Changes for page 3.6 Battery protection

Last modified by Admin on 2025/04/09 12:25

From version 33.5
edited by Admin
on 2024/11/21 19:00
Change comment: There is no comment for this version
To version 36.1
edited by Admin
on 2024/11/28 16:32
Change comment: There is no comment for this version

Summary

Details

Page properties
Parent
... ... @@ -1,1 +1,1 @@
1 -drafts.bms-main-2-1.configuration.WebHome
1 +drafts.bms-main-2.configuration.WebHome
Content
... ... @@ -4,7 +4,7 @@
4 4  
5 5  To change the current protection of the battery, select the menu "Protections → Overcurrent protection":
6 6  
7 -[[Overcurrent protection settings>>image:1732211959984-118.png||data-xwiki-image-style-alignment="center" height="266" width="386"]]
7 +[[image:1732211959984-118.png||data-xwiki-image-style-alignment="center" height="266" width="386"]]
8 8  
9 9   In this section:
10 10  
... ... @@ -34,13 +34,13 @@
34 34  If there is the "Overcurrent" error, the **charging **and **discharging **relay open.
35 35  )))
36 36  
37 -== 3.6.2 Undervoltage protection ==
37 +== 3.6.2 Undervoltage protection ==
38 38  
39 39  The board implements battery protection from too low or too high voltage on the cells.
40 40  
41 41  To change the battery protection parameters from low voltage on the cells, select the menu "Protections → Undervoltage protection":
42 42  
43 -[[Undervoltage protection settings>>image:1732212212350-294.png||data-xwiki-image-style-alignment="center" height="207" width="359"]]
43 +[[image:1732212212350-294.png||data-xwiki-image-style-alignment="center" height="207" width="359"]]
44 44  
45 45   In this section:
46 46  
... ... @@ -66,11 +66,11 @@
66 66  If there is the "Undervoltage" error, the **discharging **relay opens.
67 67  )))
68 68  
69 -3.6.3 Overvoltage protection
69 +== 3.6.3 Overvoltage protection ==
70 70  
71 71  To change the battery protection parameters from high voltage on the cells, select the menu "Protections → Overvoltage protection":
72 72  
73 -[[Overvoltage protection settings>>image:1732212357972-295.png||data-xwiki-image-style-alignment="center" height="218" width="338"]]
73 +[[image:1732212357972-295.png||data-xwiki-image-style-alignment="center" height="218" width="338"]]
74 74  
75 75  In this section:
76 76  
... ... @@ -103,7 +103,7 @@
103 103  
104 104  To change the battery protection parameters from low temperature, select the menu "Protections → Low temperature protection":
105 105  
106 -[[Low temperature protection settings>>image:1732213953083-955.png||data-xwiki-image-style-alignment="center" height="237" width="338"]]
106 +[[image:1732213953083-955.png||data-xwiki-image-style-alignment="center" height="237" width="338"]]
107 107  
108 108  In this section:
109 109  
... ... @@ -138,7 +138,7 @@
138 138  
139 139  To change the battery protection parameters from high temperature, select the menu "Protections → High temperature protection":
140 140  
141 -[[High temperature protection settings>>image:1732213990755-759.png||data-xwiki-image-style-alignment="center" height="258" width="370"]]
141 +[[image:1732213990755-759.png||data-xwiki-image-style-alignment="center" height="258" width="370"]]
142 142  
143 143  In this section:
144 144  
... ... @@ -171,7 +171,7 @@
171 171  
172 172  To change the protection parameters from opening the battery cover, select the menu "Protections → Battery cover protection":
173 173  
174 -[[Battery cover protection settings>>image:1732214030014-281.png||data-xwiki-image-style-alignment="center" height="155" width="334"]]
174 +[[image:1732214030014-281.png||data-xwiki-image-style-alignment="center" height="155" width="334"]]
175 175  
176 176  In this section:
177 177  
... ... @@ -201,7 +201,7 @@
201 201  
202 202  To change the protection parameters of the battery from high humidity, select the menu "Protections → High humidity protection":
203 203  
204 -[[High humidity protection settings>>image:1732214076060-358.png||data-xwiki-image-style-alignment="center" height="185" width="321"]]
