101 101  == 3.6.4 Low temperature protection ==
102 102  
103 +The board implements battery protection from too low temperature.
103 103  
105 +To change the battery protection parameters from low temperature, select the menu "Protections → Low temperature protection":
106 +
107 +
108 +In this section:
109 +
110 +* Enable – a flag to enable the protection;
111 +* Minimum charging temperature, °C;
112 +* Tolerant charging temperature, °C;
113 +* Minimum discharging temperature, °C;
114 +* Tolerant discharging temperature, °C;
115 +* Delay before setting the error, second;
116 +* Delay before clearing the error, second;
117 +* Lock the error until the device is reset.
118 +
119 +As a result of the operation of the battery protection from low temperature, the "Low CH temperature" or “Low DCH temperature” error is generated.
120 +
121 +Error generation conditions:
122 +
123 +* the minimum temperature among all cells of the battery is less than the “Minimum charging (discharging) temperature” value for the “Delay before setting the error” time.
124 +
125 +Conditions for removing the error:
126 +
127 +* the minimum temperature among all cells of the battery is greater than the “Tolerant charging (discharging) temperature” value for the “Delay before clearing the error” time.
128 +
129 +(% class="box infomessage" %)
130 +(((
131 +If there is the "Low CH temperature" error, the charging relay opens.
132 +If there is the "Low DCH temperature" error, the discharging relay opens.
133 +)))
134 +
104 104  == 3.6.5 High temperature protection ==
105 105  
137 +The board implements battery protection from too high temperature.
138 +
139 +To change the battery protection parameters from high temperature, select the menu "Protections → High temperature protection":
140 +
141 +
142 +In this section:
143 +
144 +* Enable – a flag to enable the protection;
145 +* Maximum charging temperature, °C;
146 +* Tolerant charging temperature, °C;
147 +* Maximum discharging temperature, °C;
148 +* Tolerant discharging temperature, °C;
149 +* Delay before setting the error, second;
150 +* Delay before clearing the error, second;
151 +* Lock the error until the device is reset.
152 +
153 +As a result of the operation of the battery protection from high temperature, the "High CH temperature" or “High DCH temperature” error is generated.
154 +
155 +Error generation conditions:
156 +
157 +* the maximum temperature among all cells of the battery is greater than the “Maximum charging (discharging) temperature” value for the “Delay before setting the error” time.
158 +
159 +Conditions for removing the error:
160 +
161 +* the maximum temperature among all cells of the battery is less than the “Tolerant charging (discharging) temperature” value for the “Delay before clearing the error” time.
162 +
163 +(% class="box infomessage" %)
164 +(((
165 +If there is the "High CH temperature" error, the charging relay opens.
166 +If there is the "High DCH temperature" error, the discharging relay opens.
167 +)))
168 +
106 106  == 3.6.6 Battery cover protection ==
107 107  
171 +To change the protection parameters from opening the battery cover, select the menu "Protections → Battery cover protection":
172 +
173 +In this section:
174 +
175 +* Enable – a flag to enable the protection;
176 +* Delay before setting the error, second;
177 +* Delay before clearing the error, second;
178 +* Lock the error until the device is reset.
179 +
180 +As a result of the operation of the protection against opening the battery cover, the “Battery cover error” is generated.
181 +
182 +Error generation conditions:
183 +
184 +* there is a signal from the battery cover during the “Delay before setting the error” time.
185 +
186 +Conditions for removing the error:
187 +
188 +* no signal from the battery cover during the “Delay before clearing the error” time.
189 +
190 +(% class="box warningmessage" %)
191 +(((
192 +**If there is the "Battery cover error", the “Critical error” is generated and all relays open.**
193 +)))