... ... @@ -63,7 +63,7 @@
63 63  
64 64  (% class="box infomessage" %)
65 65  (((
66 -If there is the "Undervoltage" error, the **discharging **relay opens.
66 +If there is the "Undervoltage" error, the discharging relay opens.
67 67  )))
68 68  
69 69  3.6.3 Overvoltage protection
... ... @@ -94,7 +94,7 @@
94 94  
95 95  (% class="box infomessage" %)
96 96  (((
97 -If there is the "Overvoltage" error, the **charging **relay and **discharging **relay opens (if the “Switch off the discharging relay on error” flag is set).
97 +If there is the "Overvoltage" error, the charging relay and discharging relay opens (if the “Switch off the discharging relay on error” flag is set).
98 98  )))
99 99  
100 100  == 3.6.4 Low temperature protection ==
... ... @@ -128,8 +128,8 @@
128 128  
129 129  (% class="box infomessage" %)
130 130  (((
131 -If there is the "Low CH temperature" error, the **charging **relay opens.
132 -If there is the "Low DCH temperature" error, the **discharging **relay opens.
131 +If there is the "Low CH temperature" error, the charging relay opens.
132 +If there is the "Low DCH temperature" error, the discharging relay opens.
133 133  )))
134 134  
135 135  == 3.6.5 High temperature protection ==
... ... @@ -163,8 +163,8 @@
163 163  
164 164  (% class="box infomessage" %)
165 165  (((
166 -If there is the "High CH temperature" error, the **charging **relay opens.
167 -If there is the "High DCH temperature" error, the **discharging **relay opens.
166 +If there is the "High CH temperature" error, the charging relay opens.
167 +If there is the "High DCH temperature" error, the discharging relay opens.
168 168  )))
169 169  
170 170  == 3.6.6 Battery cover protection ==
... ... @@ -192,7 +192,7 @@
192 192  
193 193  (% class="box warningmessage" %)
194 194  (((
195 -If there is the "Battery cover error", the **“Critical error” **is generated and **all relays open.**
195 +If there is the "Battery cover error", **the “Critical error” is generated and all relays open.**
196 196  )))
197 197  
198 198  == 3.6.7 High humidity protection ==
... ... @@ -254,7 +254,7 @@
254 254  
255 255  (% class="box warningmessage" %)
256 256  (((
257 -If there is the “Water” error,** **the **“Critical error”** is generated and **all relays open.**
257 +If there is the “Water” error,** the “Critical error” is generated and all relays open.**
258 258  )))
259 259  
260 260  == 3.6.9 Current sensor error ==
... ... @@ -288,7 +288,7 @@
288 288  
289 289  (% class="box warningmessage" %)
290 290  (((
291 -If there is the “Current sensor error”, the **“Critical error” **is generated and **all relays open.**
291 +If there is the “Current sensor error”, **the “Critical error” is generated and all relays open.**
292 292  )))
293 293  
294 294  == 3.6.10 Short circuit protection ==
... ... @@ -322,7 +322,7 @@
322 322  
323 323  (% class="box infomessage" %)
324 324  (((
325 -If there is the "Short circuit" error, the **charging **relay opens (the “Switch off the charging relay on error” flag is set) and the **discharging **relay opens (the “Switch off the discharging relay on error flag” is set).
325 +If there is the "Short circuit" error, the charging relay opens (the “Switch off the charging relay on error” flag is set) and the discharging relay opens (the “Switch off the discharging relay on error flag” is set).
326 326  )))
327 327  
328 328  == 3.6.11 Contactor high temperature protection ==
... ... @@ -356,7 +356,7 @@
356 356  
357 357  (% class="box infomessage" %)
358 358  (((
359 -If there is the "Contactor high temperature" error, the **charging **relay opens (the “Switch off the charging relay on error” flag is set) and the **discharging **relay opens (the “Switch off the discharging relay on error flag” is set).
359 +If there is the "Contactor high temperature" error, the charging relay opens (the “Switch off the charging relay on error” flag is set) and the discharging relay opens (the “Switch off the discharging relay on error flag” is set).
360 360  )))
361 361  
362 362  == 3.6.12 Unallowable charging protection ==
... ... @@ -386,7 +386,7 @@
386 386  
387 387  (% class="box infomessage" %)
388 388  (((
389 -If there is the "Unallowable charging" error, the **discharging **relay opens.
389 +If there is the "Unallowable charging" error, the discharging relay opens.
390 390  )))
391 391  
392 392  == 3.6.13 Stuck contactor protection ==
... ... @@ -410,7 +410,6 @@
410 410  
411 411  * charging and discharging contactors are open, but the “Charging current present” or “Discharging current present” signal is set.
412 412  
413 -
414 414  == 3.6.14 Contactor feedback check ==
415 415  
416 416  The BMS Main 2.x can receive feedback signals from contactors and detect discrepancy between the control value and the feedback signal. To enable specific contactor protection, one of the discrete input must be set as corresponding contactor feedback signal (see section Input and output signals).