204 +[[image:1732214076060-358.png||data-xwiki-image-style-alignment="center" height="185" width="321"]]
205 205  
206 206  In this section:
207 207  
... ... @@ -231,7 +231,7 @@
231 231  
232 232  To change the protection parameters of the battery from water, select the menu "Protections → Water protection":
233 233  
234 -[[Water protection settings>>image:1732214111990-184.png||data-xwiki-image-style-alignment="center" height="199" width="340"]]
234 +[[image:1732214111990-184.png||data-xwiki-image-style-alignment="center" height="199" width="340"]]
235 235  
236 236  In this section:
237 237  
... ... @@ -263,7 +263,7 @@
263 263  
264 264  To change the test parameters of the current sensor connection circuits, select the menu "Protections → Current sensor error":
265 265  
266 -[[Current sensor error settings>>image:1732214146724-132.png||data-xwiki-image-style-alignment="center" height="438" width="365"]]
266 +[[image:1732214146724-132.png||data-xwiki-image-style-alignment="center" height="438" width="365"]]
267 267  
268 268  In this section:
269 269  
... ... @@ -297,7 +297,7 @@
297 297  
298 298  To change the protection parameters from short circuit, select the menu "Protections → Short circuit protection":
299 299  
300 -[[Short circuit protection settings>>image:1732214207026-822.png||data-xwiki-image-style-alignment="center" height="528" width="371"]]
300 +[[image:1732214207026-822.png||data-xwiki-image-style-alignment="center" height="528" width="371"]]
301 301  
302 302  In this section:
303 303  
... ... @@ -331,7 +331,7 @@
331 331  
332 332  To change the overheating protection parameters of power contactors, select the menu "Protections → Contactor high temperature protection":
333 333  
334 -[[Contactor high temperature protection settings>>image:1732214237851-405.png||data-xwiki-image-style-alignment="center" height="234" width="336"]]
334 +[[image:1732214237851-405.png||data-xwiki-image-style-alignment="center" height="234" width="336"]]
335 335  
336 336  In this section:
337 337  
... ... @@ -365,7 +365,7 @@
365 365  
366 366  To change the parameters of the unallowable charging protection, select the menu "Protections → Unallowable charging protection":
367 367  
368 -[[Unallowable charging protection settings>>image:1732214272022-547.png||data-xwiki-image-style-alignment="center" height="145" width="312"]]
368 +[[image:1732214272022-547.png||data-xwiki-image-style-alignment="center" height="145" width="312"]]
369 369  
370 370  In this section:
371 371  
... ... @@ -395,7 +395,7 @@
395 395  
396 396  To change the protection parameters against sticking, select the menu "Protections → Stuck contactor protection":
397 397  
398 -[[Stuck contactor protection settings>>image:1732214367207-318.png||data-xwiki-image-style-alignment="center" height="152" width="331"]]
398 +[[image:1732214367207-318.png||data-xwiki-image-style-alignment="center" height="152" width="331"]]
399 399  
400 400  In this section:
401 401  
... ... @@ -410,6 +410,10 @@
410 410  
411 411  * charging and discharging contactors are open, but the “Charging current present” or “Discharging current present” signal is set.
412 412  
413 +(% class="box warningmessage" %)
414 +(((
415 +If there is the “Stuck contactor error”, the **“Critical error” **is generated and **all relays open.**
416 +)))
413 413  
414 414  == 3.6.14 Contactor feedback check ==
415 415  
... ... @@ -417,7 +417,7 @@
417 417  
418 418  To change the contactor feedback check parameters, select the menu "Protections → Contactor feedback check":
419 419  
420 -[[Contactor feedback check settings>>image:1732214400721-274.png||data-xwiki-image-style-alignment="center" height="150" width="323"]]
424 +[[image:1732214400721-274.png||data-xwiki-image-style-alignment="center" height="150" width="323"]]
421 421  
422 422  In this section:
423 423  
... ... @@ -430,6 +430,10 @@
430 430  
431 431  * discrete output of charging, precharge, discharging, charging/discharging or main contactor not matches its feedback value.
