operation of the protection from the mismatch of the number of cells, the "Cell count error" is generated.
571 +
572 +Error generation conditions:
573 +
574 +* the number of cells connected to the BMS is **not equal** to the “Cell count” value during the “Delay before setting the error” time.
575 +
576 +Conditions for removing the error:
577 +
578 +* the number of cells connected to the BMS is **equal** to the “Cell count” value during the “Delay before clearing the error” time.
579 +
580 +(% class="box warningmessage" %)
581 +(((
582 +**If there is the "Cell count error", the “Critical error” is generated and all relays open.**
583 +)))
584 +
197 197  == 3.6.21 Logic count protection ==
198 198  
587 +To change the protection parameters from the mismatch of the number of BMS Logic boards to the set value, select the menu "Protections → Logic count protection":
588 +
589 +
590 +In this section:
591 +
592 +* Enable – a flag to enable the protection;
593 +* Logic count – a number of BMS Logic boards connected to the BMS Main 2.x;
594 +* Fast scan – a flag to scan BMS Logic boards fast (boards with addresses from 1 to “Logic count” are scanned; this mode reduces BMS system startup time);
595 +* Lock the error until the device is reset.
596 +
597 +As a result of the operation of the protection from the mismatch of the number of BMS Logic boards, the "Logic count error" is generated.
598 +
599 +Error generation conditions:
600 +
601 +* the number of BMS Logic boards connected to the BMS Main 2.x is **not equal** to the “Logic count” value.
602 +
603 +Conditions for removing the error:
604 +
605 +* the number of BMS Logic boards connected to the BMS Main is **equal** to the “Logic count” value.
606 +
607 +(% class="box warningmessage" %)
608 +(((
609 +**If there is the "Logic count error", the “Critical error” is generated and all relays open.**
610 +)))
611 +
199 199  == 3.6.22 WDT protection ==
200 200  
614 +If the BMS firmware hangs, the watchdog timer resets the board. The BMS can detect that the board was reset and generates the “WDT reset” error.
615 +
616 +To change the parameters of the watchdog protection, select the menu "Protections → WDT protection":
617 +
618 +
619 +In this section:
620 +
621 +* Enable – a flag to enable the protection;
622 +* Delay before clearing the error, second;
623 +* Lock the error until the device is reset.
624 +
625 +Conditions for removing the error:
626 +
627 +* the “Delay before clearing the error” time has passed from the board startup.
628 +
629 +**If there is the "WDT reset" error, the “Critical error” is generated and all relays open.**
630 +
201 201  == 3.6.23 Insulation monitoring ==
202 202  
203 203  == 3.6.24 Critical error parameters ==