34 34  If there is the "Overcurrent" error, the **charging **and **discharging **relay open.
35 35  )))
36 36  
37 -== 3.6.2 Undervoltage protection ==
37 +== 3.6.2 Undervoltage protection ==
38 38  
39 39  The board implements battery protection from too low or too high voltage on the cells.
40 40  
... ... @@ -66,7 +66,7 @@
66 66  If there is the "Undervoltage" error, the **discharging **relay opens.
67 67  )))
68 68  
69 -3.6.3 Overvoltage protection
69 +== 3.6.3 Overvoltage protection ==
70 70  
71 71  To change the battery protection parameters from high voltage on the cells, select the menu "Protections → Overvoltage protection":
72 72  
... ... @@ -434,6 +434,10 @@
434 434  
435 435  * discrete output of charging, precharge, discharging, charging/discharging or main contactor not matches its feedback value.
436 436  
437 +(% class="box warningmessage" %)
438 +(((
439 +If there is the contactor feedback error, the **“Critical error” **is generated and **all relays open.**
440 +)))
437 437  
438 438  == 3.6.15 Charging contactor cycles protection ==
439 439  
... ... @@ -654,7 +654,7 @@
654 654  
655 655  (% class="box warningmessage" %)
656 656  (((
657 -If there is the "WDT reset" error, the **“Critical error”** is generated and** all relays open.**
661 +If there is the "WDT reset" error, the **“Critical error”** is generated and** all relays open.**
658 658  )))
659 659  
660 660  == 3.6.23 Insulation monitoring ==
... ... @@ -674,6 +674,11 @@
674 674  
675 675  Error is set if corresponding discrete input is set up and it received logical zero.
676 676  
681 +(% class="box warningmessage" %)
682 +(((
683 +If there is the "Insulation monitoring" error, the **“Critical error”** is generated and** all relays open.**
684 +)))
685 +
677 677  == 3.6.24 Critical error parameters ==
678 678  
679 679  To change the critical error parameters, select the menu "Protections → Critical error parameters":
... ... @@ -698,10 +698,13 @@
698 698  * “No temp. sensors”;
699 699  * “Temp. sensor is shorted”;
700 700  * “Current sensor error”;
710 +* "Stuck contactor";
711 +* "Contactor feedback";
701 701  * “Shunt offline”;
702 702  * “Shunt error”;
703 703  * “Settings error”;
704 -* “WDT reset”.
715 +* “WDT reset”
716 +* "Insulation monitoring".
705 705  
706 706  The “Critical error” is cleared if there are no errors from the list above during the “Delay before clearing the error” time.
707 707