1 1  The BMS Main 2.x board continuously monitors the state of the cells, BMS Logic boards, the external environment and, when detecting abnormalities, protects the battery and system components from damage.
2 2  
3 -== 3.6.1 Overcurrent protection ==
9 +=== Overcurrent protection ===
4 4  
5 5  To change the current protection of the battery, select the menu "Protections → Overcurrent protection":
6 6  
... ... @@ -34,7 +34,7 @@
34 34  If there is the "Overcurrent" error, the **charging **and **discharging **relay open.
35 35  )))
36 36  
37 -== 3.6.2 Undervoltage protection ==
43 +=== Undervoltage protection ===
38 38  
39 39  The board implements battery protection from too low or too high voltage on the cells.
40 40  
... ... @@ -66,7 +66,7 @@
66 66  If there is the "Undervoltage" error, the **discharging **relay opens.
67 67  )))
68 68  
69 -== 3.6.3 Overvoltage protection ==
75 +=== Overvoltage protection ===
70 70  
71 71  To change the battery protection parameters from high voltage on the cells, select the menu "Protections → Overvoltage protection":
72 72  
... ... @@ -97,7 +97,7 @@
97 97  If there is the "Overvoltage" error, the **charging **relay and **discharging **relay opens (if the “Switch off the discharging relay on error” flag is set).
98 98  )))
99 99  
100 -== 3.6.4 Low temperature protection ==
106 +=== Low temperature protection ===
101 101  
102 102  The board implements battery protection from too low temperature.
103 103  
... ... @@ -132,7 +132,7 @@
132 132  If there is the "Low DCH temperature" error, the **discharging **relay opens.
133 133  )))
134 134  
135 -== 3.6.5 High temperature protection ==
141 +=== High temperature protection ===
136 136  
137 137  The board implements battery protection from too high temperature.
138 138  
... ... @@ -167,7 +167,7 @@
167 167  If there is the "High DCH temperature" error, the **discharging **relay opens.
168 168  )))
169 169  
170 -== 3.6.6 Battery cover protection ==
176 +=== Battery cover protection ===
171 171  
172 172  To change the protection parameters from opening the battery cover, select the menu "Protections → Battery cover protection":
173 173  
... ... @@ -195,7 +195,7 @@
195 195  If there is the "Battery cover error", the **“Critical error” **is generated and **all relays open.**
196 196  )))
197 197  
198 -== 3.6.7 High humidity protection ==
204 +=== High humidity protection ===
199 199  
200 200  The board can protect the battery from high humidity and water.
201 201  
... ... @@ -227,7 +227,7 @@
227 227  If there is the "High humidity" error, no action is taken. The error is indicative.
228 228  )))
229 229  
230 -== 3.6.8  Water protection ==
236 +=== Water protection ===
231 231  
232 232  To change the protection parameters of the battery from water, select the menu "Protections → Water protection":
233 233  
... ... @@ -257,7 +257,7 @@
257 257  If there is the “Water” error,** **the **“Critical error”** is generated and **all relays open.**
258 258  )))
259 259  
260 -== 3.6.9 Current sensor error ==
266 +=== Current sensor error ===
261 261  
262 262  The board is implemented to check the current sensor connection circuits. The circuits are checked for breakage and short-circuit to the +5 V supply line.
263 263  
... ... @@ -291,7 +291,7 @@
291 291  If there is the “Current sensor error”, the **“Critical error” **is generated and **all relays open.**
292 292  )))
293 293  
294 -== 3.6.10 Short circuit protection ==
300 +=== Short circuit protection ===
295 295  
296 296  The BMS implements a protection of power circuits (contactors, power cables) against overheating caused by the flow of high current for a long time.
297 297  
... ... @@ -325,7 +325,7 @@
325 325  If there is the "Short circuit" error, the **charging **relay opens (the “Switch off the charging relay on error” flag is set) and the **discharging **relay opens (the “Switch off the discharging relay on error flag” is set).
326 326  )))
327 327  
328 -== 3.6.11 Contactor high temperature protection ==
334 +=== Contactor high temperature protection ===
329 329  
330 330  The BMS protects power contactors from overheating. To measure the temperature of the contactor, a thermistor is used, connected to the P13 connector of the board. Configuring of the analog input for temperature measurement is described in section Input signals.
