... ... @@ -434,6 +434,10 @@
434 434  
435 435  * discrete output of charging, precharge, discharging, charging/discharging or main contactor not matches its feedback value.
436 436  
437 +(% class="box warningmessage" %)
438 +(((
439 +If there is the contactor feedback error, the **“Critical error” **is generated and **all relays open.**
440 +)))
437 437  
438 438  == 3.6.15 Charging contactor cycles protection ==
439 439  
... ... @@ -674,6 +674,11 @@
674 674  
675 675  Error is set if corresponding discrete input is set up and it received logical zero.
676 676  
681 +(% class="box warningmessage" %)
682 +(((
683 +If there is the "Insulation monitoring" error, the **“Critical error”** is generated and** all relays open.**
684 +)))
685 +
677 677  == 3.6.24 Critical error parameters ==
678 678  
679 679  To change the critical error parameters, select the menu "Protections → Critical error parameters":
... ... @@ -698,10 +698,12 @@
698 698  * “No temp. sensors”;
699 699  * “Temp. sensor is shorted”;
700 700  * “Current sensor error”;
710 +* "
701 701  * “Shunt offline”;
702 702  * “Shunt error”;
703 703  * “Settings error”;
704 -* “WDT reset”.
714 +* “WDT reset”
715 +* "Insulation monitoring".
705 705  