... ... @@ -430,7 +430,6 @@
430 430  
431 431  * discrete output of charging, precharge, discharging, charging/discharging or main contactor not matches its feedback value.
432 432  
433 -
434 434  == 3.6.15 Charging contactor cycles protection ==
435 435  
436 436  The BMS protects the charging contactor against frequent switching.
... ... @@ -461,7 +461,7 @@
461 461  
462 462  (% class="box infomessage" %)
463 463  (((
464 -If there is the "CH contactor cycles error" error, the **charging **relay opens.
462 +If there is the "CH contactor cycles error" error, the charging relay opens.
465 465  )))
466 466  
467 467  == 3.6.16 Discharging contactor cycles protection ==
... ... @@ -494,7 +494,7 @@
494 494  
495 495  (% class="box infomessage" %)
496 496  (((
497 -If there is the "DCH contactor cycles error" error, the **discharging **relay opens.
495 +If there is the "DCH contactor cycles error" error, the discharging relay opens.
498 498  )))
499 499  
500 500  == 3.6.17 Temperature sensor error ==
... ... @@ -516,7 +516,7 @@
516 516  
517 517  (% class="box warningmessage" %)
518 518  (((
519 -If there is the “No temp. sensors” or “Temp. sensor is shorted” error, the **“Critical error” **is generated and **all relays open.**
517 +If there is the “No temp. sensors” or “Temp. sensor is shorted” error, **the “Critical error” is generated and all relays open.**
520 520  )))
521 521  
522 522  == 3.6.18 Logic high temperature protection ==
... ... @@ -570,7 +570,7 @@
570 570  
571 571  (% class="box warningmessage" %)
572 572  (((
573 -If there is the "Logic offline" error, the **“Critical error”** is generated and **all relays open.**
571 +If there is the "Logic offline" error, **the “Critical error” is generated and all relays open.**
574 574  )))
575 575  
576 576  == 3.6.20 Cell count protection ==
... ... @@ -599,7 +599,7 @@
599 599  
600 600  (% class="box warningmessage" %)
601 601  (((
602 -If there is the "Cell count error",** **the **“Critical error”** is generated and **all relays open.**
600 +If there is the "Cell count error",** the “Critical error” is generated and all relays open.**
603 603  )))
604 604  
605 605  == 3.6.21 Logic count protection ==
... ... @@ -627,7 +627,7 @@
627 627  
628 628  (% class="box warningmessage" %)
629 629  (((
630 -If there is the "Logic count error", the **“Critical error” **is generated and **all relays open.**
628 +If there is the "Logic count error", **the “Critical error” is generated and all relays open.**
631 631  )))
632 632  
633 633  == 3.6.22 WDT protection ==
... ... @@ -650,7 +650,7 @@
650 650  
651 651  (% class="box warningmessage" %)
652 652  (((
653 -If there is the "WDT reset" error, the **“Critical error”** is generated and** all relays open.**
651 +If there is the "WDT reset" error, **the “Critical error” is generated and all relays open.**
654 654  )))
655 655  
656 656  == 3.6.23 Insulation monitoring ==
... ... @@ -724,10 +724,7 @@
724 724  
725 725  The “General error” is cleared if there are no errors from selected list during the “Delay before clearing the error” time.
726 726  
727 -(% class="box infomessage" %)
728 -(((
729 729  The "General error" is //indicative //and can be linked to any discrete output of the board.
730 -)))
731 731  
732 732  == 3.6.26 Low SOC signal ==
733 733  
... ... @@ -752,10 +752,7 @@
752 752  
753 753  * the battery SOC is greater than the “Tolerant SOC” during the “Delay before clearing the signal” time.
754 754  
755 -(% class="box infomessage" %)
756 -(((
757 757  The "Low SOC signal" is //indicative //and can be linked to any discrete output of the board.
758 -)))
759 759  
760 760  == 3.6.27 High charging current signal ==
761 761  
... ... @@ -780,10 +780,7 @@
780 780  
781 781  * the measured current is less than the “Tolerant charging current” value during the “Delay before clearing the signal” time.
782 782  
783 -(% class="box infomessage" %)
784 -(((
785 785  The "High charging current" signal is //indicative //and can be linked to any discrete output of the board.
786 -)))
787 787  
788 788  == 3.6.28 Heater control ==
789 789  
... ... @@ -813,7 +813,7 @@
813 813  
814 814  (% class="box infomessage" %)
815 815  (((
816 -If there is the "Heater" signal, the **heater **relay closes and/or a signal is output to the corresponded digital output.
805 +If there is the "Heater" signal, the heater relay closes and/or a signal is output to the corresponded digital output.
817 817  )))
818 818  
819 819  == 3.6.29 Heater (AUX) control ==
... ... @@ -844,7 +844,7 @@
844 844  
845 845  (% class="box infomessage" %)
846 846  (((
847 -If there is the "Heater (AUX)" signal, the **auxiliary heater **relay closes and/or a signal is output to the corresponded digital output.
836 +If there is the "Heater (AUX)" signal, the auxiliary heater relay closes and/or a signal is output to the corresponded digital output.