432 432  
437 +(% class="box warningmessage" %)
438 +(((
439 +If there is the contactor feedback error, the **“Critical error” **is generated and **all relays open.**
440 +)))
433 433  
434 434  == 3.6.15 Charging contactor cycles protection ==
435 435  
... ... @@ -437,7 +437,7 @@
437 437  
438 438  To change the protection parameters against high frequency switching of the charging contactor, select the menu "Protections → Charging contactor cycles protection":
439 439  
440 -[[Charging contactor cycles protection settings>>image:1732214432750-543.png||data-xwiki-image-style-alignment="center" height="260" width="336"]]
448 +[[image:1732214432750-543.png||data-xwiki-image-style-alignment="center" height="260" width="336"]]
441 441  
442 442  In this section:
443 443  
... ... @@ -470,7 +470,7 @@
470 470  
471 471  To change the protection parameters against high frequency switching of the discharging contactor, select the menu "Protections → Discharging contactor cycles protection":
472 472  
473 -[[Discharging contactor cycles protection settings>>image:1732214468462-541.png||data-xwiki-image-style-alignment="center" height="269" width="346"]]
481 +[[image:1732214468462-541.png||data-xwiki-image-style-alignment="center" height="269" width="346"]]
474 474  
475 475  In this section:
476 476  
... ... @@ -503,7 +503,7 @@
503 503  
504 504  To change the protection parameters of the temperature sensors circuits, select the menu "Protections → Temperature sensor error":
505 505  
506 -[[Temperature sensor error settings>>image:1732214501360-654.png||data-xwiki-image-style-alignment="center" height="154" width="334"]]
514 +[[image:1732214501360-654.png||data-xwiki-image-style-alignment="center" height="154" width="334"]]
507 507  
508 508  In this section:
509 509  
... ... @@ -516,7 +516,7 @@
516 516  
517 517  (% class="box warningmessage" %)
518 518  (((
519 -If there is the “No temp. sensors” or “Temp. sensor is shorted” error, **the “Critical error” is generated and all relays open.**
527 +If there is the “No temp. sensors” or “Temp. sensor is shorted” error, the **“Critical error” **is generated and **all relays open.**
520 520  )))
521 521  
522 522  == 3.6.18 Logic high temperature protection ==
... ... @@ -523,7 +523,7 @@
523 523  
524 524  To change the overheating protection parameters of BMS Logic boards, select the menu "Protections → Logic high temperature protection":
525 525  
526 -[[Logic high temperature protection settings>>image:1732214545352-111.png||data-xwiki-image-style-alignment="center" height="156" width="309"]]
534 +[[image:1732214545352-111.png||data-xwiki-image-style-alignment="center" height="156" width="309"]]
527 527  
528 528  In this section:
529 529  
... ... @@ -551,7 +551,7 @@
551 551  
552 552  To change the protection parameters from loss of communication with BMS Logic boards, select the menu "Protections → Logic offline protection":
553 553  
554 -[[Logic offline protection settings>>image:1732214579147-515.png||data-xwiki-image-style-alignment="center" height="107" width="204"]]
562 +[[image:1732214579147-515.png||data-xwiki-image-style-alignment="center" height="107" width="204"]]
555 555  
556 556  In this section:
557 557  
... ... @@ -570,7 +570,7 @@
570 570  
571 571  (% class="box warningmessage" %)
572 572  (((
573 -If there is the "Logic offline" error, **the “Critical error” is generated and all relays open.**
581 +If there is the "Logic offline" error, the **“Critical error”** is generated and **all relays open.**
574 574  )))
575 575  
576 576  == 3.6.20 Cell count protection ==
... ... @@ -577,7 +577,7 @@
577 577  
578 578  To change the protection parameters from the mismatch of the number of cells to the set value, select the menu "Protections → Cell count protection":
579 579  
580 -[[Cell count protection settings>>image:1732214641606-453.png||data-xwiki-image-style-alignment="center" height="178" width="341"]]
588 +[[image:1732214641606-453.png||data-xwiki-image-style-alignment="center" height="178" width="341"]]
581 581  
582 582  In this section:
583 583  
... ... @@ -599,7 +599,7 @@
599 599  
600 600  (% class="box warningmessage" %)
601 601  (((
602 -If there is the "Cell count error",** the “Critical error” is generated and all relays open.**
610 +If there is the "Cell count error",** **the **“Critical error”** is generated and **all relays open.**
603 603  )))
604 604  
605 605  == 3.6.21 Logic count protection ==
... ... @@ -606,7 +606,7 @@
606 606  
607 607  To change the protection parameters from the mismatch of the number of BMS Logic boards to the set value, select the menu "Protections → Logic count protection":
608 608  
609 -[[Logic count protection settings>>image:1732214675358-202.png||data-xwiki-image-style-alignment="center" height="163" width="230"]]
617 +[[image:1732214675358-202.png||data-xwiki-image-style-alignment="center" height="163" width="230"]]
610 610  
611 611  In this section:
612 612  
... ... @@ -627,7 +627,7 @@
627 627  
628 628  (% class="box warningmessage" %)
629 629  (((
630 -If there is the "Logic count error", **the “Critical error” is generated and all relays open.**
638 +If there is the "Logic count error", the **“Critical error” **is generated and **all relays open.**
631 631  )))
632 632  
633 633  == 3.6.22 WDT protection ==
... ... @@ -636,7 +636,7 @@
636 636  
637 637  To change the parameters of the watchdog protection, select the menu "Protections → WDT protection":
638 638  
639 -[[WDT protection settings>>image:1732214703914-144.png||data-xwiki-image-style-alignment="center" height="127" width="323"]]
647 +[[image:1732214703914-144.png||data-xwiki-image-style-alignment="center" height="127" width="323"]]
640 640  
641 641  In this section:
642 642  
... ... @@ -650,7 +650,7 @@
650 650  
651 651  (% class="box warningmessage" %)
652 652  (((
653 -If there is the "WDT reset" error, **the “Critical error” is generated and all relays open.**
661 +If there is the "WDT reset" error, the **“Critical error”** is generated and** all relays open.**
654 654  )))
655 655  
656 656  == 3.6.23 Insulation monitoring ==
... ... @@ -659,7 +659,7 @@
659 659  
660 660  To change the insulation monitoring parameters, select the menu "Protections → Insulation monitoring":
661 661  
662 -[[Insulation monitoring settings>>image:1732214731490-961.png||data-xwiki-image-style-alignment="center" height="162" width="315"]]
670 +[[image:1732214731490-961.png||data-xwiki-image-style-alignment="center" height="162" width="315"]]
663 663  
664 664  In this section:
665 665  
... ... @@ -670,11 +670,16 @@
670 670  
671 671  Error is set if corresponding discrete input is set up and it received logical zero.
