Changes for page 3.6 Battery protection

Last modified by Admin on 2025/04/09 12:25

From version 4.11
edited by Admin
on 2024/11/21 18:15
Change comment: There is no comment for this version
To version 4.10
edited by Admin
on 2024/11/21 18:13
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -100,70 +100,9 @@
100 100  
101 101  == 3.6.4 Low temperature protection ==
102 102  
103 -The board implements battery protection from too low temperature.
104 104  
105 -To change the battery protection parameters from low temperature, select the menu "Protections → Low temperature protection":
106 -
107 -
108 -In this section:
109 -
110 -* Enable – a flag to enable the protection;
111 -* Minimum charging temperature, °C;
112 -* Tolerant charging temperature, °C;
113 -* Minimum discharging temperature, °C;
114 -* Tolerant discharging temperature, °C;
115 -* Delay before setting the error, second;
116 -* Delay before clearing the error, second;
117 -* Lock the error until the device is reset.
118 -
119 -As a result of the operation of the battery protection from low temperature, the "Low CH temperature" or “Low DCH temperature” error is generated.
120 -
121 -Error generation conditions:
122 -
123 -* the minimum temperature among all cells of the battery is less than the “Minimum charging (discharging) temperature” value for the “Delay before setting the error” time.
124 -
125 -Conditions for removing the error:
126 -
127 -* the minimum temperature among all cells of the battery is greater than the “Tolerant charging (discharging) temperature” value for the “Delay before clearing the error” time.
128 -
129 -(% class="box infomessage" %)
130 -(((
131 -If there is the "Low CH temperature" error, the charging relay opens. If there is the "Low DCH temperature" error, the discharging relay opens.
132 -)))
133 -
134 134  == 3.6.5 High temperature protection ==
135 135  
136 -The board implements battery protection from too high temperature.
137 -
138 -To change the battery protection parameters from high temperature, select the menu "Protections → High temperature protection":
139 -
140 -In this section:
141 -
142 -* Enable – a flag to enable the protection;
143 -* Maximum charging temperature, °C;
144 -* Tolerant charging temperature, °C;
145 -* Maximum discharging temperature, °C;
146 -* Tolerant discharging temperature, °C;
147 -* Delay before setting the error, second;
148 -* Delay before clearing the error, second;
149 -* Lock the error until the device is reset.
150 -
151 -As a result of the operation of the battery protection from high temperature, the "High CH temperature" or “High DCH temperature” error is generated.
152 -
153 -Error generation conditions:
154 -
155 -* the maximum temperature among all cells of the battery is greater than the “Maximum charging (discharging) temperature” value for the “Delay before setting the error” time.
156 -
157 -Conditions for removing the error:
158 -
159 -* the maximum temperature among all cells of the battery is less than the “Tolerant charging (discharging) temperature” value for the “Delay before clearing the error” time.
160 -
161 -(% class="box infomessage" %)
162 -(((
163 -If there is the "High CH temperature" error, the charging relay opens.
164 -If there is the "High DCH temperature" error, the discharging relay opens.
165 -)))
166 -
167 167  == 3.6.6 Battery cover protection ==
168 168  
169 169  == 3.6.7 High humidity protection ==