Changes for page 3.6 Battery protection
Last modified by Admin on 2025/04/09 12:25
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -434,6 +434,10 @@ 434 434 435 435 * discrete output of charging, precharge, discharging, charging/discharging or main contactor not matches its feedback value. 436 436 437 +(% class="box warningmessage" %) 438 +((( 439 +If there is the contactor feedback error, the **“Critical error” **is generated and **all relays open.** 440 +))) 437 437 438 438 == 3.6.15 Charging contactor cycles protection == 439 439 ... ... @@ -674,6 +674,11 @@ 674 674 675 675 Error is set if corresponding discrete input is set up and it received logical zero. 676 676 681 +(% class="box warningmessage" %) 682 +((( 683 +If there is the "Insulation monitoring" error, the **“Critical error”** is generated and** all relays open.** 684 +))) 685 + 677 677 == 3.6.24 Critical error parameters == 678 678 679 679 To change the critical error parameters, select the menu "Protections → Critical error parameters": ... ... @@ -698,10 +698,12 @@ 698 698 * “No temp. sensors”; 699 699 * “Temp. sensor is shorted”; 700 700 * “Current sensor error”; 710 +* " 701 701 * “Shunt offline”; 702 702 * “Shunt error”; 703 703 * “Settings error”; 704 -* “WDT reset”. 714 +* “WDT reset” 715 +* "Insulation monitoring". 705 705 706 706 The “Critical error” is cleared if there are no errors from the list above during the “Delay before clearing the error” time. 707 707