331 331  
... ... @@ -359,7 +359,7 @@
359 359  If there is the "Contactor high temperature" error, the **charging **relay opens (the “Switch off the charging relay on error” flag is set) and the **discharging **relay opens (the “Switch off the discharging relay on error flag” is set).
360 360  )))
361 361  
362 -== 3.6.12 Unallowable charging protection ==
368 +=== Unallowable charging protection ===
363 363  
364 364  The BMS can detect that the battery is charging through the discharging circuit and protectively open the discharging relay to prevent unallowable battery operation.
365 365  
... ... @@ -389,7 +389,7 @@
389 389  If there is the "Unallowable charging" error, the **discharging **relay opens.
390 390  )))
391 391  
392 -== 3.6.13 Stuck contactor protection ==
398 +=== Stuck contactor protection ===
393 393  
394 394  The BMS Main 2.x protects contactors against sticking.
395 395  
... ... @@ -415,9 +415,9 @@
415 415  If there is the “Stuck contactor error”, the **“Critical error” **is generated and **all relays open.**
416 416  )))
417 417  
418 -== 3.6.14 Contactor feedback check ==
424 +=== Contactor feedback check ===
419 419  
420 -The BMS Main 2.x can receive feedback signals from contactors and detect discrepancy between the control value and the feedback signal. To enable specific contactor protection, one of the discrete input must be set as corresponding contactor feedback signal (see [[3.3 Input and output signals>>path:/bin/view/drafts/BMS%20Main%202.1/3.%20Configuration/3.3%20Input%20and%20output%20signals/]]).
426 +The BMS Main 2.x can receive feedback signals from contactors and detect discrepancy between the control value and the feedback signal. To enable specific contactor protection, one of the discrete input must be set as corresponding contactor feedback signal (see [[Input and output signals>>doc:drafts.BMS Main 2\.1.3\. Configuration.3\.3 Input and output signals.WebHome]]).
421 421  
422 422  To change the contactor feedback check parameters, select the menu "Protections → Contactor feedback check":
423 423  
... ... @@ -439,7 +439,7 @@
439 439  If there is the contactor feedback error, the **“Critical error” **is generated and **all relays open.**
440 440  )))
441 441  
442 -== 3.6.15 Charging contactor cycles protection ==
448 +=== Charging contactor cycles protection ===
443 443  
444 444  The BMS protects the charging contactor against frequent switching.
445 445  
... ... @@ -472,7 +472,7 @@
472 472  If there is the "CH contactor cycles error" error, the **charging **relay opens.
473 473  )))
474 474  
475 -== 3.6.16 Discharging contactor cycles protection ==
481 +=== Discharging contactor cycles protection ===
476 476  
477 477  The BMS protects the discharging contactor against frequent switching.
478 478  
... ... @@ -505,7 +505,7 @@
505 505  If there is the "DCH contactor cycles error" error, the **discharging **relay opens.
506 506  )))
507 507  
508 -== 3.6.17 Temperature sensor error ==
514 +=== Temperature sensor error ===
509 509  
510 510  The board is implemented to check the temperature sensors connection circuits. The circuits are checked for breakage and short-circuit.
511 511  
... ... @@ -527,7 +527,7 @@
527 527  If there is the “No temp. sensors” or “Temp. sensor is shorted” error, the **“Critical error” **is generated and **all relays open.**
528 528  )))
529 529  
530 -== 3.6.18 Logic high temperature protection ==
536 +=== Logic high temperature protection ===
531 531  
532 532  To change the overheating protection parameters of BMS Logic boards, select the menu "Protections → Logic high temperature protection":
533 533  
... ... @@ -555,7 +555,7 @@
555 555  Cell balancing is prohibited for overheated boards.