672 672  
681 +(% class="box warningmessage" %)
682 +(((
683 +If there is the "Insulation monitoring" error, the **“Critical error”** is generated and** all relays open.**
684 +)))
685 +
673 673  == 3.6.24 Critical error parameters ==
674 674  
675 675  To change the critical error parameters, select the menu "Protections → Critical error parameters":
676 676  
677 -[[Critical error parameters settings>>image:1732214761141-983.png||data-xwiki-image-style-alignment="center" height="158" width="348"]]
690 +[[image:1732214761141-983.png||data-xwiki-image-style-alignment="center" height="158" width="348"]]
678 678  
679 679  In this section:
680 680  
... ... @@ -694,10 +694,13 @@
694 694  * “No temp. sensors”;
695 695  * “Temp. sensor is shorted”;
696 696  * “Current sensor error”;
710 +* "Stuck contactor";
711 +* "Contactor feedback";
697 697  * “Shunt offline”;
698 698  * “Shunt error”;
699 699  * “Settings error”;
700 -* “WDT reset”.
715 +* “WDT reset”
716 +* "Insulation monitoring".
701 701  
702 702  The “Critical error” is cleared if there are no errors from the list above during the “Delay before clearing the error” time.
703 703  
... ... @@ -710,7 +710,7 @@
710 710  
711 711  To change the general error parameters, select the menu "Protections → General error parameters":
712 712  
713 -[[General error parameters settings>>image:1732214987517-111.png||data-xwiki-image-style-alignment="center" height="535" width="349"]]
729 +[[image:1732214987517-111.png||data-xwiki-image-style-alignment="center" height="535" width="349"]]
714 714  
715 715  In this section:
716 716  
... ... @@ -724,13 +724,16 @@
724 724  
725 725  The “General error” is cleared if there are no errors from selected list during the “Delay before clearing the error” time.
726 726  
743 +(% class="box infomessage" %)
744 +(((
727 727  The "General error" is //indicative //and can be linked to any discrete output of the board.
746 +)))
728 728  
729 729  == 3.6.26 Low SOC signal ==
730 730  
731 731  To change the parameters of the generation a signal about low battery level, select the menu "Protections → Low SOC signal":
732 732  
733 -[[Low SOC signal settings>>image:1732215174961-645.png||data-xwiki-image-style-alignment="center" height="186" width="325"]]
752 +[[image:1732215174961-645.png||data-xwiki-image-style-alignment="center" height="186" width="325"]]
734 734  
735 735  In this section:
736 736  
... ... @@ -749,13 +749,16 @@
749 749  
750 750  * the battery SOC is greater than the “Tolerant SOC” during the “Delay before clearing the signal” time.
751 751  
771 +(% class="box infomessage" %)
772 +(((
752 752  The "Low SOC signal" is //indicative //and can be linked to any discrete output of the board.
774 +)))
753 753  
754 754  == 3.6.27 High charging current signal ==
755 755  
756 756  To change the parameters of the generation high-current signal, select the menu "Protections → High charging current signal":
757 757  
758 -[[High charging current signal settings>>image:1732215211714-445.png||data-xwiki-image-style-alignment="center" height="181" width="322"]]
780 +[[image:1732215211714-445.png||data-xwiki-image-style-alignment="center" height="181" width="322"]]
759 759  
760 760  In this section:
761 761  
... ... @@ -774,13 +774,16 @@
774 774  
775 775  * the measured current is less than the “Tolerant charging current” value during the “Delay before clearing the signal” time.
