Summary

Details

Page properties
Content
... ... @@ -6,9 +6,8 @@
6 6  
7 7  [[Overcurrent protection settings>>image:1732211959984-118.png||data-xwiki-image-style-alignment="center" height="266" width="386"]]
8 8  
9 + In this section:
9 9  
10 -In this section:
11 -
12 12  * Enable – a flag to enable the protection;
13 13  * Maximum charging current, А;
14 14  * Tolerant charging current, А;
... ... @@ -32,7 +32,7 @@
32 32  
33 33  (% class="box infomessage" %)
34 34  (((
35 -If there is the "Overcurrent" error, the charging relay and discharging relay open.
34 +If there is the "Overcurrent" error, the charging and discharging relay open.
36 36  )))
37 37  
38 38  == 3.6.2 Undervoltage protection ==
... ... @@ -128,7 +128,8 @@
128 128  
129 129  (% class="box infomessage" %)
130 130  (((
131 -If there is the "Low CH temperature" error, the charging relay opens. If there is the "Low DCH temperature" error, the discharging relay opens.
130 +If there is the "Low CH temperature" error, the charging relay opens.
131 +If there is the "Low DCH temperature" error, the discharging relay opens.
132 132  )))
133 133  
134 134  == 3.6.5 High temperature protection ==
... ... @@ -137,6 +137,7 @@
137 137  
138 138  To change the battery protection parameters from high temperature, select the menu "Protections → High temperature protection":
139 139  
140 +
140 140  In this section:
141 141  
142 142  * Enable – a flag to enable the protection;
... ... @@ -166,8 +166,58 @@
166 166  
167 167  == 3.6.6 Battery cover protection ==
168 168  
169 -== 3.6.7 High humidity protection ==
170 +To change the protection parameters from opening the battery cover, select the menu "Protections → Battery cover protection":
170 170  
172 +In this section:
173 +
174 +* Enable – a flag to enable the protection;
175 +* Delay before setting the error, second;
176 +* Delay before clearing the error, second;
177 +* Lock the error until the device is reset.
178 +
179 +As a result of the operation of the protection against opening the battery cover, the “Battery cover error” is generated.
180 +
181 +Error generation conditions:
182 +
183 +* there is a signal from the battery cover during the “Delay before setting the error” time.
184 +
185 +Conditions for removing the error:
186 +
187 +* no signal from the battery cover during the “Delay before clearing the error” time.
188 +
189 +(% class="box warningmessage" %)
190 +(((
191 +**If there is the "Battery cover error", the “Critical error” is generated and all relays open.**
192 +)))
193 +
194 +== 3.6.7 High humidity protection ==
195 +
196 +The board can protect the battery from high humidity and water.
197 +
198 +To change the protection parameters of the battery from high humidity, select the menu "Protections → High humidity protection":
199 +
200 +In this section:
201 +
202 +* Enable – a flag to enable the protection;
203 +* Maximum humidty, RH%;
204 +* Tolerant humidty, RH%;
205 +* Delay before setting the error, second;
206 +* Delay before clearing the error, second;
207 +* Lock the error until the device is reset.
208 +
209 +As a result of the operation of the battery protection from high humidity, the "High humidity" error is generated.
210 +
211 +Error generation conditions:
212 +
213 +* the measured humidity is greater than “Maximum humidity” during the “Delay before setting the error” time.
214 +
215 +Conditions for removing the error:
216 +
217 +* the measured humidity is less than the “Tolerant humidity” during the “Delay before clearing the error” time.
218 +
219 +If there is the "High humidity" error, no action is taken. The error is indicative.
220 +
221 +