556 556  )))
557 557  
558 -== 3.6.19 Logic offline protection ==
564 +=== Logic offline protection ===
559 559  
560 560  To change the protection parameters from loss of communication with BMS Logic boards, select the menu "Protections → Logic offline protection":
561 561  
... ... @@ -581,7 +581,7 @@
581 581  If there is the "Logic offline" error, the **“Critical error”** is generated and **all relays open.**
582 582  )))
583 583  
584 -== 3.6.20 Cell count protection ==
590 +=== Cell count protection ===
585 585  
586 586  To change the protection parameters from the mismatch of the number of cells to the set value, select the menu "Protections → Cell count protection":
587 587  
... ... @@ -610,7 +610,7 @@
610 610  If there is the "Cell count error",** **the **“Critical error”** is generated and **all relays open.**
611 611  )))
612 612  
613 -== 3.6.21 Logic count protection ==
619 +=== Logic count protection ===
614 614  
615 615  To change the protection parameters from the mismatch of the number of BMS Logic boards to the set value, select the menu "Protections → Logic count protection":
616 616  
... ... @@ -638,7 +638,7 @@
638 638  If there is the "Logic count error", the **“Critical error” **is generated and **all relays open.**
639 639  )))
640 640  
641 -== 3.6.22 WDT protection ==
647 +=== WDT protection ===
642 642  
643 643  If the BMS firmware hangs, the watchdog timer resets the board. The BMS can detect that the board was reset and generates the “WDT reset” error.
644 644  
... ... @@ -661,7 +661,7 @@
661 661  If there is the "WDT reset" error, the **“Critical error”** is generated and** all relays open.**
662 662  )))
663 663  
664 -== 3.6.23 Insulation monitoring ==
670 +=== Insulation monitoring ===
665 665  
666 666  BMS Main 2.x can detect a signal from an external insulation monitoring device (such as Bender IR155) to monitor the insulation quality.
667 667  
... ... @@ -683,7 +683,7 @@
683 683  If there is the "Insulation monitoring" error, the **“Critical error”** is generated and** all relays open.**
684 684  )))
685 685  
686 -== 3.6.24 Critical error parameters ==
692 +=== Critical error parameters ===
687 687  
688 688  To change the critical error parameters, select the menu "Protections → Critical error parameters":
689 689  
... ... @@ -722,7 +722,7 @@
722 722  **If there is the “Critical error”, all relays open.**
723 723  )))
724 724  
725 -== 3.6.25 General error parameters ==
731 +=== General error parameters ===
726 726  
727 727  To change the general error parameters, select the menu "Protections → General error parameters":
728 728  
... ... @@ -745,7 +745,7 @@
745 745  The "General error" is //indicative //and can be linked to any discrete output of the board.
746 746  )))
747 747  
748 -== 3.6.26 Low SOC signal ==
754 +=== Low SOC signal ===
749 749  
750 750  To change the parameters of the generation a signal about low battery level, select the menu "Protections → Low SOC signal":
751 751  
... ... @@ -773,7 +773,7 @@
773 773  The "Low SOC signal" is //indicative //and can be linked to any discrete output of the board.
774 774  )))
775 775  
776 -== 3.6.27 High charging current signal ==
782 +=== High charging current signal ===
777 777  
778 778  To change the parameters of the generation high-current signal, select the menu "Protections → High charging current signal":
779 779  
... ... @@ -801,7 +801,7 @@
801 801  The "High charging current" signal is //indicative //and can be linked to any discrete output of the board.
802 802  )))
803 803  
804 -== 3.6.28 Heater control ==
810 +=== Heater control ===
805 805  
806 806  To change the parameters of the heater control algorithm, select the menu "Protections → Heater control":
807 807  
... ... @@ -832,7 +832,7 @@
832 832  If there is the "Heater" signal, the **heater **relay closes and/or a signal is output to the corresponded digital output.
833 833  )))
834 834  
835 -== 3.6.29 Heater (AUX) control ==
841 +=== Heater (AUX) control ===
836 836  
837 837  To change the parameters of the auxiliary heater control algorithm, select the menu "Protections → Heater (AUX) control":
838 838  
... ... @@ -863,7 +863,7 @@
863 863  If there is the "Heater (AUX)" signal, the **auxiliary heater **relay closes and/or a signal is output to the corresponded digital output.
864 864  )))
865 865  
866 -== 3.6.30 Cooler control ==
872 +=== Cooler control ===
867 867  
868 868  To change the parameters of the cooler control algorithm, select the menu "Protections → Cooler control":
869 869  
... ... @@ -894,7 +894,7 @@
894 894  If there is the "Cooler" signal, the **cooler **relay closes and/or a signal is output to the corresponded digital output.
895 895  )))
896 896  
897 -== 3.6.31 Fault simulation ==
903 +=== Fault simulation ===
898 898  
899 899  The board provides the ability to manually generate error flags bypassing the protection algorithms. This functionality is intended for commissioning.
900 900