776 776  
799 +(% class="box infomessage" %)
800 +(((
777 777  The "High charging current" signal is //indicative //and can be linked to any discrete output of the board.
802 +)))
778 778  
779 779  == 3.6.28 Heater control ==
780 780  
781 781  To change the parameters of the heater control algorithm, select the menu "Protections → Heater control":
782 782  
783 -[[Heater control settings>>image:1732215252650-791.png||data-xwiki-image-style-alignment="center" height="233" width="370"]]
808 +[[image:1732215252650-791.png||data-xwiki-image-style-alignment="center" height="233" width="370"]]
784 784  
785 785  In this section:
786 786  
... ... @@ -804,7 +804,7 @@
804 804  
805 805  (% class="box infomessage" %)
806 806  (((
807 -If there is the "Heater" signal, the heater relay closes and/or a signal is output to the corresponded digital output.
832 +If there is the "Heater" signal, the **heater **relay closes and/or a signal is output to the corresponded digital output.
808 808  )))
809 809  
810 810  == 3.6.29 Heater (AUX) control ==
... ... @@ -811,7 +811,7 @@
811 811  
812 812  To change the parameters of the auxiliary heater control algorithm, select the menu "Protections → Heater (AUX) control":
813 813  
814 -[[Heater (AUX) control settings>>image:1732215282135-420.png||data-xwiki-image-style-alignment="center" height="228" width="361"]]
839 +[[image:1732215282135-420.png||data-xwiki-image-style-alignment="center" height="228" width="361"]]
815 815  
816 816  In this section:
817 817  
... ... @@ -835,7 +835,7 @@
835 835  
836 836  (% class="box infomessage" %)
837 837  (((
838 -If there is the "Heater (AUX)" signal, the auxiliary heater relay closes and/or a signal is output to the corresponded digital output.
863 +If there is the "Heater (AUX)" signal, the **auxiliary heater **relay closes and/or a signal is output to the corresponded digital output.
839 839  )))
840 840  
841 841  == 3.6.30 Cooler control ==
... ... @@ -842,7 +842,7 @@
842 842  
843 843  To change the parameters of the cooler control algorithm, select the menu "Protections → Cooler control":
844 844  
845 -[[Cooler control settings>>image:1732215313977-499.png||data-xwiki-image-style-alignment="center" height="219" width="348"]]
870 +[[image:1732215313977-499.png||data-xwiki-image-style-alignment="center" height="219" width="348"]]
846 846  
847 847  In this section:
848 848  
... ... @@ -866,7 +866,7 @@
866 866  
867 867  (% class="box infomessage" %)
868 868  (((
869 -If there is the "Cooler" signal, the cooler relay closes and/or a signal is output to the corresponded digital output.
894 +If there is the "Cooler" signal, the **cooler **relay closes and/or a signal is output to the corresponded digital output.
870 870  )))
871 871  
872 872  == 3.6.31 Fault simulation ==
... ... @@ -875,41 +875,6 @@
875 875  
876 876  To simulate battery and BMS errors, select the menu "Protections → Fault simulation":
877 877  
878 -[[Fault simulation settings>>image:1732215359330-850.png||data-xwiki-image-style-alignment="center" height="732" width="204"]]
903 +[[image:1732215359330-850.png||data-xwiki-image-style-alignment="center" height="732" width="204"]]
879 879  
880 -In this section:
881 -
882 -* Overcurrent;
883 -* Undervoltage;
884 -* Overvoltage;
885 -* Low CH temperature;
886 -* Low DCH temperature;
887 -* High CH temperature;
888 -* High DCH temperature;
889 -* Battery cover error;
890 -* High humidity;
891 -* Water;
892 -* Current sensor error;
893 -* Short circuit;
894 -* Contactor high temperature;
895 -* Unallowable charging;
896 -* Stuck contactor;
897 -* CH contactor feedback error;
898 -* DCH contactor feedback error;
899 -* PCH contactor feedback error;
900 -* CH/DCH contactor feedback error;
901 -* Main contactor feedback error;
902 -* CH contactor cycles error;
903 -* DCH contactor cycles error;
904 -* Logic high temperature;
905 -* Logic offline;
906 -* Cell count error;
907 -* Logic count error;
908 -* Insulation error;
909 -* Critical error;
910 -* Low SOC;
911 -* High charging current;
912 -* Heater;
913 -* Cooler.
914 -
915 915  To simulate errors, set the necessary flags and click on the "Save" button.